It should be ensured that all equipment connected to the system including any appliances to be used on it are suitable for the voltage and frequency of supply of the system. The nominal values of low and medium voltage systems in India are 240 V and 415 V a.c., respectively, and the frequency is 50 Hz.
bok Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63,84.35) valid up
NOTE — The design of the wiring system and the sizes of the cables should be decided taking into account following factors:
a) Voltage drop — This should be kept below 6 percent to ensure proper functioning of all electrical appliances and equipment including motors;
b) Thermal limit based current carrying capacity of the cable with appropriate derating factors applicable to the installation conditions;
c) Capacity to withstand the let through fault current based on the fault level and the controlling switchgear disconnection characteristics.