6.1 The concrete mix proportions chosen should be such that the concrete is of adequate workability for the placing conditions of the concrete and can properly be compacted with the means available. Suggested ranges of workability of concrete measured in accordance with good practice [6-5A(16)] are given below:
| Placing Conditions(1) | Degree of Workability(2) | Slump mm(3) |
|---|---|---|
| Blinding concrete; Shallow sections; Pavements using pavers | Very low | See 6.1.1 |
| Mass concrete; Lightly reinforced sections in slabs, | Low | 25-75 |
| (1) | (2) | (3) |
|---|---|---|
| beams, walls, columns; Floors; | ||
| Hand placed pavements; Canal | ||
| lining; Strip footings | ||
| Heavily reinforced sections in | Medium | 50-100 |
| slabs, beams, walls, columns | ||
| Slipform work; Pumped | Medium | 75-100 |
| concrete | ||
| Trench fill; in-situ piling | High | 100-150 |
| Tremie concrete | Very high | See 6.1.2 |
NOTE — For most of the placing conditions, internal vibrators (needle vibrators) are suitable. The diameter of the needle shall be determined based on the density and spacing of reinforcement bars an thickness of sections. For tremie concrete, vibrators are not required to be used (see also 13.3).
6.1.1 In the ‘very low’ category of workability where strict control is necessary, for example, pavement quality concrete, measurement of workability by determination of compacting factor will be more appropriate than slump (see accepted standard [6-5A(16)]) and a value of compacting factor of 0.75 to 0.80 is suggested.
6.1.2 In the ‘very high’ category of workability, measurement of workability by determination of flow will be appropriate (see accepted standard [6-5A(17)] ).