Size: A habitable room shall have a carpet area of minimum 9.0 sq.m except those in the hostels attached to recognised educational institutions, the minimum size of a habitable room for the residence of a single person shall be 7.5 sq. m; the minimum width of a habitable room shall be 2.4 m. One full side of a habitable room shall abut on the open space. Where there is more than one room, one shall be not less than 9.0 sq.m and other 6.50 sq.m.
The size of the room in a single room tenement shall not be less than 12.5 sq. m. with a minimum width of 2.4 m.
17.2.1.2 Height: The height of all rooms for human habitation shall not be less than 2.75 m. measured from the surface of the floor to the lowest point of the ceiling (bottom of slab). The minimum clear head room under beam shall be 2.4 m. In case of centrally air conditioned building, height of the habitable room shall not be less than 2.4 m, measured from the surface of the floor to the underside of the slab or to the underside of the false ceiling.
In the case of pitched roof, the average height shall not be less than 2.75 m. and the minimum height at eaves level shall not be less than 2.1 m.
The maximum internal room height shall be as per the Table No. 8b below.
Table No- 8b
| Sr No | Occupancy Type | Maximum internal height of rooms (meters) |
|---|---|---|
| 1 | Residential | 4.4* |
| 2 | Educational or Institutional (including government offices) | 4.5 |
| 3 | Public occupancy or assembly buildings, star hotels above 3 star category | 4.5* |
| 4 | Business premises - commercial offices | 4.5 |
| 5 | Mercantile - Retail | 5.5 |
| 6 | Mercantile - Wholesale | 5.5 |
| 7 | Auditoriums, cinema halls and theatres with capacity less than 200 persons | 11 |
| 8 | Auditoriums, cinema halls and theatres with capacity more than 200 persons | 14 |
| 9 | Banquet halls and convention halls less than 1000 sqm | 9 |
| 10 | Banquet halls and convention halls more than 1000 sqm | 14 |
| 11 | Industrial buildings | As per industry requirement for process buildings; 4.5m for all other buildings |
| 12 | Storage buildings | 15m in case of warehouses; 4.5m for all other buildings |
| 13 | Hazardous buildings | As per industry requirement for process building; 4.5m for all other buildings |
* Except portions common to two floors in case of duplex flats/ villas or double height areas in case of star category hotels as applicable.
Height of room for Information Technology Establishment (I. T. E.) for any telemetric equipment storage erection facility can have a height as required for effective functioning of that system.
17.2.1.6 In case of double height spaces in residential villas or portions common to two floors of duplex flats, the minimum height shall be 5.65m.