8.2.1 Earthing shall generally be carried out in accordance with the requirements of Regulation 16, 41 and 48 of Central Electricity Authority (Measures relating to Safety and Electricity Supply) Regulations, 2010 as amended from time-to-time (see Annex B) and good practice [8-2(44)] and the relevant regulations of the Electricity Supply Authority concerned.
8.2.2 Conductors and earth electrodes in an earthing system shall be so designed and constructed that in normal use their performance is reliable and without danger to persons and surrounding equipment. Earthing system shall be designed such as to have touch potential and step potential as specified in good practice [8-2(44)]. The choice of a material depends on its ability to match the particular application requirement. The requirements for earthing arrangements are intended to provide a connection to earth which,
a) is reliable and suitable for the protective requirements of the installation;
b) can carry earth fault currents and protective conductor currents to earth without danger from thermal, thermo-mechanical and electromechanical stresses and from electric shock arising from these currents;
c) if relevant, is also suitable for functional requirements; and
d) is suitable for the foreseeable external influences {see good practice [8-2(44)] and IEC 60364-5-51:2005 'Electrical installations of buildings — Part 5-51: Selection and erection of electrical equipment — Common rules'}, for example, mechanical stresses and corrosion.
8.2.3 The main earthing system of an electrical installation shall consist of,
a) an earth electrode, (electrode can be one vertical rod/pipe/buried plate or an earth mat with several vertical installations or a ring earthing with vertical installations.
b) a main earthing wire;
c) an earth bar (located on the main switchboard for small installation and installed in the wall/room in case of large industrial electronic installations) for the connection of the main earthing wire, protective earthing wires and/or bonding wires within the installation; and
d) a removable link, which effectively disconnects the neutral bar from the earth bar. NOTE — The requirements of (c) and (d) shall be carried out by a licensed electrician as part of the switchboard installation.
8.2.4 The main earthing wire connection shall,
a) be mechanically and electrically sound;
b) be protected against damage, corrosion, and vibration;
c) not place any strain on various parts of the connection;
d) not damage the wire or fittings; and
e) be secured at the earth electrode.
8.2.4.1 The main earthing wire termination shall be readily accessible at the earth electrode except for 8.2.20. As far as possible, all earth connections, except exothermically welded, shall be visible for inspection.
8.2.5 Consideration shall be given to the earthing arrangements where currents with high frequencies are expected to flow (see 444 of IEC 60364-4-44:2007 'Low-voltage electrical installations — Part 4-44: Protection for safety — Protection against voltage disturbances and electromagnetic disturbances').
8.2.6 Protection against electric shock (see IEC 60364-4-41 'Low-voltage electrical installations — Part 4-41: Protection for safety — Protection against electric shock'), shall not be adversely affected by any foreseeable change of the earth electrode resistance (for example, due to corrosion, drying or freezing).
8.2.7 Where the supply to an installation is at high or extra high voltage, requirements concerning the earthing arrangements of the high or extra high voltage supply and of the low-voltage installation shall also comply with 442 of IEC 60364-4-44:2007 'Low-voltage electrical installations — Part 4-44: Protection for safety — Protection against voltage disturbances and electromagnetic disturbances'.
8.2.8 A permanent fitting (like a screwed-down plastic label or copper label, or one that can be threaded onto the cable) shall be used at the connection point that is clearly marked with the words: 'EARTHING LEAD — DO NOT DISCONNECT' or 'EARTHING CONDUCTOR — DO NOT DISCONNECT'.
8.2.9 All medium voltage equipment shall be earthed by two separate and distinct connections with earth. The contact area of earth conductor/plate shall be determined in accordance with good practice [8-2(44)].
8.2.9.1 The 415/240 V, 4-wire, 3-phase systems are normally operated with the neutral solidly earthed at source. At medium voltage, Central Electricity
Authority regulations require that the neutral be earthed by two separate and distinct connections with earth. Source in the case of a substation (such as 11 kV/415 V) will be the neutral(s) of the transformer(s). Neutral conductor shall be of the same size as the phase conductor.
NOTE — Neutral conductor of half the size of the phase conductor was permitted in earlier installations. But with the proliferation of equipment using non-linear devices and consequent increase in harmonics, the neutral will carry a current more than the notional out-of-balance current and therefore neutral conductor shall be of the same size as the phase conductor.
8.2.10 In the case of high and extra high voltages, the neutral points shall be earthed by not less than two separate and distinct connections to earth, each having its own electrode at the generating station or substation and may be earthed at any other point provided no interference is caused by such earthing. The neutral may be earthed through suitable impedance. Neutral earthing conductor shall be sized as to have a current carrying capacity not less than the phase current.
8.2.11 For industrial/commercial installations having a transformer within the facility, soil resistivity of the place of installation shall be measured as per good practice [8-2(44)] and recorded. For the adopted type of earth electrode configuration, earth resistance of each electrode configuration shall be calculated and recorded based on good practice [8-2(44)].
8.2.12 It is recommended that a drawing showing the main earth connection and earth electrodes be prepared for each installation.
8.2.13 Conductors, other than live conductors, and any other parts intended to carry a fault current shall be capable of carrying that current without attaining an excessive temperature.
8.2.14 Earth system shall be so devised that the testing of individual earth electrode is possible {except for installations according to 5.3.6 of good practice [8-2(45)]}. It is recommended that the value of any earth system resistance shall be such as to conform to the degree of shock protection desired. For measuring purposes, the joint shall be capable of being opened with the aid of a tool. In normal use it shall remain closed.
8.2.15 No addition to the current-carrying system, either temporary or permanent, shall be made which will increase the maximum available earth fault current or its duration until it has been ascertained that the existing arrangement of earth electrodes, earth bus-bar, etc, are capable of carrying the new value of earth fault current which may be obtained by this addition.
8.2.16 No cut-out, link or switch other than a linked switch arranged to operate simultaneously on the
earthed or earthed neutral conductor and the live conductors, shall be inserted on any supply system. This, however, does not include the case of a switch for use in controlling a generator or a transformer or a link for test purposes.
8.2.17 All materials, fittings, etc, used in earthing shall conform to relevant Indian Standard specification, wherever these exist.
8.2.18 Earthing associated with current-carrying conductor is normally essential for the function of the system and is generally known as system earthing or functional earthing, while earthing of non-current carrying metal work and conductor is essential for the safety of human life, of animals and of property and it is generally known as equipment earthing or protective earthing. The earthing arrangements may be used jointly or separately for protective and functional purposes according to the requirements of the electrical installation. The requirements for protective purposes shall always take precedence.
8.2.19 For selection of electrodes for use in corrosive environments, reference shall be made to good practice [8-2(44)].
8.2.20 Test joints are not required in the case of natural down-conductors combined with foundation earth electrodes (see Fig. 5).
8.2.21 For computer and other sensitive electronic equipment system in industrial and commercial application, special bonding techniques with isolation transformer should be employed (see Fig. 6).
8.2.22 Isolated earthing is unsafe during a transient condition. In unavoidable conditions if isolated earthing is used, to reduce potential difference between isolated earthing, earth couplers or isolating spark gaps shall be installed. This will reduce potential difference during a transient condition such as lightning.