Section 4 Masonry
1.1 This Section primarily covers the structural design aspects of unreinforced load bearing and non-load bearing walls, constructed with masonry units permitted in accordance with this Section. This, however, also covers provisions for design of reinforced brick and reinforced brick concrete floors and roofs. It also covers guidelines regarding earthquake resistance of low strength masonry buildings.
1.2 The recommendations of the Section do not apply to walls constructed in mud mortars.
2.1 For the purpose of this Section, the following definitions shall apply.
2.1.1 Bed Block — A block bedded on a wall, column or pier to disperse a concentrated load on a masonry element.
2.1.2 Bond — Arrangement of masonry units in successive courses to tie the masonry together both longitudinally and transversely; the arrangement is usually worked out to ensure that no vertical joint of one course is exactly over the one in the next course above or below it, and there is maximum possible amount of lap.
a) Column — An isolated vertical load bearing member, width of which does not exceed four times the thickness.
b) Pier — A thickened section forming integral part of a wall placed at intervals along the wall, to increase the stiffness of the wall or to carry a vertical concentrated load. Thickness of a pier is the overall thickness including the thickness of the wall or, when bonded into a leaf of a cavity wall, the thickness obtained by treating that leaf as an independent wall (see Fig. 1).
c) Buttress — A pier of masonry built as an integral part of wall and projecting from either or both surfaces, decreasing in cross-sectional area from base to top.
2.1.4 Cross-Sectional Area of Masonry Unit — Net cross-sectional area of a masonry unit shall be taken as the gross cross-sectional area minus the area of cellular space. Gross cross-sectional area of cored units
shall be determined to the outside of the coring but cross-sectional area of grooves shall not be deducted from the gross cross-sectional area to obtain the net cross-sectional area.
2.1.5 Curtain Wall — A non-load bearing wall subject to lateral loads. It may be laterally supported by vertical or horizontal structural members where necessary (see Fig. 2).
2.1.6 Effective Height — The height of a wall or column, to be considered for calculating slenderness ratio.
2.1.7 Effective Length — The length of a wall to be considered for calculating slenderness ratio.
2.1.8 Effective Thickness — The thickness of a wall or column to be considered for calculating slenderness ratio.
2.1.9 Hollow Unit — A masonry unit of which net cross-sectional area in any plane parallel to the bearing surface is less than 75 percent of its gross cross-sectional area measured in the same plane.
2.1.10 Grout — Mortar of pourable consistency.
2.1.11 Joint — A junction of masonry units.
a) Bed joint — A horizontal mortar joint upon which masonry units are laid.
b) Cross joint — A vertical joint, normal to the face of the wall.
c) Wall joint — A vertical joint parallel to the face of the wall.
2.1.12 Leaf — Inner or outer section of a cavity wall.
2.1.13 Lateral Support — A support which enables a masonry element to resist lateral load and/or restrains lateral deflection of a masonry element at the point of support.
2.1.14 Load Bearing Wall — A wall designed to carry an imposed vertical load in addition to its own weight, together with any lateral load.
5
2.1.15 Masonry — An assemblage of masonry units properly bonded together with mortar.
2.1.16 Masonry Unit — Individual units which are bonded together with the help of mortar to form a masonry element such as wall, column, pier, buttress, etc.
2.1.17 Partition Wall — An interior non-load bearing wall, one storey or part storey in height.

FIG. 1 DEFINITION OF PIER

FIG. 2 MASONRY CURTAIN WALL
2.1.18 Panel Wall — An exterior non-load bearing wall in framed construction, wholly supported at each storey but subjected to lateral loads.
2.1.19 Shear Wall — A wall designed to carry horizontal forces acting in its plane with or without vertical imposed loads.
2.1.20 Slenderness Ratio — Ratio of effective height or effective length to effective thickness of a masonry element.
a) Cavity wall — A wall comprising two leaves,
each leaf being built of masonry units and separated by a cavity and tied together with metal ties or bonding units to ensure that the two leaves act as one structural unit, the space between the leaves being either left as continuous cavity or filled with a non-load bearing insulating and water-proofing material.
b) Faced wall — A wall in which facing and backing of two different materials are bonded together to ensure common action under load (see Fig. 3).


FIG. 3 TYPICAL FACED WALL
NOTE — To ensure monolithic action in faced walls, shear strength between the facing and the backing shall be provided by toothing, bonding or other means.
c) Veneered wall — A wall in which the facing is attached to the backing but not so bonded as to result in a common action under load.
The materials used in masonry construction shall be in accordance with Part 5 ‘Building Materials’.
Masonry units used in construction shall conform to accepted standards [6-4(1)].
3.2.1 Masonry units may be of the following types:
a) Common burnt clay building bricks,
b) Burnt clay fly ash building bricks,
c) Pulverized fuel ash lime bricks,
d) Stones (in regular sized units),
e) Sand-lime bricks,
f) Concrete blocks (solid and hollow),
g) Lime based blocks,
h) Burnt clay hollow blocks,
j) Gypsum partition blocks,
k) Autoclaved cellular concrete blocks, and
m) Concrete stone masonry blocks.
1 Gypsum partition blocks are used only for construction of non-load bearing partition walls.
2 Use of other masonry units, such as, precise stone blocks, fly-ash-lime-gypsum bricks, stabilized mud blocks and other bricks/blocks not covered by the above specifications may also be permitted based on test results.
3.2.2 Masonry units that have been previously used shall not be re-used in brickwork or blockwork construction, unless they have been thoroughly cleaned
and conform to this Section for similar new masonry units.
Mortar for masonry shall conform to accepted standard [6-4(2)].
3.3.1 Mix proportions and compressive strengths of some of the commonly used mortars are given in Table 1.
| Sl No. | Grade of Mortar | Mix Proportions (by Loose Volume) | Minimum Compressive Strength at 28 Days in N/mm ² | ||||
| Cement | Lime | Lime Pozzolana Mixture | Pozzolana | Sand | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| 1 | H1 | 1 | (1)/(4) C or B | 0 | 0 | 3 | 10 |
| 2(a) | H2 | 1 | (1)/(4) C or B | 0 | 0 | 4 | 7.5 |
| 2(b) | 1 | (1)/(2) C or B | 0 | 0 | 4(1)/(2) | 6.0 |
| 3(a) | M1 | 1 | 0 | 0 | 5 | 5.0 |
| 3(b) | 1 | 1 C or B | 0 | 0 | 6 | 3.0 |
| 3(c) | 0 | 0 | 1 (LP-40) | 0 | 1(1)/(2) | 3.0 |
| 4(a) | M2 | 1 | 0 | 0 | 0 | 6 | 3.0 |
| 4(b) | 1 | 2 B | 0 | 0 | 9 | 2.0 |
| 4(c) | 0 | 1 A | 0 | 0 | 2 | 2.0 |
| 4(d) | 0 | 1 B | 0 | 1 | 1 | 2.0 |
| 4(e) | 0 | 1 C or B | 0 | 2 | 0 | 2.0 |
| 4(f) | 0 | 0 | 1 (LP-40) | 0 | 1(3)/(4) | 2.0 |
| 5(a) | M3 | 1 | 0 | 0 | 0 | 7 | 1.5 |
| 5(b) | 1 | 3 B | 0 | 0 | 12 | 1.5 |
| 5(c) | 0 | 1 A | 0 | 0 | 3 | 1.5 |
| 5(d) | 0 | 1 B | 0 | 2 | 1 | 1.5 |
| 5(e) | 0 | 1 C or B | 0 | 3 | 0 | 1.5 |
| 5(f) | 0 | 0 | 1 (LP-40) | 0 | 2 | 1.5 |
| 6(a) | L1 | 1 | 0 | 0 | 0 | 8 | 0.7 |
| 6(b) | 0 | 1 B | 0 | 1 | 2 | 0.7 |
| 6(c) | 0 | 1 C or B | 0 | 2 | 1 | 0.7 |
| 6(d) | 0 | 0 | 1 (LP-40) | 0 | 2(1)/(4) | 0.7 |
| 6(e) | 0 | 0 | 1 (LP-20) | 0 | 1(1)/(2) | 0.7 |
| 7(a) | L2 | 0 | 1 B | 0 | 0 | 3 | 0.5 |
| 7(b) | 0 | 1 C or B | 0 | 1 | 2 | 0.5 |
| 7(c) | 0 | 0 | 1 (LP-7) | 0 | 1(1)/(2) | 0.5 |
1 Sand for making mortar should be well graded. In case sand is not well graded, its proportion shall be reduced in order to achieve the minimum specified strength.
2 For mixes in Sl No. 1 and 2, use of lime is not essential from consideration of strength as it does not result in increase in strength. However, its use is highly recommended since it improves workability.
3 For mixes in Sl No. 3(a), 4(a), 5(a) and 6(a), either lime C or B to the extent of ¼ part of cement (by volume) or some plasticizer should be added for improving workability.
4 For mixes in Sl No. 4(b) and 5(b), lime and sand should first be ground in mortar mill and then cement added to coarse stuff.
5 It is essential that mixes in Sl No. 4(c), 4(d), 4(e), 5(d), 5(e), 6(b), 6(c), 7(a) and 7(b) are prepared by grinding in a mortar mill.
6 Mix in Sl No. 2(b) has been classified to be of same grade as that of Sl No. 2(a), mixes in Sl No. 3(b) and 3(c) same as that in Sl No. 3(a), mixes in Sl No. 4(b) to 4(f) same as that in Sl No. 4(a), even though their compressive strength is less. This is from consideration of strength of masonry using different mix proportions.
7 A, B and C denote eminently hydraulic lime, semi-hydraulic lime and fat lime respectively, as specified in appropriate standards listed in Part 5 ‘Building Materials’.