19.1 General - The following general requirement shall apply to exits.
a) Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants in case of fire or other emergency;
b) In every building, exits shall comply with the minimum requirements of this part, except those not accessible for general public use;
c) All exits shall be free of obstructions;
d) No building shall be altered to reduce the number, width or protection of exits to less than that required;
e) Exits shall be clearly visible and the routes to reach the exits shall be clearly marked and sign posted to guide the occupants to the floor concerned;
f) All exit ways shall be properly illuminated;
g) Fire fighting equipment where provided along exits shall be suitably located and clearly marked but must not obstruct the exit way and yet there should be clear indication about its location from either side of the exit way;
h) Alarm devices shall be installed for buildings above 15m in height, to insure prompt evacuation of the occupants concerned through the exits;
i) All exits shall provide continuous means of egress to the exterior of a building or to an exterior open space leading to a street and;
j) Exits shall be so arranged that they shall be reached without passing through another occupied unit.
19.2 Type of Exits
Exits shall be either of horizontal or vertical type. An exit may be doorway, corridor, and passageways to an internal staircase or external staircase, ramps or to a verandah and/or terraces which have access to the street or to roof of a building. An exit may also include a horizontal exit leading to an adjoining building at the same level. Lifts and escalators shall not be considered as exits.
19.3Number and Size of Exits
The requisite number and size of various exits shall be provided, based on number of occupants in each room and floor based on the occupant load, capacity of exits; travel distance and height of building as per provisions of Regulation No. 19.3.1 to 19.3.5.
Arrangement of Exits
Exits shall be so located so that the travel distance on the floor shall not exceed as given below:
Type of Building
Travel Distance
1) Residential, Educational, Institutional and Hazardous occupancies
22.5 m
2) Assembly, Business, Mercantile, Industrial and Storage occupancies
30.0 m
Note: Wherever more than one exit is required for a floor of a building, they shall be placed as remote from each other as possible. All the exits shall be accessible from the entire floor area at all floor levels. For buildings equipped with sprinklers, the maximum travel distance to an exit shall be 1.5 times the distance given above.
Occupant Load
For determining the exits required the number of persons within any floor area or the occupant load shall be based on the actual number of occupants but in no case, less than that specified in Table No. 10
Table No- 10
Sr. No.
Group of Occupancy
Occupant Load Gross Area*in sqm per person
(1)
(2)
(3)
1
Residential
12.5
2
Educational
04.00
3
Institutional
15 (see Note-a)
4
Assembly
(a) with fixed or loose seats and dance floors
0.6 (see Note-b)
(b) without seating facilities including dining rooms
1.5 (see Note-b)
5
Mercantile
(a) Street floor and sales basement
3
(b) Upper sale floors
6
6
Business and industrial
10
7
Storage
30
8
Hazardous
10
*The gross area shall mean plinth area or covered area.
a) Occupant load in dormitory portions of homes for the aged, orphanages, insane asylums, etc. where sleeping accommodation is provided shall be calculated @ not less than 7.5 sq.m. gross area/ person.
b) The gross area shall include, in addition to the main assembly room or space, any occupied connecting room or space in the same storey or in the storeys above or below where entrance is common to such rooms and spaces and they are available for use by the occupants of the assembly space. No deductions shall be made in the gross area for corridors, closets or other sub-divisions. The area shall include all space serving the particular assembly occupancy.
Capacity of Exits
The capacity of exits (doors and stairways) indicating the number of persons that could be safely evacuated through a unit exit width of 50 cm. shall be as given in Table No. 11.
Table No- 11
S.No.
Group or Occupancy
Number of Occupants
Stairways
Ramps
Doors
1
Residential
25
50
75
2
Educational
25
50
75
3
Institutional
25
50
75
4
Assembly
40
50
60
5
Business
50
60
75
6
Mercantile
50
60
75
7
Industrial
50
60
75
8
Storage
50
60
75
9
Hazardous
25
30
40
For all buildings identified in Regulation No. 6.2.6.1 there shall be a minimum of two staircases. They shall be of an enclosed type stairway. At least one of them shall be on the external walls of buildings and shall open directly to the exterior, interior open space or to any open place of safety.
The following minimum width provisions shall be made for stairways:
Type of Building
Min Width of staircase
Residential Buildings (multi-storey)
1.2 m
for Individual House & Row housing with G+2 storeys
0.75 m
Hotel (with accommodation)
1.50 m
Assembly buildings like auditoria, theatres, Cinemas etc., mangal karyalaya, marriage halls.
2.00 m
Institutional Buildings like hospitals & Educational
2.00 m
All other buildings
1.50 m
19.4 Other Requirements of Individual Exits- The detailed requirements of individual exits are given in regulation No. 19.4.1 to 19.4.6.
Doorways:
a) Every exit doorway shall open into an enclosed stairway, a horizontal exit or a corridor or passage way providing continuous and protected means of egress.
b) No exit doorway shall be less than 90 cm in width in case of residential and 100 cm. in width in case of other buildings. Doorways shall be not less than 200 cm. in height. Doorways for bathrooms, water closet, stores etc. shall be not less than 75 cm. wide.
c) Exit doorways shall open outwards, that is away from the room but shall not obstruct the travel along any exit. No door, when open, shall reduce the required width of stairway or landing to less than 90 cm. Overhead or sliding doors shall not be installed.
d) Exit door shall not open immediately upon a flight of stairs, a landing equal to at least the width of the door shall be provided in the stairway at each doorway. Level of landing shall be the same as that of the floor which it serves.
e) Exit doorways shall be openable from the side which they serve without the use of a key.
Revolving Doors :
a) Revolving doors shall not be used as required exits except in residential, business and mercantile occupancies, but shall not constitute more than half the total required door width;
b) When revolving doors are considered as required exit way the following assumptions shall be made;
i) Each revolving door shall be credited one half a unit exit width; and
ii) Revolving doors shall not be located at the foot of a stairway. Any stairway served by a revolving door shall discharge through a lobby or foyer.
Stairways:
a) Interior stair shall be constructed of non-combustible materials throughout;
b) Interior staircase shall be constructed as a self-contained unit with at least one side adjacent to an external wall and shall be completely enclosed;
c) A staircase shall not be arranged around a lift shaft unless the latter is entirely enclosed by a material of required fire- resistance rating. For buildings more than 16m. in height, the staircase location shall be to the satisfaction of Fire Officer, Fire Brigade Authority.
d) Hollow combustible construction shall not be permitted.
e) The minimum width of an internal staircase shall be as per the provisions of regulation No. 19.3.5
f) The minimum width of treads without nosing shall be 25 cm. for an internal staircase for residential buildings. In the case of other buildings, the minimum treads shall be 30 cm. The treads shall be constructed and maintained in a manner to prevent slipping.
g) The maximum height of riser shall be 20 cm. in the case of residential buildings and 15 cm. in the case of other buildings. They shall be limited to 12 per flight. For low income housing scheme in narrow plots, the riser may be provided in one flight.
h) Handrails shall be provided with a minimum height of 90 cm. from the tread,
i) The minimum unobstructed headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
j) No living space, store or other fire risk spaces shall open directly into the external staircase or staircases.
k) External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through a large lobby.
In the case of assembly, institutional, residential, hotels, industrial and hazardous occupancies, the exit sign with arrow indicating the way to the escape route shall be provided on the wall / floor and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipment. Further all landings of floor shall have floor indication boards indicating the floor number. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of appropriate size.
m) In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. Wherever the building is served by more than one staircase, one of the staircases may lead to basement levels, provided the same is separated at ground level by either a ventilated lobby or cut-off screen wall without opening, having a fire resistance of not less than 2 hours with discharge point at two different ends or through enclosures. It shall also be cut off from the basement areas at various basement levels by a protected and ventilated lobby / lobbies. The staircase shall be lighted and ventilated and the minimum size of openings on walls abutting to open spaces shall be 0.3 sq. m. per landing.
Fire escape or external stairs –
For buildings above 15 m. in height fire escape stairs shall be provided subject to the following conditions:
a) Fire escape shall not be taken into account in calculating the evacuation time of building;
b) All fire escapes shall be directly connected to the ground;
c) Entrance to fire escape shall be separate and remote from the internal staircase;
d) The route to fire escape shall be free of obstructions at all times, except a doorway leading to the fire escape; which shall have the required fire resistance;
e) Fire escape shall be constructed of non-combustible materials;
f) Fire escape stairs shall have straight flights not less than 75 cm. wide with 25 cm. treads and risers not more than 20 cm. The number of risers shall be limited to 16 per flight.
g) Handrail shall be of height not less than 90 cm.
h) Fire escape staircase shall be connected to other staircases through common passage at every floor.
i) Unprotected steel frame staircase will not be accepted as means of escape. However, steel staircase in an enclosed fire rated compartment of 2 h. will be accepted as means of access.
Spiral stairs (fire escape) -
The use of spiral staircase shall be limited to low occupant load and to a building of height 9 m. unless they are connected to platforms, such as balconies and terraces to allow escapee to pause.
A spiral fire escape shall not be less than 150 cm. in diameter and shall be designed to give adequate headroom.
Ramps
Ramps for pedestrians-
a) Ramps with a slope of not more than 1 in 10 may be substituted for and shall comply with all the applicable requirements of required stairways as to enclosure capacity and limiting dimensions. Ramps shall be surfaced with approved non-slipping material;
b) The minimum width of the ramps in hospitals shall be 2.25 m;
c) Handrails shall be provided on both sides of the ramp.
Ramps for basement or storeyed parking
a) For parking spaces in a basement and upper floors, at least two ramps of minimum 3.5 m. width each and slope of not steeper than 1:10, shall be provided preferably to the opposite ends. In case of bona-fide hardship, the Chairman, NIT may allow only one ramp, if proposed to be provided due to space restriction, it shall not less than 6.5 m. in width.
b) Such ramps may be permitted in the side and rear marginal open spaces after leaving sufficient space required for movement of firefighting vehicles or 6m whichever is more. Provided that when a building is abutting 3 or more roads, then ramps shall be allowed in front marginal open spaces facing the smaller road or less important road from traffic point of view.
c) If a parking garage is used exclusively for two wheeler parking, minimum width of the ramp shall be 2m in each direction of travel. If the ramp is used for trucks, the minimum width of ramp shall be 6m in case of one way and separate ramps shall be provided for each direction of travel.
Ramps for access to plot from the approach road
In cases when the level of plot and the approach roads are different and ramps are required for access, the entire length of such ramps shall be provided within the plot boundary.
Corridors
a) The minimum width of a corridor other than internal passage shall be calculated based on the provisions of Regulation 19.3.1 to 19.3.3 as per corresponding width of staircase.
b) In case of more than one main staircase of the building interconnected by a corridor or other enclosed space, there shall be at least one smoke stop door across the corridor or enclosed space between the doors in the enclosing walls of any two staircases.
c) The passages (covered or uncovered) including an arcade, a courtyard, a porch or portico, spaces to be left open to sky in accordance with these Regulations, in any premises shall not be used for any other purpose than the one permissible.
Refuge Area
For buildings more than 24 m in height, refuge area of 15 sq.m or an area equivalent to 0.3 sq.m per person to accommodate the occupants of two consecutive floors whichever is higher shall be provided as under:
The refuge area shall be provided on the periphery of the floor or preferably on a cantilever projection and open to air at least on one side protected with suitable railings.
a) For floors above 24 m and upto 39 m – One refuge area on the floor immediately above 24 m.
b) For floors above 39 m –One refuge area on the floor immediately above 39 m and so on after every 15 m.
Note: Residential flats on multi-storeyed buildings with balcony, need not be provided with refuge area. However, flats without balcony or with enclosed balconies shall be provided with refuge area as given above. All refuge areas shall be accessible from common passages/staircases.
Lifts and Escalators
Lifts:
All buildings above 15m height shall have provision of 2 separate lifts and all public and special buildings below 15m height shall have provision of atleast one lift.
a) All the floors shall be accessible for 24 hours by the lifts. The lifts provided in the buildings shall not be considered as a means of escape in case of emergency.
b) Grounding switch at ground floor level to enable the fire service to ground the lift cars in any emergency shall also be provided;
c) The lift machine room shall be separate and no other machinery shall be installed therein.
Escalators:
Escalators may be permitted in addition to required lifts. Such escalators may be permitted in atrium area in shopping malls / public buildings.
Fire Lift
Where applicable, fire lifts shall be provided with a minimum capacity for 8 passengers and fully automated with emergency switch on ground level. In general, buildings 15 m in height or above shall be provided with fire lifts. In case of fire, only fireman shall operate the fire lift. In normal course, it may be used by other persons. Each fire lift shall be equipped with suitable inter-communication equipment for communicating with the control room on the ground floor of the building. The number and location of fire lifts in a building shall be decided after taking into consideration various factors like building population, floor area, compartments, etc.
20 FIRE PROTECTION REQUIREMENTS
All buildings shall be planned, designed and constructed to ensure fire safety and this shall be done in accordance with the regulations mentioned in Part VI of these regulations and Part IV of Fire Protection of National Building Code of India and Maharashtra Fire Prevention and Life Safety Measures Act, 2006, unless otherwise specified in these regulations. In case of buildings identified in Regulation No. 6.2.6.1, the building schemes shall also be cleared by the Fire Officer Fire Brigade Authority.