4.1 Fundamental Requirements
4.1.1 The objective of installing air conditioning, heating and mechanical ventilation in buildings shall be to provide comfortable conditions without compromising on health and safety of occupants.
4.1.2 Air conditioning, heating and mechanical ventilation installation shall aim at controlling and optimizing the following factors in the building:
a) Air quality
b) Air movement,
c) Dry-bulb temperature,
d) Relative humidity,
e) Noise and vibration,
f) Energy efficiency, and
g) Fire safety.
4.1.3 All plans, design drawings, specifications and data for air conditioning, heating and mechanical ventilation systems of all buildings and serving all occupancies within the scope of the Code, shall be supplied to the Authority, where called for (see Part 2 ‘Administration’ of the Code).
4.1.4 The plans and design drawings for air conditioning, heating and mechanical ventilation (HVAC) systems shall include all details and data necessary for review of installation such as,
a) building: name, type and location;
b) owner: name;
c) use of building;
d) orientation: north direction on plans and design drawings;
e) general plans: dimensions and height of all rooms;
f) intended use of internal spaces;
g) detail or description of wall construction, including insulation and finish;
h) detail or description of roof, ceiling and floor construction, including insulation and finish;
j) detail or description of windows and outside doors, including sizes, weather stripping, storm sash, sills and storm doors;
k) internal load, such as people, equipment, computer/server load and lighting load;
m) layout showing the location, size and components of the HVAC equipment being installed;
n) information regarding air distribution system;
12
p) information on air and water flow rates;
q) information regarding location, size and accessibility of shafts;
r) information regarding type and location of dampers (both volume control and fire/smoke dampers) used in air conditioning system, such as, whether motorized or manually operated;
s) location and grade of the required fire separations;
t) water softening arrangement; and
u) Information on presence of any chemical fumes or gases.