Section 4 Masonry
1.1 This Section primarily covers the structural design aspects of unreinforced load bearing and non-load bearing walls, constructed with masonry units permitted in accordance with this Section. This, however, also covers provisions for design of reinforced brick and reinforced brick concrete floors and roofs. It also covers guidelines regarding earthquake resistance of low strength masonry buildings.
1.2 The recommendations of the Section do not apply to walls constructed in mud mortars.
2.1 For the purpose of this Section, the following definitions shall apply.
2.1.1 Bed Block — A block bedded on a wall, column or pier to disperse a concentrated load on a masonry element.
2.1.2 Bond — Arrangement of masonry units in successive courses to tie the masonry together both longitudinally and transversely; the arrangement is usually worked out to ensure that no vertical joint of one course is exactly over the one in the next course above or below it, and there is maximum possible amount of lap.
a) Column — An isolated vertical load bearing member, width of which does not exceed four times the thickness.
b) Pier — A thickened section forming integral part of a wall placed at intervals along the wall, to increase the stiffness of the wall or to carry a vertical concentrated load. Thickness of a pier is the overall thickness including the thickness of the wall or, when bonded into a leaf of a cavity wall, the thickness obtained by treating that leaf as an independent wall (see Fig. 1).
c) Buttress — A pier of masonry built as an integral part of wall and projecting from either or both surfaces, decreasing in cross-sectional area from base to top.
2.1.4 Cross-Sectional Area of Masonry Unit — Net cross-sectional area of a masonry unit shall be taken as the gross cross-sectional area minus the area of cellular space. Gross cross-sectional area of cored units
shall be determined to the outside of the coring but cross-sectional area of grooves shall not be deducted from the gross cross-sectional area to obtain the net cross-sectional area.
2.1.5 Curtain Wall — A non-load bearing wall subject to lateral loads. It may be laterally supported by vertical or horizontal structural members where necessary (see Fig. 2).
2.1.6 Effective Height — The height of a wall or column, to be considered for calculating slenderness ratio.
2.1.7 Effective Length — The length of a wall to be considered for calculating slenderness ratio.
2.1.8 Effective Thickness — The thickness of a wall or column to be considered for calculating slenderness ratio.
2.1.9 Hollow Unit — A masonry unit of which net cross-sectional area in any plane parallel to the bearing surface is less than 75 percent of its gross cross-sectional area measured in the same plane.
2.1.10 Grout — Mortar of pourable consistency.
2.1.11 Joint — A junction of masonry units.
a) Bed joint — A horizontal mortar joint upon which masonry units are laid.
b) Cross joint — A vertical joint, normal to the face of the wall.
c) Wall joint — A vertical joint parallel to the face of the wall.
2.1.12 Leaf — Inner or outer section of a cavity wall.
2.1.13 Lateral Support — A support which enables a masonry element to resist lateral load and/or restrains lateral deflection of a masonry element at the point of support.
2.1.14 Load Bearing Wall — A wall designed to carry an imposed vertical load in addition to its own weight, together with any lateral load.
5
2.1.15 Masonry — An assemblage of masonry units properly bonded together with mortar.
2.1.16 Masonry Unit — Individual units which are bonded together with the help of mortar to form a masonry element such as wall, column, pier, buttress, etc.
2.1.17 Partition Wall — An interior non-load bearing wall, one storey or part storey in height.

FIG. 1 DEFINITION OF PIER

FIG. 2 MASONRY CURTAIN WALL
2.1.18 Panel Wall — An exterior non-load bearing wall in framed construction, wholly supported at each storey but subjected to lateral loads.
2.1.19 Shear Wall — A wall designed to carry horizontal forces acting in its plane with or without vertical imposed loads.
2.1.20 Slenderness Ratio — Ratio of effective height or effective length to effective thickness of a masonry element.
a) Cavity wall — A wall comprising two leaves,
each leaf being built of masonry units and separated by a cavity and tied together with metal ties or bonding units to ensure that the two leaves act as one structural unit, the space between the leaves being either left as continuous cavity or filled with a non-load bearing insulating and water-proofing material.
b) Faced wall — A wall in which facing and backing of two different materials are bonded together to ensure common action under load (see Fig. 3).


FIG. 3 TYPICAL FACED WALL
NOTE — To ensure monolithic action in faced walls, shear strength between the facing and the backing shall be provided by toothing, bonding or other means.
c) Veneered wall — A wall in which the facing is attached to the backing but not so bonded as to result in a common action under load.
The materials used in masonry construction shall be in accordance with Part 5 ‘Building Materials’.
Masonry units used in construction shall conform to accepted standards [6-4(1)].
3.2.1 Masonry units may be of the following types:
a) Common burnt clay building bricks,
b) Burnt clay fly ash building bricks,
c) Pulverized fuel ash lime bricks,
d) Stones (in regular sized units),
e) Sand-lime bricks,
f) Concrete blocks (solid and hollow),
g) Lime based blocks,
h) Burnt clay hollow blocks,
j) Gypsum partition blocks,
k) Autoclaved cellular concrete blocks, and
m) Concrete stone masonry blocks.
1 Gypsum partition blocks are used only for construction of non-load bearing partition walls.
2 Use of other masonry units, such as, precise stone blocks, fly-ash-lime-gypsum bricks, stabilized mud blocks and other bricks/blocks not covered by the above specifications may also be permitted based on test results.
3.2.2 Masonry units that have been previously used shall not be re-used in brickwork or blockwork construction, unless they have been thoroughly cleaned
and conform to this Section for similar new masonry units.
Mortar for masonry shall conform to accepted standard [6-4(2)].
3.3.1 Mix proportions and compressive strengths of some of the commonly used mortars are given in Table 1.
| Sl No. | Grade of Mortar | Mix Proportions (by Loose Volume) | Minimum Compressive Strength at 28 Days in N/mm ² | ||||
| Cement | Lime | Lime Pozzolana Mixture | Pozzolana | Sand | |||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| 1 | H1 | 1 | (1)/(4) C or B | 0 | 0 | 3 | 10 |
| 2(a) | H2 | 1 | (1)/(4) C or B | 0 | 0 | 4 | 7.5 |
| 2(b) | 1 | (1)/(2) C or B | 0 | 0 | 4(1)/(2) | 6.0 | |
| 3(a) | M1 | 1 | 0 | 0 | 5 | 5.0 | |
| 3(b) | 1 | 1 C or B | 0 | 0 | 6 | 3.0 | |
| 3(c) | 0 | 0 | 1 (LP-40) | 0 | 1(1)/(2) | 3.0 | |
| 4(a) | M2 | 1 | 0 | 0 | 0 | 6 | 3.0 |
| 4(b) | 1 | 2 B | 0 | 0 | 9 | 2.0 | |
| 4(c) | 0 | 1 A | 0 | 0 | 2 | 2.0 | |
| 4(d) | 0 | 1 B | 0 | 1 | 1 | 2.0 | |
| 4(e) | 0 | 1 C or B | 0 | 2 | 0 | 2.0 | |
| 4(f) | 0 | 0 | 1 (LP-40) | 0 | 1(3)/(4) | 2.0 | |
| 5(a) | M3 | 1 | 0 | 0 | 0 | 7 | 1.5 |
| 5(b) | 1 | 3 B | 0 | 0 | 12 | 1.5 | |
| 5(c) | 0 | 1 A | 0 | 0 | 3 | 1.5 | |
| 5(d) | 0 | 1 B | 0 | 2 | 1 | 1.5 | |
| 5(e) | 0 | 1 C or B | 0 | 3 | 0 | 1.5 | |
| 5(f) | 0 | 0 | 1 (LP-40) | 0 | 2 | 1.5 | |
| 6(a) | L1 | 1 | 0 | 0 | 0 | 8 | 0.7 |
| 6(b) | 0 | 1 B | 0 | 1 | 2 | 0.7 | |
| 6(c) | 0 | 1 C or B | 0 | 2 | 1 | 0.7 | |
| 6(d) | 0 | 0 | 1 (LP-40) | 0 | 2(1)/(4) | 0.7 | |
| 6(e) | 0 | 0 | 1 (LP-20) | 0 | 1(1)/(2) | 0.7 | |
| 7(a) | L2 | 0 | 1 B | 0 | 0 | 3 | 0.5 |
| 7(b) | 0 | 1 C or B | 0 | 1 | 2 | 0.5 | |
| 7(c) | 0 | 0 | 1 (LP-7) | 0 | 1(1)/(2) | 0.5 | |
1 Sand for making mortar should be well graded. In case sand is not well graded, its proportion shall be reduced in order to achieve the minimum specified strength.
2 For mixes in Sl No. 1 and 2, use of lime is not essential from consideration of strength as it does not result in increase in strength. However, its use is highly recommended since it improves workability.
3 For mixes in Sl No. 3(a), 4(a), 5(a) and 6(a), either lime C or B to the extent of ¼ part of cement (by volume) or some plasticizer should be added for improving workability.
4 For mixes in Sl No. 4(b) and 5(b), lime and sand should first be ground in mortar mill and then cement added to coarse stuff.
5 It is essential that mixes in Sl No. 4(c), 4(d), 4(e), 5(d), 5(e), 6(b), 6(c), 7(a) and 7(b) are prepared by grinding in a mortar mill.
6 Mix in Sl No. 2(b) has been classified to be of same grade as that of Sl No. 2(a), mixes in Sl No. 3(b) and 3(c) same as that in Sl No. 3(a), mixes in Sl No. 4(b) to 4(f) same as that in Sl No. 4(a), even though their compressive strength is less. This is from consideration of strength of masonry using different mix proportions.
7 A, B and C denote eminently hydraulic lime, semi-hydraulic lime and fat lime respectively, as specified in appropriate standards listed in Part 5 ‘Building Materials’.
Masonry structures gain stability from the support offered by cross walls, floors, roof and other elements, such as, piers and buttresses. Load bearing walls are structurally more efficient when the load is uniformly distributed and the structure is so planned that eccentricity of loading on the members is as small as possible. Avoidance of eccentric loading by providing adequate bearing of floor/roof on the walls providing adequate stiffness in slabs and avoiding fixity at the supports, etc, is especially important in load bearing walls in multi-storey structures. These matters should receive careful consideration during the planning stage of masonry structures.
Lateral supports for a masonry element, such as, load bearing wall or column are intended:
a) to limit slenderness of a masonry element so as to prevent or reduce possibility of buckling of the member due to vertical loads; and
b) to resist horizontal components of forces so as to ensure stability of a structure against overturning.
4.2.1.1 Lateral support may be in the vertical or horizontal direction, the former consisting of floor/roof bearing on the wall or properly anchored to the same and latter consisting of cross walls, piers or buttresses.
4.2.1.2 Requirements of 4.2.1(a) from consideration of slenderness may be deemed to have been met with, if:
a) In case of a wall, where slenderness ratio is based on effective height, any of the following constructions are provided:
RCC floor/roof slab (or beams and slab) irrespective of the direction of span, bears on the supported wall as well as cross walls, to the extent of at least 90 mm;
RCC floor/roof slab not bearing on the supported wall or cross wall is anchored to it with non-corrodible metal ties of 600 mm length and of section not less than 6 mm × 30 mm, and at intervals not exceeding 2 m, as shown in Fig. 4; and

= Cement concrete only at places where anchors are provided (200 mm in width in the direction perpendicular to the plane of paper)
FIG. 4 ANCHORING OF RCC SLAB WITH MASONRY WALL (WHEN SLAB DOES NOT BEAR ON WALL)

FIG. 5 TYPICAL DETAILS FOR ANCHORAGE OF SOLID WALLS

anchors shall be provided in the direction of span of timber joists as well as in its perpendicular direction, at intervals of not more than 2 m in buildings up to two storeys and 1.25 m for buildings more than two storeys in height.
1 In case precast RCC units are used for floors and roofs, it is necessary to interconnect them and suitably anchor them to the cross walls so that they can transfer lateral forces to the cross walls.
2 In case of small houses of conventional designs, not exceeding two storeys in height, stiffening effect of partitions and cross walls is such that metal anchors are normally not necessary in case of timber floor/roof and precast RCC floor/roof units.
In case of a wall, when slenderness ratio is based on its effective length; a cross wall/pier/buttress of thickness equal to or more than half the thickness of the supported wall or 90 mm, whichever is more, and length equal to or more than one-fifth of the height of wall, is built at right angle to the wall (see Fig. 7) and bonded to it according to provision of 4.2.2.2 (d);

FIG. 7 MINIMUM DIMENSION FOR MASONRY WALL OR BUTTRESS EFFECTIVE LATERAL SUPPORT
c) In case of a column, an RCC or timber beam/R S joist/roof truss, is supported on the column. In this case, the column will not be deemed to be laterally supported in the direction at right angle to it; and
d) In case of a column, an RCC beam forming a part of beam and slab construction, is supported on the column, and slab adequately bears on stiffening walls. This construction will provide lateral support to the column, in the direction of both horizontal axes.
A wall or column subject to vertical and lateral loads may be considered to be provided with adequate lateral
support from consideration of stability, if the construction providing the support is capable of resisting some of the following forces:
a) Simple static reactions at the point of lateral support to all the lateral loads; plus
b) 2.5 percent of the total vertical load that the wall or column is designed to carry at the point of lateral support.
4.2.2.1 For the purpose specified in 4.2.2, if the lateral supports are in the vertical direction, these should meet the requirements given in 4.2.1.2(a) and should also be capable of acting as horizontal girders duly anchored to the cross wall so as to transmit the lateral loads to the foundations without exceeding the permissible stresses in the cross walls.
4.2.2.2 In case of load bearing buildings up to four storeys, stability requirements of 4.2.2 may be deemed to have been met with, if:
a) height to width ratio of building does not exceed 2;
b) cross walls acting as stiffening walls continuous from outer wall to outer wall or outer wall to a load bearing inner wall, and of thickness and spacings as given in Table 2 are provided. If stiffening wall or walls that are in a line, are interrupted by openings, length of solid wall or walls in the zone of the wall that is to be stiffened shall be at least one-fifth of height of the opening as shown in Fig. 8;
c) floors and roof either bear on cross walls or are anchored to those walls as in 4.2.1.2 such that all lateral loads are safely transmitted to those walls and through them to the foundation; and
| Sl No. | Thickness of Load Bearing Wall to be Stiffened | Height ¹⁾ of Storey Not to Exceed | Stiffening Wall ¹⁾ | ||
| Thickness not less than | Maximum Spacing | ||||
| 1 to 3 storeys mm | 4 to 6 storeys mm | m | |||
| (1) | mm (2) | m (3) | (4) | (5) | (6) |
| i) | 100 | 3.2 | 100 | — | 4.5 |
| ii) | 200 | 3.2 | 100 | 200 | 6.0 |
| iii) | 300 | 3.4 | 100 | 200 | 8.0 |
| iv) | Above 300 | 5.0 | 100 | 200 | 8.0 |
Effective height of a wall shall be taken as shown in Table 4 (see Fig. 11).
NOTE — A roof truss or beam supported on a column meeting the requirements of 4.2.2.1 is deemed to provide lateral support to the column only in the direction of the beam/truss.
In case of a column, effective height shall be taken as actual height for the direction it is laterally supported and twice the actual height for the direction it is not laterally supported (see Fig. 12).
| Sl No. | Condition of Support | Effective Height |
| (1) | (2) | (3) |
| i) | Lateral as well as rotational restraint (that is, full restraint) at top and bottom. For example, when the floor/roof spans on the walls so that reaction to load of floor/roof is provided by the walls, or when an RCC floor/roof has bearing on the wall (minimum 9 cm), irrespective of the direction of the span foundation footings of a wall give lateral as well as rotational restraint | 0.75 H |
| ii) | Lateral as well as rotational restraint (that is, full restraint) at one end and only lateral restraint (that is, partial restraint) at the other. For example, RCC floor/roof at one end spanning or adequately bearing on the wall and timber floor/roof not spanning on wall, but adequately anchored to it, on the other end | 0.85 H |
| iii) | Lateral restraint, without rotational restraint (that is, partial restraint) on both ends. For example, timber floor/roof, not spanning on the wall but adequately anchored to it on both ends of the wall, that is, top and bottom | 1.00 H |
| iv) | Lateral restraint as well as rotational restraint (that is, full restraint) at bottom but have no restraint at the top. For example, parapet walls with RCC roof having adequate bearing on the lower wall, or a compound wall with proper foundation on the soil. | 1.50 H |
| NOTES | ||
| 1 H is the height of wall between centres of support in case of RCC slabs and timber floors. In case of footings or foundation block, height (H) is measured from top of footing or foundation block. In case of roof truss, height (H) is measured up to bottom of the tie beam. In case of beam and slab construction, height should be measured from centre of bottom slab to centre of top beam. All these cases are illustrated by means of examples shown in Fig. 11. | ||
| 2 For working out effective height, it is assumed that concrete DPC, when properly bonded with masonry, does not cause discontinuity in the wall. | ||
| 3 Where memberane type damp-proof course or termite shield causes a discontinuity in bond, the effective height of wall may be taken to be greater of the two values calculated as follows: | ||
| a) consider H from top of footing ignoring DPC and take effective height as 0.75 H. | ||
| b) consider H from top of DPC and take effective height as 0.85 H. | ||
| 4 When assessing effective height of walls, floors not adequately anchored to walls shall not be considered as providing lateral support to such walls. | ||
| 5 When thickness of a wall bonded to a pier is at least two-thirds of the thickness of the pier measured in the same direction, the wall and pier may be deemed to act as one structural element. | ||

FIG. 11 EFFECTIVE HEIGHT OF WALL

1 A roof truss or beam supported on a column meeting the requirements of 4.2.2.1 is deemed to provide lateral support to the column only in the direction of the beam/truss.
2 When floor or roof consisting of RCC beams and slabs is supported on columns, the columns would be deemed to be laterally supported in both directions.
When openings occur in a wall such that masonry between the openings is by definition a column, effective height of masonry between the openings shall be reckoned as follows:
a) When wall has full restraint at the top:
Effective height for the direction perpendicular to plane of wall equals 0.75 H plus 0.25 H , where H is the distance between supports and H is the height of the taller opening; and
Effective height for the direction parallel to the wall equals H, that is, the distance between the supports.
b) When wall has partial restraint at the top and bottom:
0.5 H and it is equal to 2 H when height of any opening exceeds 0.5 H; and
Effective length of a wall shall be as given in Table 5.
Effective thickness to be used for calculating slenderness ratio of a wall or column shall be obtained as in 4.5.1 to 4.5.5.
4.5.1 For solid walls, faced walls or columns, effective thickness shall be the actual thickness.
4.5.2 For solid walls adequately bonded into piers, buttresses, effective thickness for determining slenderness ratio based on effective height shall be the actual thickness of wall multiplied by stiffening coefficient as given in Table 6. No modification in effective thickness, however, shall be made when slenderness ratio is to be based on effective length of walls.
4.5.3 For solid walls or faced walls stiffened by cross walls, appropriate stiffening coefficient may be
| (SI No. | Conditions of Support (See Fig. 13) | Effective Length |
| (1) | (2) | (3) |
| i) | Where a wall is continuous and is supported by cross wall and there is no opening within a distance of H/8 from the face of cross wall (see Fig. 13)orWhere a wall is continuous and is supported by piers/buttresses conforming to4.2.1.2(b) | 0.8 L |
| ii) | Where a wall is supported by a cross wall at one end and continuous with cross wall at other endorWhere a wall is supported by a pier/buttress at one end and continuous with pier/buttress at other end conforming to4.2.1.3(b) | 0.9 L |
| iii) | Where a wall is supported at each end by cross wallorWhere a wall is supported at each end by a pier/buttress conforming to4.2.1.2(b) | 1.0 L |
| iv) | Where a wall is free at one end and continuous with a pier/buttress at the other endorWhere a wall is free at one end and continuous with a pier/buttress at the other end conforming to4.2.1.2(b) | 1.5 L |
| v) | Where a wall is free at one end and supported at the other end by a cross wallorWhere a wall is free at one end and supported at the other end by a pier/buttress conforming to4.2.1.2(b)where L = Length of wall from or between centres of cross wall, piers or buttress; and H = Actual height of wall between centres of adequate lateral support. | 2.0 L |
| NOTE — In case there is an opening taller than 0.5 H in a wall, ends of the wall at the opening shall be considered as free. Cross walls shall conform to4.2.2.1(d). | ||

determined from Table 6 on the assumption that the cross walls are equivalent to piers of width equal to the thickness of the cross wall and of thickness equal to three times the thickness of stiffened wall.
| Sl No. | Ratio S pw p | Stiffening Coefficient | ||
| t pt w = 1 | t pt w = 2 | t pt w = 3 or more | ||
| (1) | (2) | (3) | (4) | (5) |
| i) | 6 | 1.0 | 1.4 | 2.0 |
| ii) | 8 | 1.0 | 1.3 | 1.7 |
| iii) | 10 | 1.0 | 1.2 | 1.4 |
| iv) | 15 | 1.0 | 1.1 | 1.2 |
| v) | 20 or more | 1.0 | 1.0 | 1.0 |
where
S p = Centre-to-centre spacing of the pier or cross wall,
t p = Thickness of pier as defined in 2.3.2 (see Fig. 1),
t w = Actual thickness of the wall proper (see Fig. 1), and
w p Width of the pier in the direction of the wall or the actual thickness of the cross wall.
NOTE — Linear interpolation between the values given in this table is permissible but not extrapolation outside the limits given.
4.5.4 For cavity walls with both leaves of uniform thickness throughout, effective thickness shall be taken as two-thirds of the sum of the actual thickness of the two leaves.
4.5.5 For cavity walls with one or both leaves adequately bonded into piers, buttresses or cross walls at intervals, the effective thickness of the cavity wall shall be two-thirds of the sum of the effective thickness of each of the two leaves; the effective thickness of each leaf being calculated using 4.5.1 or 4.5.2 as appropriate.
For a wall, slenderness ratio shall be effective height divided by effective thickness or effective length divided by the effective thickness, whichever is less. In case of a load bearing wall, slenderness ratio shall not exceed that given in Table 7.
| Number of Storeys | Maximum Slenderness Ratio | |
| Using Portland Cement or Portland Pozzolana Cement in Mortar | Using Lime Mortar | |
| (1) | (2) | (3) |
| Not exceeding 2 | 27 | 20 |
| Exceeding 2 | 27 | 13 |
For a column, slenderness ratio shall be taken to be the greater of the ratios of effective heights to the respective effective thickness, in the two principal directions. Slenderness ratio for a load bearing column shall not exceed 12.
Eccentricity of vertical loading at a particular junction in a masonry wall shall depend on factors, such as extent of bearing, magnitude of loads, stiffness of slab or beam, fixity at the support and constructional details at junctions. No exact calculations are possible to make accurate assessment of eccentricity. Extent of eccentricity under any particular circumstances has, therefore, to be decided according to the best judgement of the designer. Some guidelines for assessment of eccentricity are given in Annex A.
The building as a whole shall be analyzed by accepted principles of mechanics to ensure safe and proper functioning in service of its component parts in relation to the whole building. All component parts of the structure shall be capable of sustaining the most adverse combinations of loads, which the building may be reasonably expected to be subjected to during and after construction.
The angle of dispersion of vertical load on walls shall be taken as not more than 30° from the vertical.
Account may also be taken of the arching action of well-bonded masonry walls supported on lintels and beams, in accordance with established practice. Increased axial stresses in the masonry associated with arching action in this way, shall not exceed the permissible stresses given in 5.4.
Lintels that support masonry construction shall be designed to carry loads from masonry (allowing for arching and dispersion), where applicable and loads received from any other part of the structure. Length of bearing of lintel at each end shall not be less than 90 mm or one-tenth of the span, whichever is more and area of the bearing shall be sufficient to ensure that stresses in the masonry (combination of wall stresses, stresses due to arching action and bearing stresses from the lintel) do not exceed the stresses permitted in 5.4 (see Annex C).
Permissible compressive stress in masonry shall be based on value of basic compressive stress ( f b ) as given in Table 8 and multiplying this value by factors known as stress reduction factor ( k s ) , area reduction factor ( k a ) and shape modification factor ( k p ) as detailed in 5.4.1.1
to 5.4.1.3. Values of basic compressive stress given in Table 8 take into consideration crushing strength of masonry unit and grades of mortar and hold good for values of slenderness ratio not exceeding 6, zero eccentricity and masonry unit having height to width ratio (as laid) equal to 0.75 or less.
Alternatively, basic compressive stress may be based on results of prism test given in Annex B on masonry made from masonry units and mortar to be actually used in a particular job.
This factor, as given in Table 9, takes into consideration the slenderness ratio of the element and also the eccentricity of loading.
This factor takes into consideration smallness of the sectional area of the element and is applicable when sectional area of the element is less than 0.2 m2. The factor k a = 0 . 7 + 1 . 5 A , A being the area of section in m2.
This factor takes into consideration the shape of the unit, that is, height to width ratio (as laid) and is given in Table 10. This factor is applicable for units for crushing strength up to 15 N/mm2.
| Table 8 Basic Compressive Stresses for Masonry (After 28 days)(Clauses 5.4.1 and 6.3.1) | |||||||||||||
| Sl No. | Mortar Type(Ref Table 1) | Basic Compressive Stresses in N/mm2Corresponding to Masonry Units of which Height to Width Ratio does not Exceed 0.75 and Crushing Strength, in N/mm2, is not Less than | |||||||||||
| 3.5 | 5.0 | 7.5 | 10 | 12.5 | 15 | 17.5 | 20 | 25 | 30 | 35 | 40 | ||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) | (14) |
| i) | H1 | 0.35 | 0.50 | 0.75 | 1.00 | 1.16 | 1.31 | 1.45 | 1.59 | 1.91 | 2.21 | 2.5 | 3.05 |
| ii) | H2 | 0.35 | 0.50 | 0.74 | 0.96 | 1.09 | 1.19 | 1.30 | 1.41 | 1.62 | 1.85 | 2.1 | 2.5 |
| iii) | M1 | 0.35 | 0.50 | 0.74 | 0.96 | 1.06 | 1.13 | 1.20 | 1.27 | 1.47 | 1.69 | 1.9 | 2.2 |
| iv) | M2 | 0.35 | 0.44 | 0.59 | 0.81 | 0.94 | 1.03 | 1.10 | 1.17 | 1.34 | 1.51 | 1.65 | 1.9 |
| v) | M3 | 0.25 | 0.41 | 0.56 | 0.75 | 0.87 | 0.95 | 1.02 | 1.10 | 1.25 | 1.41 | 1.55 | 1.78 |
| vi) | L1 | 0.25 | 0.36 | 0.53 | 0.67 | 0.76 | 0.83 | 0.90 | 0.97 | 1.11 | 1.26 | 1.4 | 1.06 |
| vii) | L2 | 0.25 | 0.31 | 0.42 | 0.53 | 0.58 | 0.61 | 0.65 | 0.69 | 0.73 | 0.78 | 0.85 | 0.95 |
| NOTES | |||||||||||||
| 1 The table is valid for slenderness ratio up to 6 and loading with zero eccentricity. | |||||||||||||
| 2 The values given for basic compressive stress are applicable only when the masonry is properly cured. | |||||||||||||
| 3 Linear interpolation is permissible for units having crushing strengths between those given in the table. | |||||||||||||
| 4 The permissible stress for random rubble masonry may be taken as 75 percent of the corresponding stress for coarsed walling of similar materials. | |||||||||||||
| 5 The strength of ashlar masonry (natural stone masonry of massive type with thin joints) is closely related to intrinsic strength of the stone and allowable working stress in excess of those given in the table may be allowed for such masonry at the discretion of the designer. | |||||||||||||
| 6 For calculation of basic compressive stress of stabilized mud block having thickness 100 mm or more, reference to specialist literature may be made. | |||||||||||||
| Slenderness Ratio | Eccentricity of Loading Divided by the Thickness of the Member | |||||
| 0 | 1/24 | 1/12 | 1/6 | 1/4 | 1/3 | |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) |
| 6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| 8 | 0.95 | 0.95 | 0.94 | 0.93 | 0.92 | 0.91 |
| 10 | 0.89 | 0.88 | 0.87 | 0.85 | 0.83 | 0.81 |
| 12 | 0.84 | 0.83 | 0.81 | 0.78 | 0.75 | 0.72 |
| 14 | 0.78 | 0.76 | 0.74 | 0.70 | 0.66 | 0.66 |
| 16 | 0.73 | 0.71 | 0.68 | 0.63 | 0.58 | 0.53 |
| 18 | 0.67 | 0.64 | 0.61 | 0.55 | 0.49 | 0.43 |
| 20 | 0.62 | 0.59 | 0.55 | 0.48 | 0.41 | 0.34 |
| 22 | 0.56 | 0.52 | 0.48 | 0.40 | 0.32 | 0.24 |
| 24 | 0.51 | 0.47 | 0.42 | 0.33 | 0.24 | — |
| 26 | 0.45 | 0.40 | 0.35 | 0.25 | — | — |
| 27 | 0.43 | 0.38 | 0.33 | 0.22 | — | — |
NOTES
1 Linear interpolation between values is permitted.
2 Where in special cases the eccentricity of loading lies between 1/3 and 1/2 of the thickness of the member, the stress reduction factor should vary linearly between unity and 0.20 for slenderness ratio of 6 and 20 respectively.
3 Slenderness ratio of a member for sections within 1/8 of the height of the member above or below a lateral support may be taken to be 6.
| Height to Width Ratio of Units(as Laid) | Shape Modification Factor ( kp ) for Units Having Crushing Strength in N/mm2 is | |||
| 5.0(2) | 7.5(3) | 10.0(4) | 15.0(5) | |
| Up to 0.75 | 1.0 | 1.0 | 1.0 | 1.0 |
| 1.0 | 1.2 | 1.1 | 1.1 | 1.0 |
| 1.5 | 1.5 | 1.3 | 1.2 | 1.1 |
| 2.0 to 4.0 | 1.8 | 1.5 | 1.3 | 1.2 |
NOTE — Linear interpolation between values is permissible.
5.4.1.4 Increase in permissible compressive stresses allowed for eccentric vertical loads, lateral loads under certain conditions
In members subjected to eccentric and/or lateral loads, increase in permissible compressive stress is allowed as follows:
a) When resultant eccentricity ratio exceeds 1/24 but does not exceed 1/6, 25 percent increase in permissible compressive stress is allowed in design.
b) When resultant eccentricity ratio exceeds 1/6, 25 percent increase in permissible stress is allowed but the area of the section under
tension shall be disregarded for computing the load carrying capacity of the member.
NOTE — When resultant eccentricity ratio of loading is 1/24 or less, compressive stress due to bending shall be ignored and only axial stress need be computed for the purpose of design.
When a wall is subjected to a concentrated load (a load being taken to be concentrated when area of supporting wall equals or exceeds three times the bearing area), certain increase in permissible compressive stress may be allowed because of dispersal of the load. Since, according to the present state of art, there is diversity of views in regard to manner and extent of dispersal, design of walls subjected to concentrated loads may, therefore, be worked out as per the best judgement of the designer. Some guidelines in this regard are given in Annex C.
As a general rule, design of masonry shall be based on the assumption that masonry is not capable of taking any tension. However, in case of lateral loads normal to the plane of wall, which causes flexural tensile stress, as for example, panel, curtain partition and free standing walls, flexural tensile stresses as follows may be permitted in the design for masonry:
– 0.07 N/mm2 for bending in the vertical direction where tension developed is normal to bed joints.
– 0.14 N/mm2 for bending in the longitudinal direction where tension developed is parallel to bed joints, provided crushing strength of masonry units is not less than 10 N/mm2.
Grade M2 mortar – 0.05 N/mm2 for bending in the vertical direction where tension developed is normal to bed joints.
0.10 N/mm2 for bending in the longitudinal direction where tension developed i s parallel to bed joints, provided crushing strength of masonry units is not less than 7.5 N/mm2.
1 No tensile stress is permitted in masonry in case of waterretaining structures in view of water in contact with masonry. Also no tensile stress is permitted in earth-retaining structures, in view of the possibility of presence of water at the back of such walls.
2 Allowable tensile stress in bending in the vertical direction may be increased to 0.1 N/mm2 for M1 mortar and 0.07 N/mm2 for M2 mortar in case of boundry walls/compound at the discretion of the designer, since there is not much risk to life and property in the event of failure of such walls.
In case of walls built in mortar not leaner than Grade M1 (see Table 1) and resisting horizontal forces in the plane of the wall, permissible shear stress calculated on the area of bed joints, shall not exceed the value obtained by the formula given below, subject to a maximum of 0.5 N/mm2:
f s = 0. 1 + f d / 6
f= Compressive stress due to dead loads in N/mm2, and
f = Permissible shear stress in N/mm2.
5.4.4 If there is tension in any part of a section of masonry, the area under tension shall be ignored while working out shear stress on the section.

FIG. 8 OPENING IN STIFFENING WALL
d) cross walls are built jointly with the bearing walls and are jointly mortared, or the two interconnected by toothing. Alternatively, cross walls may be anchored to walls to be supported by ties of non-corrodible metal of minimum section 6 mm × 35 mm and length 600 mm with ends bend at least 50 mm; maximum vertical spacing of ties being 1.2 m (see Fig. 9).

FIG. 9 ANCHORING OF STIFFENING WALL WITH SUPPORT WALL
4.2.2.3 In case of halls exceeding 8.0 m in length, safety and adequacy of lateral supports shall always be checked by structural analysis.
4.2.2.4 A trussed roofing may not provide lateral support unless special measures are adopted to brace and anchor the roofing. However, in case of residential and similar buildings of conventional design with trussed roofing having cross walls, it may be assumed that stability requirements are met with by the cross walls and structural analysis for stability may be dispensed with.
4.2.2.5 Capacity of a cross wall, also called shear wall, sometimes to take horizontal loads and consequently bending moments increases, when parts of bearing walls act as flanges to the cross wall. Maximum overhanging length of bearing wall which could effectively function as a flange should be taken as 12 t or H/6, whichever is less in case of T/I shaped walls, and 6 t or H/16, whichever is less in case of L/U shaped walls, where t is the thickness of bearing wall and H is the total height of wall above the level being considered, as shown in Fig. 10.
In case of external walls of basement and plinth, stability requirements of 4.2.2 may be deemed to have been met with, if:
a) bricks used in basement and plinth have a minimum crushing strength of 5 N/mm2 and mortar used in masonry is of Grade M1 or better;
b) clear height of ceiling in basement does not exceed 2.6 m;
c) walls are stiffened according to provisions of 4.2.2.1;
d) in the zone of action of soil pressure on basement walls, traffic load excluding any surcharge due to adjoining buildings does not exceed 5 kN/m2 and terrain does not rise; and
e) minimum thickness of basement walls is in accordance with Table 3.
NOTE — In case there is surcharge on basement walls from adjoining buildings, thickness of basement walls shall be based on structural analysis.
| Sl No. | Height of the Ground Above Basement Floor Level | Minimum Nominal Thickness of Basement | |
| Wall loading (permanent load) less than 50 kN/m | Wall loading (permanent load) more than 50 kN/m | ||
| (1) | (2) | (3) | (4) |
| i) | Up to 1.4 m | Up to 1.75 m | 300 mm |
| ii) | Up to 2 m | Up to 2.5 m | 400 mm |
4.2.2.7 Walls mainly subjected to lateral loads
a) Free standing wall — A free standing wall such as compound wall or parapet wall is acted upon by wind force which tends to overturn it. This tendency to over-turning is resisted by gravity force due to self-weight of wall, and also by flexural moment of resistance on account of tensile strength of

FIG. 10 TYPICAL DETAILS FOR ANCHORAGE OF SOLID WALLS
masonry. Free standing walls shall thus be designed as in 5.5.2.1. If mortar used for masonry cannot be relied upon for taking flexural tension (see 5.4.2), stability of free standing wall shall be ensured such that stability moment of wall due to self-weight equals or exceeds 1.5 times the overturning moment.
b) Retaining wall — Stability for retaining walls shall normally be achieved through gravity action but flexural moment of resistance could also be taken advantage of under special circumstances at the discretion of the designer (see 5.4.2).
Walls and columns bearing vertical loads shall be designed on the basis of permissible compressive stress. Design consists in determining thickness in case of
walls and section in case of columns in relation to strength of masonry units and grade of mortar to be used, taking into consideration various factors, such as slenderness ratio, eccentricity, area of section, workmanship, quality of supervision, etc, subject further to provisions of 5.5.1.1 to 5.5.1.4.
Thickness used for design calculation shall be the actual thickness of masonry computed as the sum of the average dimensions of the masonry units specified in the relevant standard, together with the specified joint thickness. In masonry with raked joints, thickness shall be reduced by the depth of raking, of joints for plastering/pointing.
a) Thickness of each leaf of a cavity wall shall not be less than 75 mm.
b) Where the outer leaf is half masonry unit in thickness, the uninterrupted height and length of this leaf shall be limited so as to avoid undue loosening of ties due to differential movements between the two leaves. The outer leaf shall, therefore, be supported at least at every third storey or at every 10 m of height whichever is less, and at every 10 m or less along the length.
c) Where the load is carried by both leaves of a wall of a cavity construction, the permissible stress shall be based on the slenderness ratio derived from the effective thickness of the wall as given in 4.5.4 or 4.5.5. The eccentricity of the load shall be considered with respect to the centre of gravity of the cross-section of the wall.
d) Where the load is carried by one leaf only, the permissible stress shall be the greater of values calculated by the following two alternative methods:
The slenderness ratio is based on the effective thickness of the cavity wall as a whole as given in 4.5.4 or 4.5.5 and on the eccentricity of the load with respect to the centre of gravity of the cross-section of the whole wall (both leaves). (This is the same method as where the load is carried by both the leaves but the eccentricity will be more when the load is carried by one leaf only.)
The slenderness ratio is based on the effective thickness of the loaded leaf only using 4.5.1 and 4.5.2, and the eccentricity of the load will also be with respect to the centre of gravity of the loaded leaf only.
In either alternative, only the actual thickness of the load bearing leaf shall be used in arriving at the cross-sectional area resisting the load (see 5.5.1.1).
The permissible load per length of wall shall be taken as the product of the total thickness of the wall and the permissible stress in the weaker of the two materials. The permissible stress shall be found by using the total thickness of the wall when calculating the slenderness ratio.
The facing (veneer) shall be entirely ignored in calculations of strength and stability. For the purpose of determining the permissible stress in the backing, the slenderness ratio shall be based on the thickness of the backing alone.
a) Free standing walls, subjected to wind pressure or seismic forces shall be designed on the basis of permissible tensile stress in masonry or stability as in 4.2.2.4. However, in seismic Zones II, free-standing walls may be apportioned without making any design calculations with the help of Table 11 provided the mortar used is of grade not leaner than M1.
b) If there is a horizontal damp-proof course near the base of the wall, that is, not capable of developing tension vertically, the minimum wall thickness should be the greater of that calculated from either:
the appropriate height to thickness ratio given in Table 11 reduced by 25 percent, reckoning the height from the level of the damp-proof course; or
the appropriate height to thickness ratio given in Table 11 reckoning the height from the lower level at which the wall is restrained laterally.
Normally masonry of retaining walls shall be designed on the basis of zero-tension, and permissible compressive stress. However, in case of retaining walls for supporting horizontal thrust from dry materials, retaining walls may be designed on the basis of permissible tensile stress at the discretion of the designers.
| Design Wind Pressure Height to Thickness Ratio N/mm<sup>2</sup>(1) (2) |
|---|
| Up to 285 10575 7860 51 150 4NOTES 1 For intermediate values, linear interpolation is permissible. 2 Height is to be reckoned from 150 mm below ground level or top of footing/foundation block, whichever is higher, and up to the top edge of the wall. 3 The thickness should be measured including the thickness of the plaster. |
For walls and columns, stress worked out separately for vertical loads as in 5.5.1 and lateral loads as in 5.5.2 shall be combined and elements designed on the basis of permissible stress.
Walls subjected to in-plane bending and vertical loads, that is, shear walls shall be designed on the basis of no tension with permissible shear stress and permissible compressive stress.
Non-load bearing walls, such as panel walls, curtain walls and partition walls which are mainly subjected to lateral loads, according to present state of art, are not capable of precise design and only approximate methods based on some tests are available. Guidelines for approximate design of these walls are given in Annex D.
Construction of the following types of load bearing and non-load bearing masonry walls shall be carried out in accordance with good practice [6-4(3)].
a) Brickwork,
b) Stone masonry,
c) Hollow concrete block masonry,
d) Gypsum partition blocks,
e) Autoclaved cellular concrete block masonry, and
f) Lightweight concrete block masonry.
No special provisions on construction are necessary for buildings constructed in Zones II. Special features of construction for earthquake resistant masonry buildings in Zones III, IV and V shall be applicable according to good practice [6-4(3)].
Thickness of walls determined from consideration of strength and stability may not always be adequate in respect of other requirements, such as resistance to fire, thermal insulation, sound insulation and resistance to damp penetration for which reference may be made to the appropriate Parts/Sections of the Code, and thickness suitably increased, where found necessary.
Workmanship has considerable effect on strength of masonry and bad workmanship may reduce the strength of brick masonry to as low as half the intended strength. The basic compressive stress values for masonry as given in Table 8 would hold good for commercially obtainable standards of workmanship with reasonable degree of supervision. If the work is inadequately supervised, strength should be reduced to three-fourth or less at the discretion of the designer.
Masonry units shall be laid on a full bed of mortar with frog, if any, upward such that cross-joints and wall joints are completely filled with mortar. Masonry units which are moved after initial placement shall be relaid in fresh mortar, discarding the disturbed mortar.
Cross-joints in any course of one brick thick masonry wall shall be not less than one-fourth of a masonry unit in horizontal direction from the cross-joints in the course below. In masonry walls more than one brick in thickness, bonding through the thickness of wall shall be provided by either header units or by other equivalent means in accordance with good practice [6-4(4)].
All masonry shall be built true and plumb within the tolerances prescribed below; care shall be taken to keep the perpends properly aligned:
a) Deviation from vertical within a storey shall not exceed 6 mm per 3 m height.
b) Deviation in verticality in total height of any wall of a building more than one storey in height shall not exceed 12.5 mm.
c) Deviation from position shown on plan of any brickwork shall not exceed 12.5 mm.
d) Relative displacement between load bearing walls in adjacent storeys intended to be in vertical alignment shall not exceed 6 mm.
e) Deviation of bed-joint from horizontal in a length of 12 m shall not exceed 6 mm subject to a maximum deviation of 12 mm.
f) Deviation from the specified thickness of bed joints, cross-joints and perpends shall not exceed one-fifth of the specified thickness.
NOTE — These tolerances have been specified from the point of view of their effect on the strength of masonry. The permissible stress recommended in 5.3 may be considered applicable only if these tolerances are adhered to.
Special provision shall be made to control or isolate thermal and other movements so that damage to the fabric of the building is avoided and its structural sufficiency preserved. Design and installation of joints shall be done according to the appropriate recommendations in accordance with good practice [6-4(5)].
6.5.1 Chases, recesses and holes are permissible in masonry only if these do not impair strength and stability of the structure.
6.5.2 In masonry, designed by structural analysis, all chases, recesses and holes shall be considered in structural design and detailed in building plans.
6.5.3 When chases, recesses and holes have not been considered in structural design and are not shown in drawings, these may be provided, subject to the constraints and precautions specified in 6.5.3.1 to 6.5.3.10.
6.5.3.1 As far as possible, services should be planned with the help of vertical chases and use of horizontal chases should be avoided.
6.5.3.2 For load bearing walls, depth of vertical and horizontal chases shall not exceed one-third and onesixth of the wall thickness respectively.
6.5.3.3 Vertical chases shall not be closer than 2 m in any stretch of wall and shall not be located within 345 mm of an opening or within 230 mm of a cross wall that serves as a stiffening wall for stability. Width of a vertical chase shall not exceed thickness of wall in which it occurs.
6.5.3.4 When unavoidable horizontal chases of width not exceeding 60 mm in a wall having slenderness ratio not exceeding 15 may be provided. These shall be located in the upper or lower middle third height of wall at a distance not less than 600 mm from a lateral support. No horizontal chase shall exceed 1 m in length and there shall not be more than 2 chases in any one wall. Horizontal chases shall have minimum mutual separation distance of 500 mm. Sum of lengths of all chases and recesses in any horizontal plane shall not exceed one-fourth the length of the wall.
6.5.3.5 Holes for supporting put-logs of scaffolding shall be kept away from bearings of beams, lintels, and other concentrated loads. If unavoidable, stresses in the affected area shall be checked to ensure that these are within safe limits.
6.5.3.6 No chase, recess or hole shall be provided in any stretch of a masonry wall, the length of which is less than four times the thickness of wall, except when found safe by structural analysis.
6.5.3.7 Masonry directly above a recess or a hole, if wider than 300 mm, shall be supported on a lintel. No lintel, however, is necessary in case of a circular recess or hole exceeding 300 mm in diameter provided upper half of the recess or hole is built as a semi-circular arch of adequate thickness and there is a adequate length of masonry on the sides of openings to resist the horizontal thrust.
6.5.3.8 As far as possible chases, recesses and holes in masonry should be left (inserting sleeves, where necessary) at the time of construction of masonry so as to obviate subsequent cutting. If cutting is unavoidable, it should be done without damage to the surrounding or residual masonry. It is desirable to use such tools for cutting which depend upon rotary and not on heavy impact for cutting action.
6.5.3.9 No chase, recess or hole shall be provided in half-brick load bearing wall, excepting the minimum number of holes needed for scaffolding.
6.6.1 Where corbelling is required for the support of some structural element, maximum projection of masonry unit should not exceed one-half of the height of the unit or one-half of the built-in part of the unit and the maximum horizontal projection of the corbel should not exceed one-third of the wall thickness.
6.6.2 The load per unit length on a corbel shall not be greater than half of the load per unit length on the wall above the corbel. The load on the wall above the corbel, together with four times the load on the corbel, shall not cause the average stress in the supporting wall or leaf to exceed the permissible stresses given in 5.4.
6.6.3 It is preferable to adopt header courses in the corbelled portion of masonry from considerations of economy and stability.
7.4.1 Masonry bearing walls built in mortar, as specified in 7.3.1 unless rationally designed as reinforced masonry shall not be built of greater height than 15 m subject to a maximum of four storeys when measured from the mean ground level to the roof slab or ridge level. The masonry bearing walls shall be reinforced in accordance with 7.6.1.
7.4.2 The bearing walls in both directions shall be straight and symmetrical in plan as far as possible.
7.4.3 The wall panels formed between cross walls and floors or roof shall be checked for their strength in bending as a plate or as a vertical strip subjected to the earthquake force acting on its own mass.
NOTE — For panel walls of 200 mm or larger thickness having a storey height not more than 3.5 m and laterally supported at the top, this check need not be exercised.
For achieving full strength of masonry, the usual bonds specified for masonry should be followed so that the vertical joints are broken properly from course to course. To obtain full bond between perpendicular walls, it is necessary to make a slopping (stepped) joint by making the corners first to a height of 600 mm and then building the wall in between them. Otherwise,
the toothed joint should be made in both the walls alternatively in lifts of about 450 mm (see Fig. 14).

FIG. 14 ALTERNATING TOOTHED JOINTS IN WALLS AT CORNER AND T-JUNCTION
7.4.5 Ignoring tensile strength, free standing walls shall be checked against overturning under the action of design seismic coefficient α h allowing for a factor of safety of 1.5.
7.4.6 Panel or filler walls in framed buildings shall be properly bonded to surrounding framing members by means of suitable mortar (see Table 13) or connected through dowels. If the walls are so bonded they shall be checked according to 7.4.3 otherwise as in 7.4.5.
6.5.3.10 Chases, recesses or holes shall not be cut into walls made of hollow or perforated units, after the units have been incorporated in masonry.