1.1 This Code (Part 9/Section 2) covers the design, layout, construction and maintenance of drains for foul water, surface water, subsoil water and sewage together with all ancillary works, such as connections, manholes and inspection chambers used within the building and from building to the connection to a public sewer, private sewer, individual sewage-disposal system, cess-pool, soakaway or to other approved point of disposal/treatment work.
NOTE — A sanitary drainage system consists of a building sewer, a building drain, a soil and/or waste stack, horizontal branches or fixture drain, and vents. The sanitary drainage of a large building may have a number of primary and secondary branches, and several soil and/or waste stacks, each of them in turn may have a number of horizontal branches.
2.91Systems of Drainage
a) Combined system — A system in which foul water (sewage) (black and grey water) and surface water are conveyed by the same sewers and drains.
b) Separate system — A system in which foul water (sewage) (black and grey water) and surface water are conveyed by the separate sewers and drains.
c) Partially separate system — A modification
of the separate system in which part of the surface water is conveyed by the foul (sanitary) sewers and drains.
2.92 Trade Effluent — Any liquid either with or without particles of matter in suspension which is wholly or in part produced in the course of any trade or industry, at trade premise. It includes farm wastes but does not include domestic sewage.
2.93 Trap — A fittings or device so designed and constructed as to provide, when properly vented, a
NATIONAL BUILDING CODE OF INDIA 2016
liquid seal which will prevent the back passage of air without materially affecting the flow of sewage or waste water through it.
2.94 Vertical Pipe — Any pipe or fitting which is installed in a vertical position or which makes an angle or not more than 45° with the vertical.
2.95 Vent Stack/Vent Pipe — A vertical vent-pipe installed primarily for the purpose of proving circulation of air to and from any part of the drainage system. It also protects trap seals from excessive pressure fluctuation.
2.96 Vent System — A pipe or pipes installed to provide a flow of air to or from a drainage system or to provide a circulation of air with in such system to protect traps seals from siphonage and back-pressure.
2.97 Waste Appliance — A sanitary appliance for the collection and discharge of water after use for ablutionary, culinary and other domestic purpose.
2.98 Waste Pipe — In plumbing, any pipe that receives the discharge of any fixtures, except water closets or similar fixtures and conveys the same to the house drain or soil or waste stack. When such pipe does not connect directly with a house drain or soil stack, it is called an indirect waste pipe.
2.99 Waste Water (Sullage) — The discharge from wash basins, sinks and similar appliances, which does not contain human or animal excreta.
2.100 Water Closet — A water flushed plumbing fixture designed to receive human excrement directly from the user of the fixture. The term is used sometimes to designate the room or compartment in which the fixture is placed.
2.101 Water Seal — The water in a trap, which acts as a barrier to the passage of air through the trap.
3GENERAL
2Terminology
For the purpose of this Section, the following definitions shall apply in addition to the definitions given in accepted standards [9-2(1)].
2.1 Air Admittance Valve — One way valves designed to allow air to enter drainage system when negative pressure develops in the system. The purpose is to provide a method of allowing air to enter the drainage system for prevention of siphonage of traps.
2.2 Air Break — Physical separation which may be a low inlet into the indirect waste receptor from the fixture or device indirectly connected.
2.3 Air Gap, Drainage — Unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe, plumbing fixture or appurtenance conveying waste to flood level of the receptor.
2.4 Back Up — A condition where the waste water may flow back into another fixture or compartment but not back into the potable water system.
2.5 Back Water Valve — Device installed in a drainage system to prevent reverse flow.
2.6 Bath Room Group — Group of fixtures consisting of water closet, lavatories bath tub or shower and other fittings with a floor drain located together.
2.7 Battery of Fixtures — Any group of two or more similar adjacent fixtures which discharge into a common horizontal waste or soil pipe.
2.8 Bed Pan Washer — A washer which is to be used for disposing human waste and sterilizing the Bed Pan for reuse. Bed pan washer requires water connection and electrical heating arrangement. This is to be considered as soil appliance.
2.9 Benching — Sloping surfaces constructed on either side of channels at the base of a manhole or inspection chamber for the purpose of confining the flow of sewage, avoiding the accumulation of deposits and providing a safe working platform.
3.1Basic Principles
The basic principles of water supply, drainage and sanitation are given below, and the design of drainage and sanitation should in general be guided by the applicable principles.
3.1.1 Potable Water
All premises intended for human habitation, occupancy, or use shall be provided with supply of potable water. This water supply shall not be connected with unsafe water resources, nor shall it be subject to the hazards of backflow.
3.1.2 Water Provision
Plumbing fixtures, devices and appurtenances shall be
provided with water in sufficient volume and at pressures adequate to enable them to function properly and without undue noise under normal conditions of use.
There should be at least a residual head of 0.018N / mm² at the consumer's tap. There may be certain fixtures or appliances in the installation that may require a higher pressure, such as 0.05N / mm² or even higher (such as 0.1N / mm² in case of flush valves), in which case the system shall be designed using pumps, tanks or both to achieve the required minimum pressure.
NOTE — The residual head shall be taken at the highest/farthest outlets in the building.
3.1.3 Water Efficiency
Plumbing system shall be designed, installed and adjusted to use the optimum quantity of water consistent with proper performance and cleaning.
3.1.4 Safety Devices
Plumbing system shall be designed and installed with safety devices to safeguard against dangers from contamination, explosion, overheating, etc.
3.1.5 Minimum Amenities
Each dwelling unit on premises (abutting on a sewer or with a private sewage disposal system) shall have at least one water closet, one kitchen wash place or a sink, and one bathing place or shower to meet the basic requirements of sanitation and personal hygiene.
In case of a group housing, the requirements relating to toilet or sanitary room and kitchen as given in 13 and B-9 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code shall also be complied with.
3.1.6 Drainage System
The drainage system shall be designed, installed and maintained to guard against fouling, deposit of solids and clogging and with adequate cleanouts so arranged that the pipes may be readily cleaned.
3.3Licensing/Registration of Plumbers
3.3.1 Execution of Work
The work which is required to be carried out under the provisions of this section, shall be executed only by a licensed/registered plumber under the control of the Authority and shall be responsible to carry out all lawful directions given by the Authority. No individual shall engage in the business of plumbing unless so licensed/registered under the provisions of this Section.
3.3.1.1 No individual, firm, partnership or corporation shall engage in the business of installing, repairing or altering plumbing unless the plumbing work performed in the course of such business is under the direct supervision of a licensed/registered plumber from approved Authority.
3.3.2 Examination and Certification
The Authority shall establish standards and procedure for the qualification, examination and licensing/registration of plumbers and shall issue licences to such persons who meet the qualifications thereof and successfully pass the examination.
3.3.3 For guidelines for registration of plumbers including the minimum standards for qualifications for the grant of licences, reference may be made to good practice [9-2(2)] . The Authority may also utilize the services of the certified plumbers who are certified for the required skill level under the appropriate scheme of the Government.
4Drainage and Sanitation
4.1 Types of Sanitary Appliances
4.1.1 Soil Appliances
4.1.1.1 Water closet
It shall essentially consist of a closet consisting of a bowl to receive excretory matter, trap and a flushing apparatus. It is recommended to provide ablution tap adjacent to the water closet, preferably on right hand side wall. The various types/style of water closets may be:
a) Squatting Indian type water closet,
b) Washdown type water closet,
c) Siphonic washdown type water closet, and
d) Universal or Anglo-Indian water closet.
4.1.1.2 Bidet
Bidet is an ablution appliance for cleansing excretory organs with water for personnel hygiene. It may be pedestal type or wall hung with a shallow bowl. Hot and cold water supplied through a mixer is discharged from a spray installed over the rim of the appliance. The bidet outlet should essentially connect to soil pipe in a system.
4.1.1.3 Urinal
It is a soil appliance for urination and is connected to soil pipe after a suitable trap. Urinal should have adequate provision of flushing apparatus. The various types/style of urinal may be:
a) Bowl type urinal: flat back or angle back.
b) Slab (single) type urinal.
c) Stall (single) type urinal.
d) Squatting plate type urinal.
e) Syphon jet urinal with integral trap.
f) Water less (non-water) urinal
4.1.1.4 Slop sink
Slop sink is a large sink, generally of square shape. the appliance is used in hospitals and is installed in the dirty utility room, sluice room and similar locations for disposal of excreta and other foul waste and for washing bed pans and urine bottles/pans. It is provided with a flushing mechanism. It is also provided in Janitor's closet where it is used for cleaning the housekeeping mops, etc.
4.1.1.5 Bed pan sink
Bed pan sink, also known as bedpan washer and disinfector, is a part of medical equipment inventory which is used to clean manually or automatically, the hospital bedpans, urine bottles and other containers used for collecting body fluids. It is provided in dirty utility room, sluice room, similar locations for disposal of excreta and other foul waste and for washing bed pans, urine bottles/pans. It is a soil appliance and is connected to soil pipe after a suitable trap. In manual models, it has a flushing arrangement.
Part 9 Section 2Drainage and Sanitation
Various tables on the requirements for fitments for drainage and sanitation for various occupancies have been updated, and a new table for shopping malls and retail buildings has been included.
Enabling provisions for use of corrugated pipes, low noise pipes and under slung pipes have been included.
Information about bio-toilets has been added.
Typical mounting arrangements for various plumbing fixtures, including drainage systems and ventilation have been illustrated.
A new table for calculation of single stack sizing has been included.
Various additional requirements relating to layout of drainage and sanitation system have been added.
Venting system for high rise buildings, along with a comprehensive table on size and developed length of stack vents and vent stacks, has been included.
General provisions on design of drainage pipes have been elaborated.
Provisions relating to gradients of drainage pipes have been elaborated.
The table on fixture unit for different types of fixtures has been updated.
The tables on maximum number of fixture units that can be connected to branches and stacks, and to building drains and sewers, have been updated.
New provisions on design requirement for high rise buildings drainage system have been included.
The minimum diameter for floor drains outlets before connecting to floor trap has been included.
Provisions related to manhole covers and recommended locations have been included.
Provision for estimation of storm water runoff and coefficient of runoff for various surfaces have been included.
The table on sizing of rainwater pipes for roof drainage has been updated.
The illustration on artificial ground water recharge structure has been detailed.
Guidelines relating to siphonic drainage system for large roofs have been included.
Provisions on rainwater harvesting for plotted/group housing developments and deep well/bore well recharging, have been included.
Clarifications and recommendations on use of septic tanks have been made.
3.2Drainage and Sanitation
3.2.1 Preparation and Submission of Plan
No person shall install or carry out any water-borne sanitary installation or drainage installation or any works in connection with anything existing or new buildings or any other premises without obtaining the prior sanction of the Authority.
The owner shall make an application in the prescribed form (see Annex A) to the Authority to carry out such a work.
3.2.2 Site Plan
A site plan of the premises on which the building is to be situated or any such work is to be carried out shall be prepared drawn to a scale not smaller than 1 in 500 (see Part 2 ‘Administration’ of the Code). The site plan of the building premises shall show,
a) the adjoining plots and streets with their names;
b) the position of the municipal sewer and the direction of flow in it;
c) the invert level of the municipal sewer, the road level, and the connection level of the proposed drain connecting the building in relation to the sewer,
d) the angle at which the drain from the building joints the sewer; and
e) the alignment, sizes and gradients of all drains and also of surface drains, if any.
A separate site plan is not necessary if the necessary particulars to be shown in such a site plan are already shown in the drainage plan.
3.2.3 Drainage Plan
The application (see 3.3.1) shall be accompanied by a drainage plan drawn to a scale of not smaller than 1 in 100 and furnished along with the building plan (see Part 2 ‘Administration’ of the Code). The plans shall show the following:
14
a) Every floor of the building in which the pipes or drains are to be used;
b) The position, forms, level and arrangement of the various parts of such building, including the roof thereof;
c) All new drains as proposed with their sizes and gradients;
d) Invert levels of the proposed drains with corresponding ground levels;
e) The position of every manhole, gully, soil and waste pipe, vent pipe, rainwater pipe, water closet, urinal, latrine, bath, lavatory, sink, trap or other appliances in the premises proposed to be connected to any drain and the following colours are recommended for indicating sewers, waste water pipes, rainwater pipes an existing work:
4.3Materials, Fittings and Appliances
4.3.1 Standards for Materials, Fittings and Sanitary Appliances
All materials, fittings and sanitary appliances shall conform to Part 5 ‘Building Materials’ of the Code.
4.3.2 Choice of Material for Pipes
4.3.2.1 Salt glazed stoneware pipe
For all sewers and drains in all soils, except where supports are required as in made-up ground, glazed stoneware pipe shall be used as far as possible in preference to other types of pipes. These pipes are particularly suitable where acid effluents or acid subsoil conditions are likely to be encountered. Salt glazed stoneware pipes shall conform to accepted standards [9-2(4)].
4.3.2.2 Cement concrete pipes
When properly ventilated, cement concrete pipes with spigot and socket or collar joints present an alternative to glazed stoneware sewers of over 150mm diameter.
These shall not be used to carry acid effluents or sewage under conditions favourable for the production of hydrogen sulphide and shall not be laid in those subsoils that are likely to affect adversely the quality or strength of concrete. Where these pipes are employed for conveying liquid containing sulphates, the pipes used shall be manufactured using sulphate resisting Portland cement. Owing to the longer lengths of pipes available, the joints would be lesser in the case of cements concrete pipes. These pipes may be used for surface water drains in all diameters. Cement concrete pipes shall conform to accepted standards [9-2(5)] .
4.3.2.3 Cast iron pipes
4.3.2.3.1 These pipes shall be used in the following situation:
a) In bed or unstable ground where soil movement is expected;
b) In made-up or tipped ground;
c) To provide for increased strength where a sewer is laid at insufficient depth, where it is exposed or where it has to be carried on piers or above ground;
d) Under buildings and where pipes are suspended in basements and like situations;
e) In reaches where the velocity is more than 2.4m / s; and
f) For crossings of watercourses.
NOTE — In difficult foundation condition such a in the case of black cotton soil, the cast iron pipes shall be used only when suitable supporting arrangements are made.
4.3.2.3.2 It shall be noted that cast iron pipes even when given a protective paint are liable to severe external corrosion in certain soils; among such soils are:
3.1.7 Materials and Workmanship
The plumbing system shall have durable material, free from defective workmanship and so designed and installed as to give satisfactory service for its reasonable expected life. The accessories of the plumbing system should be of such specifications as to meet the functional requirements of the installation, so as to also avoid any inconsistency leading to leakage and resultant seepage.
3.1.8 Fixture Traps and Vent Pipes
Each fixture directly connected to the drainage system shall be equipped with a liquid seal trap. Trap seals shall be maintained to prevent sewer gas, other
potentially dangerous or noxious fumes, or vermin from entering the building. Further, the drainage system shall be designed to provide an adequate circulation of air in all pipes with no danger of siphonage, aspiration, or forcing of trap seals under conditions of ordinary use by providing vent pipes throughout the system.
3.1.9 Foul Air Exhaust
Each vent terminal shall extend to the outer air and be so installed as to minimize the possibilities of clogging and the return of foul air to the building, as it conveys potentially noxious or explosive gases to the outside atmosphere. All vent pipes shall be provided with a cowl.
3.1.10 Testing
The plumbing system shall be subjected to required tests to effectively disclose all leaks and defects in the work or the material.
3.1.11 Exclusion from Plumbing System
No substance that will clog or accentuate clogging of pipes, produce explosive mixtures, destroy the pipes or their joints, or interfere unduly with the sewage-disposal process shall be allowed to enter the drainage system.
3.1.12 Light and Ventilation
Wherever water closet or similar fixture is located in a room or compartment, it should be properly lighted and ventilated.
3.1.13 Individual Sewage Disposal Systems
If water closets or other plumbing fixtures are installed in buildings where connection to public sewer is not possible, suitable provision shall be made for acceptable treatment and disposal.
3.1.14 Maintenance
Plumbing systems shall be maintained in a safe and serviceable condition.
3.1.15 Approach for Use and Cleaning
All plumbing fixtures shall be so installed with regard to spacing as to be approachable for their intended use and for cleaning. All doors, windows and any other device needing access within the toilet shall be so located that they have proper approach.
3.1.16 Accessibility for Persons with Disabilities
All doors, windows and fixtures, including WC, urinals, grab bars, wash basin, mirror and all other accessories for use by persons with disabilities shall be so installed/located that they have proper access with appropriate width, height, space, centerlines, and ease of operation
(see 13 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code).
3.1.17 Structural Safety
Plumbing system shall be installed with due regard to preservation of the structural members and prevention of damage to walls and other surfaces.
3.1.18 Protection of Ground and Surface Water
Sewage or other waste shall not be discharged into surface or sub-surface water without acceptable form of treatment.
Provision for installing a bedpan washer and disinfector should be made in all intensive care units in hospitals.
4.1.2 Waste Appliances
4.1.2.1 Wash basin
It is of one-piece construction having a combined overflow and preferably should have soap holding recess or recesses that should properly drain into the bowl. Each basin shall have circular waste hole through which the liquid content of the basin shall drain.
4.1.2.2 Wash-trough
It is a linear trough for simultaneous use by number of persons.
4.1.2.3 Sink
It is used in kitchen and laboratory for the purpose of cleaning utensils/ apparatus and also serve the purpose of providing water for general usage. The sink may be made with or without overflow arrangement. The sink shall be of one-piece construction including combined over flow, where provided. The sink shall have a circular waste hole into which the interiors of the sink shall drain.
4.1.2.4 Bath tub
Bath tub may be of enameled steel, cast iron, gel-coated, glass fibre reinforced plastic or may be cast in-situ. It shall be stable, comfortable, easy to get in and out, water tight, with anti-skid base, and easy to install and maintain. The bath tub shall be fitted with overflow and waste pipe of nominal diameter of not less than 32 mm and 40 mm, respectively.
4.1.2.5 Drinking fountain
It is a bowl fitted with a push button tap and a water bubbler or a tap with a swan neck outlet fitting. It has a waste fitting, a trap and is connected to the waste pipe.
4.1.3 The requirements of various soil appliances and waste appliances shall be in accordance with accepted standards [9-2(3)].
New provisions related to pumping and treatment of sewage have been included.
A provision on treatment of waste water and usage of recycled water has been included through cross-reference to Section 1 ‘Water supply’ of this Part of the Code.
Provisions have been reviewed and updated from the point of view of accessibility by elderly and persons with disabilities, also, in this context, duly giving cross-reference to 13 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code.
Certain terminologies have been included and some have been updated.
Cross-referred standards have been updated.
This Section is largely based on the following Indian Standards:
IS 1742 : 1983 Code of practice for building drainage (second revision)
IS 4111 (Part 1): 1986 Code of practice for ancillary structures in sewage system: Part 1 Manholes (first revision)
IS 5329 : 1983 Code of practice for sanitary pipe work above ground for buildings (first revision)
IS 6295 : 1986 Code of practice for water supply and drainage in high altitudes and or sub-zero temperature regions (first revision)
A reference to SP 35:1987 ‘Handbook on Water Supply and Drainage’ may be useful, from where also, assistance has been derived.
All standards, whether given herein above or cross-referred to in the main text of this Section, are subject to revision. The parties to agreement based on this section are encouraged to investigate the possibility of applying the most recent editions of the standards.
In the formulation of this Section, reference has also been made to the following:
International Plumbing Code 2015, International Code Council, and
Uniform Plumbing Code 2015, International Association of Plumbing and Mechanical Officials
Description of Work
Colour
Sewers
Red
Waste water pipes and rainwater pipes
Blue
Existing work
Black
f) The position of refuse chute, inlet hopper and collection chamber.
3.2.3.1 In the case of an alteration or addition to an existing building, this clause shall be deemed to be satisfied if the plans as furnished convey sufficient information for the proposals to be readily identified with previous sanctioned plans and provided the locations of tanks and other fittings are consistent with the structural safety of the building.
3.2.3.2 The plans for the building drainage shall in every case be accompanied by specifications for the various items of work involved. This information shall be supplied in the prescribed form given in Annex B.
3.2.4 In respect of open drains, cross-sectional details shall be prepared to a scale not smaller than 1 in 50 showing the ground and invert levels and any arrangement already existing or proposed for the inclusion of any or exclusion of all storm water from the sewers.
3.2.5 Completion Certificate
At the completion of the plumbing installation work, the licensed/registered plumber shall give a completion certificate in the prescribed form, which is given in Annex C.
a) Soils permeated by peaty waters; and
b) Soils in which the subsoil contains appreciable concentrations of sulphates. Local experiences shall be ascertained before cast iron pipes are used where corrosive soil conditions are suspected. Where so used, suitable measures for the protection of the pipes may be resorted to as an adequate safeguard.
4.3.2.3.3 Cast iron pipes shall conform to accepted standards [9-2(6)].
4.3.2.4 Asbestos cement pipes
Asbestos cement pipes are commonly used for house drainage systems and they shall conform to accepted standards [9-2(7)]. They are not recommended for underground situations. However, asbestos cement pressure pipes conforming to accepted standards [9-2(7)] may be used in underground situations also, provided they are not subject to heavy superimposed
loads. These shall not be used to carry acid effluents or sewage under conditions favourable for the production of hydrogen sulphide and shall not be laid in those subsoils which are likely to affect adversely the quality or strength of asbestos cement pipes. Where so desired, the life of asbestos cement pipes may be increased by lining inside of the pipe with suitable coatings like epoxy/polyester resins, etc.
4.3.2.5 PVC pipes
Unplasticized PVC pipes may be used for drainage purposes; however, where hot water discharge is anticipated, the wall thickness shall be minimum 3 mm irrespective of the size and flow load.
PVC and HDPE pipes shall conform to accepted standards [9-2(8)].
NOTE — Where possible, high density polyethylene pipes (HDPE) and PVC pipes may be used for drainage and sanitation purposes, depending upon the suitability.
4.3.2.6 Corrugated pipes
These pipes (externally corrugated) are used for sewerage and drainage applications. They are light weight and have long life. The leakage and infiltration at joints are less. The operational cost is low and can easily withstand natural settlements without suffering cracks or leakages. They consume fewer raw material and have less carbon dioxide emission.
4.3.2.7 Low noise pipes
Waste water systems encompass the system of drainage and pressure relief pipes within a building and terminate 0.5 m outside the external wall. Waste water systems are based on the primary pressure-relief system in which water and air-flow occurs in the same pipe. The waste water system shall be separated from the roof drainage system.
Noise is a variance in air pressure that spreads like a wave. If quick changes in pressure occur between 20 and 20 000 times a second (frequency 20 Hz and 20 kHz), they are audible to humans. The loudness of noise is determined by the amplitude of the wave, which is measured in decibels (dB).
The main cause of noise in indoor drainage systems (primarily focused on the downpipe) are the choice of the pipe system, the bracket type and the design of drainage system. Optimizing these factors will therefore have the best influence on noise reduction.
4.3.2.8 Under slung pipes
In under slung plumbing, the toilet slab is built at the same level as the slabs outside the toilet. Holes/core cuts are punctured through the slab wherever pipes have to pass through, and the plumbing is clamped to the
bottom of the slab. It is then concealed above a false ceiling, which is accessible above the false ceiling for routine maintenance. In this type of plumbing, any leaks will drip onto the false ceiling which is easily detectable thus allow quick maintenance without much damage to the structure or occupied premises
4.2Drainage and Sanitation Requirements
4.2.1 General
There should be at least one water tap and arrangement for drainage in the vicinity of each water closet or group of water closet in all the buildings.
4.2.2 Each dwelling unit on premises (abutting on a sewer or with a private sewage disposal system) shall have at least one water closet, one kitchen wash place or a sink, and one bathing place or shower to meet the basic requirements of sanitation and personal hygiene.
In case of a group housing, the requirements relating to toilet or sanitary room and kitchen as given in 13 and B-9 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code shall also be complied with.
4.2.3 All other structures for human occupancy or use on premises (abutting on a sewer or with a private sewage disposal system) shall have adequate sanitary facilities, but in no case less than one water closet and one other fixture for cleaning purposes.
16
Table 1 Office Building(Clause 4.2.5.1)
Sl No.
Fixtures
Public Toilets
Staff Toilets
Males(3)
Females(4)
Males(5)
Females(6)
(1)
(2)
Executive Rooms and Conference Halls in Office Buildings
i)
Toilet suite comprising one WC, one wash basin (with optional shower stall if building is used round the clock at user's option)
Unit could be common for male/female or separate depending on the number of user of each facility
For individual officer rooms
Pantry optional as per user requirement
Main Office Toilets for Staff and Visitors
ii)
Water closets
See Note
1 per 25
1 per 15
iii)
Ablution tap with each water closet
←
1 in each water closet
iv)
Urinals
See Note
—
Nil up to 61 for 7 to 202 for 21 to 453 for 46 to 704 for 71 to 100From 101 to 200, add @ 3%For over 200, add @ 2.5%
—
v)
Wash basins
See Note
1 per 25
1 per 25
vi)
Drinking water fountain
See Note
1 per 100
1 per 100
vii)
Cleaner's sink
←
1 per floor
NOTE — Staff and public toilet utilities are generally common in office buildings. Where public toilets are to be provided independently, similar requirements as that of staff toilet may be provided.
4.2.4 For Residences
4.2.4.1 Dwelling with individual convenience shall have at least the following fitments:
a) One bath room provided with a tap and a floor trap;
b) One water closet with flushing apparatus with an ablution tap; and
c) One tap with a floor trap or a sink in kitchen or wash place.
4.2.4.1.1 Where only one water closet is provided in a dwelling, it is desirable to have the bath and water closet separately accommodated.
4.2.4.2 Dwellings without individual conveniences shall have the following fitments:
a) One water tap with floor trap in each tenement,
b) One water closet with flushing apparatus and one ablution tap bath for every two tenements, and
c) One bath with water tap and floor trap for every two tenements.
4.2.5 For Buildings Other than Residences
4.2.5.1 The requirements for fitments for drainage and sanitation in the case of buildings other than residences shall be in accordance with Table 1 to Table 15.
The accessibility requirements for provision of these facilities for persons with disabilities shall be in accordance with 13 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code.
The following shall be, in addition, taken into consideration:
a) The figures shown are based upon one (1) fixture being the minimum required for the number of persons indicated or part thereof.
b) Building categories not included in the tables shall be considered separately by the Authority.
c) Drinking fountains shall not be installed in the toilets.
d) Where there is the danger of exposure to skin contamination with poisonous, infectious or irritating material, wash basin with eye wash jet and an emergency shower (safety shower with eye wash unit) located in an area accessible at all times with the passage/right of way suitable for access to a wheel chair, shall be provided.
e) When applying the provision of these tables for providing the number of fixtures, consideration shall be given to the accessibility of the fixtures. Using purely numerical basis may not result in an
Table 2 Factories(Clause 4.2.5.1)
Sl No.
Fixtures
Offices/Visitors
Workers
Males(3)
Females(4)
Males(5)
Females(6)
i)
Water closets (workers and staff)
1 for up to 25
1 for up to 15
1 for up to 15
1 for up to 12
2 for 26 to 35
2 for 16 to 25
2 for 16 to 35
2 for 13 to 25
3 for 36 to 65
3 for 26 to 40
3 for 36 to 65
3 for 26 to 40
4 for 66 to 100
4 for 41 to 57
4 for 66 to 100
4 for 41 to 57
5 for 58 to 77
5 for 58 to 77
6 for 78 to 100
6 for 78 to 100
For persons 101-200 add
3%
5%
3%
5%
For persons over 200 add
2.5%
4%
2.50%
4%
ii)
Ablution tap
1 in each water closet
1 in each water closet
1 in each water closet
1 in each water closet
iii)
Urinals
Nil up to 6
—
Nil up to 6
—
1 for 7 to 20
1 for 7 to 20
2 for 21 to 45
2 for 21 to 45
3 for 46 to 70
3 for 46 to 70
4 for 71 to 100
4 for 71 to 100
From 101 to 200, add@ 3%
From 101 to 200,add @ 3%
For over 200,add @ 2.5%
For over 200,add @ 2.5%
iv)
Wash basins
1 per 25 or part thereof
1 per 25 or part thereof
1 per 25 or part thereof
1 per 25 or part thereof
Wash basins in rows or troughs and taps spaced 750 mm c/c
v)
Drinking water fountain
1 per every 100 or part thereof with minimum one on each floor
1 per every 100 or part thereof with minimum one on each floor
vi)
Cleaner's sink
1 on each floor
1 on each floor
1 on each floor
1 on each floor
vii)
Showers/bathing rooms
As per trade requirements
viii)
Emergency shower and eye wash fountain
—
—
1 per every shop floor
per 500 persons
NOTES
1 For factories requiring workers to be engaged in dirty and dangerous operations or requiring them to being extremely clean and sanitized conditions additional and separate (if required so) toilet facilities and if required by applicable Industrial and safety laws and the Factories Act shall be provided in consultation with the user.
2 Depending on the type of disability of a person and the hazard posed by the type of activities in the factory for a person with disabilities, if a person with disabilities is decided to be engaged for a particular activity, the requirements of accessibility shall be guided by the provisions given in 13 of Part 3 ‘Development Control Rules and General Building Requirements’ of the Code.
Table 3Cinema, Multiplex Cinema, Concert and Convention Halls, Theatres and Stadia (Clause 4.2.5.1)
Sl No.
Fixtures
Public
Staff
Males(3)
Females(4)
Males(5)
Females(6)
i)
Water closets
1 per 100 up to 400Over 400 add at 1 per 250 or part thereof
3 per 100 up to 200Over 200 add at 2 per 100 or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
ii)
Ablution tap
1 in each water closet
1 in each water closet
1 in each water closet
1 in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
1 per 25 or part thereof
—
Nil up to 61 for 7 to 202 for 21 to 45
—
iv)
Wash basins
1 per 200 or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
v)
Drinking water fountain
1 per 100 persons or part thereof
vi)
Cleaner's sink
1 per floor
vii)
Showers/bathing rooms
As per trade requirements
NOTES
1 Some WCs may be Indian style, if desired.2 Male population may be assumed as two-third and female population as one-third.
Table 4Art Galleries, Libraries and Museums (Clause 4.2.5.1)
Sl No.
Fixtures
Public
Staff
Males(3)
Females(4)
Males(5)
Females(6)
i)
Water closets
1 per 200 up to 400Over 400 add at 1 per 250 or part thereof
1 per 100 up to 200Over 200 add at 1 per 150 or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
1 per 50
—
Nil up to 61 per 7 to 202 per 21 to 45
—
iv)
Wash basins
1 for every 200 or part thereof. For over 400, add at 1 per 250 persons or part thereof
1 for every 200 or part thereof. For over 200, add at 1 per 150 persons or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
v)
Drinking water fountain
1 per 100 persons or part thereof
vi)
Cleaner's sink
1 per floor (Minimum)
vii)
Showers/bathing rooms
As per requirements
1 Some WCs may be Indian style, if desired.
2 Male population may be assumed as two-third and female population as one-third.
Table 5 Hospitals with Indoor Patient Wards(Clause 4.2.5.1)
Sl No.
Fixtures
Patient Toilets
Staff Toilets
Males(3)
Females(4)
Males(5)
Females(6)
i)
Toilet suite comprising one WC and one wash basin and shower stall
Private room with up to 4 patients
For individual doctor's/officer's rooms
ii)
For General Wards, Hospital Staff and Visitors
Water closets
1 per 5 beds or part thereof
1 per 5 beds or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
iii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iv)
Urinals
1 per 15 beds
—
Nil up to 61 for 7 to 202 for 21 to 45
—
v)
Wash basins
2 for every 30 beds or part thereof. Add 1 per additional 30 beds or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
vi)
Drinking water fountain
1 per ward
1 per 100 persons or part thereof
vii)
Cleaner's sink
1 per ward
—
viii)
Bed pan sink
1 per ward
—
ix)
Kitchen sink
1 per ward
—
NOTES
1
Some WCs may be of Indian style, if desired.
2
Male population may be assumed as two-third and female population as one-third.
3
Provision for additional and special hospital fittings where required shall be made.
4
Drinking water fountains are not recommended for hospitals for reasons of infection control. This is to be decided by the health authority recommendations.
Table 6 Hospitals with Outdoor Patient Department(Clause 4.2.5.1)
Sl No.
Fixtures
Patient Toilets
Staff Toilets
Males(3)
Females(4)
Males(5)
Females(6)
i)
Toilet suite comprising one WC and one wash basin (with optional shower stall if building used for 24 h)
For up to 4 patients
For individual doctor's/officer's rooms
ii)
Water closets
1 per 100 persons or part thereof
2 per 100 persons or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
iii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iv)
Urinals
1 per 50 persons or part thereof
—
Nil up to 61 for 7 to 202 for 21 to 45
—
v)
Wash basins
2 per 100 persons of part thereof
2 per 100 persons or part thereof
1 for up to 152 for 16 to 35
1 for up to 122 for 13 to 25
vi)
Drinking water fountain
See Note 2
1 per 100 persons or part thereof
NOTES
1 Some WCs may be Indian style, if desired.
2 Drinking water fountains are not recommended for hospitals for reasons of infection control. This to be decided by the health authority recommendation.
3 The WCs shall be provided keeping in view the location of main OPD waiting hall and sub-waiting halls, floor wise, so as to serve the people effectively. The number of patients shall be calculated floor wise. The OPD population shall include patient attendants @ at least 1 per patient.
4 Male population may be assumed as two-third and female population as one-third.
5 Provision for additional and special hospital fittings where required shall be made.
Toilet suite comprising one WC, one urinal and one wash basin (with optional shower stall if building used for 24 h)
For individual doctor's/officer's rooms
ii)
Water closets
1 per 25 persons or part thereof
1 per 15 persons or part thereof
iii)
Ablution tap
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iv)
Urinals
—
1 for 6 to 15
2 for 16 to 50
v)
Wash basins
1 per 25 persons or part thereof
1 per 25 persons or part thereof
vi)
Drinking water fountain
1 per 100 persons or part thereof (See Note 2)
vii)
Cleaner's sink
1 per floor, Min
viii)
Kitchen sink
1 per floor, Min
NOTES
1
Some WCs may be Indian style, if desired.
2
Drinking water fountains to be provided only when it is a separate block and patients will not use it.
Table 8Hospitals Staff Quarters and Nurses Homes (Clause 4.2.5.1)
Sl No.
Fixtures
Staff Quarters
Nurses Homes
Males(3)
Females(4)
Males(5)
Females(6)
i)
Water closets
1 per 4 persons or part thereof
1 per 4 persons or part thereof
1 per 4 persons or part thereof2 for 5 to 35
1 per 4 persons or part thereof2 for 5 to 25
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Wash basins
1 per 8 persons or part thereof
1 per 8 persons or part thereof
iv)
Bath (showers)
1 per 4 persons or part thereof
1 per 4 to 6 persons or part thereof
v)
Drinking water fountain
1 per 100 persons or part thereof, Min 1 per floor
1 per 100 persons or part thereof, Min 1 per floor
vi)
Cleaner's sink
1 per Floor
1 per Floor
NOTES
1 Some WCs may be Indian style, if desired.
2 For independent housing units, fixtures shall be provided as for residences.
Table 9 Hotels(Clause 4.2.5.1)
Sl No.
Fixtures
Public Rooms
Non Residential Staff
Males(3)
Females(4)
Males(5)
Females(6)
i)
Toilet suite comprising one WC, wash basin with shower or a bath tub
Individual guest rooms with attached toilets
—
ii)
Guest Rooms with Common Facilities
Water closets
1 per 100 persons up to 400Over 400 add at 1 per 250 or part thereof
2 per 100 persons up to 200Over 200 add at 1 per 100 or part thereof
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 575 for 58 to 776 for 78 to 100
iii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iv)
Urinals
1 per 50 persons or part thereof
—
Nil up to 61 for 7 to 202 for 21 to 453 for 46 to 704 for 71 to 100
—
v)
Wash basins
1 per WC/Urinal
1 per WC
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 57
vi)
Bath (showers)
1 per 10 persons or part thereof
—
—
vii)
Cleaner's sink
1 per 30 rooms, Min 1 per floor
viii)
Kitchen sink
1 per kitchen
NOTES
1
Some WCs may be Indian style, if desired.
2
Male population may be assumed as two-third and female population as one-third.
3
Provision for additional and special fittings where required shall be made.
Table 10 Restaurants(Clause 4.2.5.1)
Sl No.(1)
Fixtures(2)
Public Rooms
Non-Residential Staff
Males(3)
Females(4)
Males(5)
Females(6)
i)
Water closets
1 per 50 seats up to 200Over 200 add at 1 per100 or part thereof
2 per 50 seats up to 200Over 200 add at 1 per100 or part thereof
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 575 for 58 to 776 for 78 to 100
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
1 per 50 persons or part thereof
—
Nil up to 61 for 7 to 202 for 21 to 453 for 46 to 704 for 71 to 100
—
iv)
Wash basins
1 per WC
1 per WC
1 per WC
1 per WC
v)
Cleaner's sink
1 per each restaurant
vi)
Kitchen sink/dish washer
1 per kitchen
NOTES
1
Some WCs may be Indian style, if desired.
2
Male population may be assumed as two-third and female population as one-third.
3
Provision for additional and special fittings where required shall be made.
Table 11 Schools and Educational Institutions(Clause 4.2.5.1)
Sl No.
Fixtures
Nursery School
Non-Residential
Residential
Boys(4)
Girls(5)
Boys(6)
Girls(7)
i)
Water closets
1 per 15 pupils or part thereof
1 per 40 pupils or part thereof
1 per 25 pupils or part thereof
1 per 8 pupils or part thereof
1 per 6 pupils or part thereof
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
—
1 per 20 pupils or part thereof
—
1 per 25 pupils or part thereof
—
iv)
Wash basins
1 per 15 pupils or part thereof
1 per 60 pupils or part thereof
1 per 40 pupils or part thereof
1 per 8 pupils or part thereof
1 per 6 pupils or part thereof
v)
Bath/showers
1 per 40 pupils or part thereof
—
—
1 per 8 pupils or part thereof
1 per 6 pupils or part thereof
vi)
Drinking water fountain or taps
1 per 50 pupils or part thereof
1 per 50 pupils or part thereof
1 per 50 pupils or part thereof
1 per 50 pupils or part thereof
1 per 50 pupils or part thereof
vii)
Cleaner's sink
1 per each floor
NOTES1 Some WCs may be Indian style, if desired.2 For teaching staff, the schedule of fixtures to be provided shall be the same as in case of office building.
Book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.84.35) valid up Table 12 Hostels (Clause 4.2.5.1)
Sl No.(1)
Fixtures(2)
Resident
Non-Resident
Visitor/Common Rooms
Males(3)
Females(4)
Males(5)
Females(6)
Males(7)
Females(8)
i)
Water closets
1 per 8 or part thereof
1 per 6 or part thereof
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 575 for 58 to 776 for 78 to 100
1 per 100up to 400Over 400 addat 1 per 250
2 per 100up to 200Over 200 addat 1 per 100
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
1 per 25 or part thereof
—
Nil up to 61 for 7 to 202 for 21 to 453 for 46 to 704 for 71 to 100
—
1 per 50 or part thereof
—
iv)
Wash basins
1 per 8 persons or part thereof
1 per 6 persons or part thereof
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 575 for 58 to 776 for 78 to 100
1 per WC/Urinal
1 per WC
v)
Bath/showers
1 per 8 persons or part thereof
1 per 6 persons or part thereof
—
—
—
—
vi)
Cleaner's sink
1 per each floor
NOTE — Some WCs may be Indian style, if desired.
Table 13 Fruit and Vegetable Markets(Clause 4.2.5.1)
Sl No.
Fixtures
Shop Owners
Common Toilets in Market Building
Public Toilet for Floating Population
Males(3)
Females(4)
Males(5)
Females(6)
Males(7)
Females(8)
i)
Water closets
1 per 8 or part thereof
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 575 for 58 to 776 for 78 to 100
1 per 50(Min 2)
1 per 50(Min 2)
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided in receiving/ sale area of each shop and for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
—
—
Nil up to 61 for 7 to 202 for 21 to 453 for 46 to 704 for 71 to 100
—
1 per 50
—
iv)
Wash basins
1 per 8 or part thereof
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 57
—
—
v)
Bath/showers
1 per 8 persons or part thereof
1 per 6 persons or part thereof
—
—
1 per 50persons
1 per 50persons
NOTES1 Toilet facilities for individual buildings in a market should be taken same as that for office buildings.2 Common toilets in the market buildings provide facilities for persons working in shops and their regular visitors.3 Special toilet facilities for a large floating population of out of town buyers/sellers, labour, drivers of vehicles for whom special toilet (public toilets).
book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.84.35) valid up Table 14 Bus Stations, Airports and Railway Stations (Clause 4.2.5.1)
Sl No.
Fixtures
Junction Stations, Intermediate Stations and Bus Stations
Terminal Railway and Bus Stations
Domestic and International Airports
Males (3)
Females (4)
Males (5)
Females (6)
Males (7)
Females (8)
(1)
(2)
i)
Water closets
3 for up to 1 000
4 for up to 1 000
4 for up to 1 000
5 for up to 1 000
Min 2
Min 2
Add 1 per additional 1 000 or part thereof
Add 1 per additional 1 000 or part thereof
Add 1 per additional 1 000 or part thereof
Add 1 per additional 1 000 or part thereof
For 200 : 5 For 400 : 9 For 600 : 12 For 800 : 16 For 1 000 : 18
For 200 : 8 For 400 : 15 For 600 : 20 For 800 : 26 For 1 000 : 29
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
One in each water closet
1 water tap with draining arrangements shall be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
iii)
Urinals
4 for up to 1 000
—
6 for up to 1 000
—
1 per 40 or part thereof
—
Add 1 per additional 1 000
Add 1 per additional 1 000
iv)
Wash basins
1 per WC/ Urinal
1 per WC
1 per WC/ Urinal
1 per WC
1 per WC/ Urinal
1 per WC
v)
Bath/showers
2 per 1 000
3 per 1 000
4 per 1 000
vi)
Drinking water fountain or taps (in common lobby for male/female)
2 per 1 000 or part thereof
3 per 1 000 or part thereof
4 per 1 000 or part thereof
vii)
Cleaner's sink
1 per toilet compartment with 3 WCs
1 per toilet compartment with 3 WCs
1 per toilet compartment with 3 WCs
1 per toilet compartment with 3 WCs
1 per toilet compartment with 3 WCs
1 per toilet compartment with 3 WCs
NOTES
1
Some WCs may be Indian style, if desired.
2
Male population may be assumed as three-fifth and female population as two-fifth.
3
Separate provision shall be made for staff and workers.
Table 15Shopping Malls and Retail Buildings (Clause 4.2.5.1)
Sl No.(1)
Fixtures(2)
Staff Toilets in Shopping Building
Public Toilet for Floating Population
Males(5)
Females(6)
Males(7)
Females(8)
i)
Water closets
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 575 for 58 to 776 for 78 to 100
1 per 50 (Min 2)
1 per 50 (Min 2)
ii)
Ablution tap
One in each water closet
One in each water closet
One in each water closet
One in each water closet
iii)
Urinals
Nil up to 61 for 7 to 202 for 21 to 453 for 46 to 704 for 71 to 100
—
1 per 50
—
iv)
Wash basins
1 for up to 152 for 16 to 353 for 36 to 654 for 66 to 100
1 for up to 122 for 13 to 253 for 26 to 404 for 41 to 57
1 per 50 (Min 2)
1 per 50 (Min 2)
v)
Bath/showers
1 per 100 persons
1 per 100 persons
—
—
NOTES1 Toilet facilities for individual facilities in a shopping building should be taken same as that for office buildings.2 Staff toilets in the shopping buildings provide facilities for persons working in shops and building, as well as for maintenance staff.3 The number of persons against the fixture bath/showers represent the maintenance staff requiring such facility.4 Public toilet facilities are provided for a large floating population for buyers and visitors.
24
installation suited to the need of a specific building. For example, schools should be provided with toilet facilities on each floor. Similarly, toilet facilities shall be provided for temporary workmen employed in any establishment according to the needs; and in any case one WC and one wash basin shall be provided.
All buildings used for human habitation for dwelling, work, occupation, medical care or any purpose detailed in the various tables, abutting a public sewer or a private sewage disposal system, shall be provided with minimum sanitary facilities as per the schedule in the tables. In case the disposal facilities are not available, they shall be provided as a part of the building design for ensuring high standards of sanitary conditions in accordance with this section.
g) Workplaces where crèches are provided, they shall be provided with one WC for 10 persons or part thereof, one wash basin for 15 persons or part thereof, one kitchen sink with floor trap for preparing food/milk preparations. The sink provided shall be with a drinking water tap.
h) In all types of buildings, individual toilets and pantry should be provided for executives, and for meeting/seminar/conference rooms, etc, as per the user requirement.
j) Where food is consumed indoors, water stations may be provided in place of drinking water fountains.