The truss shall be designed to safely sustain steps and running gear in its guides. All mechanically moving parts of the escalator or moving walk shall be completely enclosed within imperforate panels or walls. Exceptions are the accessible steps, the accessible pallets, the accessible belt and that part of the handrail available for the user. Apertures for ventilation are permitted. However, it shall not be possible to pass a straight rigid rod 10 mm in diameter through the enclosure and to touch any moving part through a ventilation aperture.
The supporting structure shall be designed in a way that it can support the dead weight of the escalator or moving walk plus a rated load of 5 000 N/m² . Based on the rated load, the maximum calculated or measured deflection shall not exceed 1/750 of the distance between the supports. Angle of inclination of an escalator from the horizontal shall not exceed 30° , but for rises not exceeding 6 m and nominal speed not exceeding 0.5 m/s the angle of inclination is permitted to be increased to 35° .
| Risem | Speedm/s | Angle of Inclination | |
| Standard | Option | ||
| ≤6 | ≤0.5 | 30° | 35° |
| ≤6 | >0.5 | 30° | — |
| >6 | ≤0.5 | 30° | — |
| >6 | >0.5 | 30° | — |
The angle of inclination of moving walks shall not exceed 12°.