21.1 Educational buildings.
Educational buildings shall not be permissible within 60 m. from the existing assembly building and 90 m. from the existing petrol pump.
Educational building shall only be permitted if 40% area is available for playground. This may be available as a part of the same plot as the educational building or as a separate plot under the same ownership within 200 meters of the educational building facility. In case of a separate plot under separate ownership for playground, the educational facility will need to furnish proof of long term lease documents (not less than 30 years) to indicate availability of the playground for the educational use. However, this provision shall not be applicable to already approved existing building wherein construction of additional floor is proposed.
No classroom shall admeasure less than 38 sq. m. with a min dimension of 5.50
The height of any classroom shall not be less than 3.60 m.
Exit Requirements -This shall conform to Regulation No. 19.
Requirements of Water Supply, Drainage and Sanitation: This shall conform to requirements of part VII of these regulations.
Parking spaces - This shall conform to regulation No.16.
FSI – permissible FSI shall be as per Regulation 13.4.1
21.2 Institutional Buildings (Hospital, Maternity Homes and Health Centre, Sanatoria)
Hospitals and Sanatoria shall be constructed on independent plot.
Any Special ward in the hospital building shall not admeasure less than 9.0. sq.m. in area with no side less than 3m
Area of the general wards shall not admeasure less than 40 sq. m. with no side less than 5.5m and minimum internal room height of 3.3m.
Every building shall have a refuge collection area of minimum 7.50 sq. m. size with cover on top and unclosed on at least three sides. The same shall not be allowed in marginal open spaces. Modern method of incineration of the refuge may be adopted.
Exit Requirements-This shall conform to regulation No. 19
Requirements of Water Supply, Drainage and Sanitation - This shall conform to requirements of part VII of these regulations.
Parking Spaces - This shall conform to Regulation No.16.
FSI – permissible FSI shall be as per Regulation 13.4.1
74
Institutional buildings other than hospitals shall have a minimum internal room height of 3.6m.
21.3 Cinema Theatre/Multiplex
Plot for Cinema theatres shall not be located within a distance of 60 m. from the plot boundary of existing or proposed educational or medical or institutional user.
They shall conform to the provisions of Maharashtra Cinema (Regulations) Rules, 1966, as amended from time to time.
Exit Requirements -This shall conform to regulations No.19.
Requirements of Water Supply Drainage and Sanitation -This shall conform to the requirements of part VII of these regulations.
Parking Spaces - This shall conform to regulation No. 16.
FSI – permissible FSI shall be as per Regulation 13.4.1.
21.4 Mercantile Buildings.
All the zones where shops and commercial activities are allowed, minimum area of a shop will be 10 sqm with minimum width of 3m. In R3 and R4 zones, minimum area of shop can be 6 sqm with a minimum width of 2.0 m.
21.5 Industrial Building
In addition of provisions of these regulations, regulations prescribed under Factory Act shall be applicable.
In the case of Industrial Buildings with different operations/processes, the different (gaseous, solid, liquid) effluents shall be so treated, subject to the approval of Maharashtra Prevention of Water Pollution Control Board and Chief Inspector of Steam Boilers and Smoke Nuisance, before letting it out in to the air, ground or water course.
Exit Requirements -This shall conform to Regulation No.19.
Requirements of Water Supply, Drainage and Sanitation: This shall conform to part VII of these regulations
Parking spaces/Loading and unloading spaces-This shall conform to regulation No.16
For construction of industrial building, buffer zone of 23 m. wide shall be left from residential or incompatible zone, wherever necessary. Such buffer zone may be part of sizable required recreational open space. Whenever a buffer zone is required to be left in between industrial zone and any incompatible zones, as mentioned in this Regulation, it shall not be a bar for availing FSI of that area, unless it is a part of required recreational open space or road.