30.1 The planning, design, construction and installation of water supply, drainage and sanitation and gas supply systems shall be in accordance with the provisions of Part 9 - Plumbing Services- Section 1 Water Supply, Drainage and Sanitation, Section 2 – Gas supply of National Building Code of India asamended from time to time.
30.2 Requirements of Water Supply in Building
The total requirements of water supply shall be calculated based on the population as given below:
| Occupancy | Basis |
|---|---|
| Residential Building | 5 persons per tenement |
| Other Buildings | No. of persons on occupant load and area of floors given in Table 10. |
The requirements of water supply for various occupancies shall be as given in Table 15f or as specified by the NIT/ SPA from time to time.
Table No- 15f
PER CAPITA WATER REQUIREMENTS FOR VARIOUS OCCUPANCIES/USES
| Sr. No | Type of Occupancy | Consumption per head per day (in liters) |
| (1) | (2) | (3) |
| 1 | Residential | Residential |
| 1 | (a) in living units | 135 |
| 1 | (b) Hotels with lodging accommodation (per bed) | 180 |
| 2 | Educational: | Educational: |
| 2 | (a) Day Schools | 45 |
| 2 | (b) Boarding Schools | 135 |
| 3 | Institutional (Medical Hospitals): | Institutional (Medical Hospitals): |
| 3 | (a) No. of beds not exceeding 100 | 340 |
| 3 | (b) No. of beds exceeding 100 | 450 |
| 3 | (c) Medical quarters and hostels | 135 |
| 4 | Assembly-Cinema theatres, auditorium etc. (per seat of accommodation). | 15 |
| 5 | Government and Semi-public business. | 45 |
| 6 | Mercantile (Commercial) | Mercantile (Commercial) |
| 6 | (a) Restaurants (per seat) | 70 |
| 6 | (b) Other business buildings. | 45 |
| 7 | Industrial | Industrial |
| (a) Factories where bathrooms are to be provided45 | 45 | |
| (b) Factories where no bath-rooms are required to be provided. | 30 | |
| 8 | Storage (including warehousing) | 30 |
| 9 | Hazardous | 30 |
| 10 | Intermediate / Stations (excluding mail and express stops). | 45 (25)* |
| 11 | Junction Stations | 70 (45)* |
| 12 | Terminal / Stations. | 45 |
| 13 | International and domestic Airports. | 70 |
*The value in parenthesis is for stations where bathing facilities are not provided.
NOTE: The number of persons for Sr. No. (10) to (13) shall be determined by the average No. of passengers: handled by the station daily; due consideration may be given to the staff and workers likely to use the facilities.
Table No- 16
FLUSHING STORAGE CAPACITIES
| Sr.No. | Classification of building | Storage capacity. |
|---|---|---|
| (1) | (2) | (3) |
| 1 | For tenements having common convenience | 900 liters net per w. c. seat. |
| 2 | For residential premises other than tenements having common convenience | 270 liters net for one w. c. seat and 180 liters for each additional seat in the same flat. |
| 3 | For Factories and Workshops | 900 liters per w. c. seat and 180 liters per urinal seat. |
| 4 | For cinemas, public assembly halls, etc. | 900 liters per w. c. seat and 350 liters per urinal seat. |
Table No- 17
DOMESTIC STORAGE CAPACITIES
| Sr No. | No. of Floors | Storage Capacity | Remarks |
| For premises occupied as tenements with common conveniences | |||
| 1 | Floor (Ground) | NIL | Provided no down-take fittings are installed. |
| 2 | Floors 1,2, 3, 4, 5 and upper floors | 500 litres* per tenement | |
| For premises occupied as Flats or blocks | |||
| 1 | Floor (Ground) | NIL | Provided no down-take fittings are installed. |
| 2 | Floors 1,2,3,4,5 and upper floors | 500* litres. | |
Note:
a) If the premises are situated at a place higher than the road level in the front of the premises, storage at ground level shall be provided on the same line as on floor 1.
The above storage may be permitted to be installed provided that the total domestic storage calculated on the above basis is not less than the storage calculation on the number of down-take fittings according to the scales given.
| Down-take taps | 70 litres each |
|---|---|
| Showers | 135 litres each |
| Bathtubs | 200 litres each |
* Subject to provisions of water supply and drainage rules.