4.1 Service shut-off valves shall be installed on all new services including replacements in a readily accessible location.
4.2 Service shut-off valves shall be located upstream of the meter if there is no regulator or upstream of the regulator, if there is one.
4.2.1 Service shut-off valves shall be located in the upstream of the meter, if a single regulator is supplying more than one consumer and each such stream shall have one additional shut-off valve upstream of regulator.
4.3 All gas services operating at pressure greater than 7 kN/m² shall be equipped with an approved service shut-off valve located on the service pipe outside the building.
4.4 Underground shut-off valves shall be located in a covered durable curb box, manhole, vault or stand pipe
which is designed to permit ready operation of the valve and the covers of which shall be clearly marked 'Gas'.