7.1 The design of joints shall be made in the light of their assessment with respect to the following considerations:
a) Feasibility — The feasibility of a joint shall be determined by its load-carrying capacity in the particular situation in which the joint is to function.
b) Practicability — Practicability of joint shall be determined by the amount and type of material required in construction; cost of material, fabrication and erection and the time for fabrication and erection.
c) Serviceability — Serviceability shall be determined by the joints/expected behaviour to repeated or possible overloading and exposure to climatic or chemical conditions.
d) Fire Rating — The fire rating for joints of precast components shall be higher or at least equal to connecting members.
e) Appearance — The appearance of precast components joint shall merge with architectural aesthetic appearance and shall not be physically prominent compared to other parts of structural components.
7.2 The following are the requirements of a structural joint:
a) It shall be capable of being designed to transfer the imposed load and moments with a known margin of safety;
b) It shall occur at logical locations in the structure and at points which may be most readily analysed and easily reinforced;
c) It shall accept the loads without marked displacement or rotation and avoid high local stresses;
d) It shall accommodate tolerances in elements;
e) It shall require little temporary support, permit adjustment and demand only a few distinct operation to make;
f) It shall permit effective inspection and rectification;
g) It shall be reliable in service with other parts of the building; and
h) It shall enable the structure to absorb sufficient energy during earthquakes so as to avoid sudden failure of the structure.
7.2.1 Precast structures may have continuous or hinged connections subject to providing sufficient rigidity to withstand horizontal loading. When only compressive forces are to be taken, hinged joints may be adopted. In case of prefabricated concrete elements, load is transmitted via the concrete. When both compressive force and bending moment are to be taken,
rigid or welded joints may be adopted; the shearing force is usually small in the column and can be taken up by the friction resistance of the joint. Here load transmission is accomplished by steel inserted parts together with concrete.
7.2.2 When considering thermal shrinkage and heat effects, provision of freedom of movement or introduction of restraint may be considered.
7.3 Joining techniques/materials normally employed are:
a) Welding of cleats or projecting steel,
b) Overlapping reinforcement, loops and linking steel grouted by concrete,
c) Reinforced concrete ties all round a slab,
d) Prestressing,
e) Epoxy grouting,
f) Bolts and nuts connection,
g) A combination of the above, and
h) Any other method proven by test.