15.1 Exterior Open Spaces
Provisions for open spaces at the front side/sides and rear of the building shall be as given in Part IV of these Regulations.
Buildings abutting on two or more streets
When a building abuts on two or more streets, the set- backs from the streets shall be such as if the building was fronting each such street.
Open Spaces/ Setbacks Requirements
Side or rear setbacks with respect to the height and depth of the building for light and ventilation:
i) Setbacks on all sides shall be provided as per Regulation 23, Tables 13 and 13(a), for buildings upto 15m height.
ii) For buildings with height between 15m and 24m, setbacks on all sides except front shall be minimum [(H/2) – 4] rounded to the nearest decimeter. This will be subject to a maximum of 20m, subject to a minimum of 3.0m for residential building and 4.5m for a commercial building; where, H = height of the building above ground level.
iii) For buildings above 24m height, the open space on all sides except the front side shall be minimum H/3. Provided that, if length/ depth exceeds 40m, an additional setback of 10 percent length or depth of the building minus 4.0m shall be added to the above required margin.
iv) For buildings that are tower like structures, minimum setback on ground for podium shall be 6m. Setbacks for the tower like portion above podium level shall be as per setbacks for high rise buildings
Provided further that:
i) The open space for separation between any building and a single storey accessory building shall not be less than 1.5m.
ii) The minimum distance between any two buildings with a maximum height of 15m in housing developed by government or semi-government agencies only, shall be 4.5m.
iii) Setbacks in a plot abutting the amenity / recreational open space in the same layout shall not be less than 3m.
iv) Buildings shall be set-back at least 3.0m from an internal means of access in a layout of buildings except in case of campus planning.
Front Margins
Front margin shall be as per Regulation 23.2.1 or as given below, whichever is more.
| Sr No | Height of the building | Front Setback (meters) |
|---|---|---|
| 1 | Above 15 m and upto 24 m | 6.00 m |
| 2 | Above 24 m and upto 37.5 m | 9.00 m |
| 3 | Height above 37.5 m | 12.00 m |
Setbacks Separate for Each Building or Wing within a Plot
The open spaces required under these regulations shall be separate or distinct for each building and where a building has two or more wings, each wing shall have separate or distinct open spaces according to these regulations for the purpose of light and ventilation of the wings.
Setbacks to be provided for the Full Consumption of FSI
Side and rear setbacks of the building shall conform to height of the building regardless of consumption of full FSI permissible for a given zone. Smaller setbacks than required under Regulation 15.1.3 may be permissible if the height of building is restricted permanently to any smaller height and the owner/ developer submits an undertaking to NIT subject to adherence to the minimum setback requirements given in Table 13.
15.2 Interior and Exterior Chowk
15.2.1
a) Interior chowk: Wherever habitable rooms or kitchen derive ventilation from inner chowk or interior open space, the size of such interior open space shall not be less than 3 m x 3m upto height of 15m. For height above than 15m, the area of the interior open space shall not less than H/5 m x H/5 m; where H = height of highest wall of the chowk.
b) Exterior Chowk: The minimum width of exterior chowk (as distinguished from its depth), for the purpose of light and ventilation, shall be not less than 2.4m and depth shall not exceed 1.5 times the width for buildings upto15m height. For height more than 15m, the exterior open space shall not be less than H/6 m x H/6 m; where H = height of the highest wall of the chowk. If width of the exterior chowk is less than 2.4m then it shall be treated as a notch and the provisions of exterior chowk shall not apply. However, if the depth of the exterior chowk is more than the width, the provisions of Regulation 15.1.4 shall apply with respect to the open spaces to be left between the wings.
15.3 Area and Height Limitations
The area and height limitations, height of buildings, floor space index, abutting different road widths shall be as given in Part IV and Regulation No. 15.5.
15.4 Permissible Structures / Projections in Marginal Open Spaces
The following Projections shall be Permissible in Marginal Open Spaces:
a) Projections into open spaces
Every open space provided either interior or exterior shall be kept free from any erection thereon and shall be open to the sky and no cornice, chajja, roof or weather shade more than 0.75 m wide shall overhang or project over the said open space so as to reduce the width to less than the minimum required. However, sloping chajja provided over balcony/ gallery etc. may be permitted to project 0.3 m. beyond balcony projections at an angle of 30 degree from horizontal level. In all instances the clear height below such projections shall be maintained at 2.5m from the finished ground level.
b) A canopy not exceeding 5 m. in length and 2.5 m. in width in the form of cantilever and unenclosed (as defined in Regulation 2.26) over the main entrance providing a minimum clear height of 2.40 m. below the canopy. The canopy shall not have access from upper floors (above floors), for using as sitting out place. There shall be a minimum clearance of 1.5 m. between the plot boundaries and canopy.
Construction of ottas, railings, barricades or supporting columns for canopy shall not be allowed in front marginal open space. However steps may be permitted within 1.2m from the building line. Porch shall be at a clear distance of required minimum setback from the plot boundary.
c) Balconies: Balcony or balconies with a minimum width of 1.00 m and maximum 2.00 m may be permitted subject to the following conditions:
i. In non-congested area, no balcony shall reduce the marginal open space to less than 2 m. In congested area balcony may be permitted on upper floors projecting in front setbacks except over lanes having width 4.50 m. or less.
ii. No balcony shall be allowed on ground floor which shall reduce minimum required front setback or marginal open space.
iii. The width of the balcony will be measured perpendicular to the building upto the outermost edge of balcony.
iv. When provided on upper floors, balconies shall be clear of building setbacks.
d) A projection of maximum 30 cm. on rooftop terrace level may be allowed throughout the periphery of the building provided that the clear height below such a projection is at least 3.2 meters. In case of pitched roof projection of maximum 45 cm. at roof top terrace level throughout periphery of the building shall be allowed.
e) Accessory buildings: The following accessory buildings may be permitted in the marginal open spaces:
i. In an existing building where toilet is not provided, a single storeyed toilet subject to a maximum area of 4.0 sq. m. in the rear or side open space and at a distance of 7.5 m. from the road line or the front boundary and 1.5 m. from other boundaries may be permissible. The Chairman, NIT may reduce 1.5 m. margin in exceptional cases to avoid hardship.
15.5 Height of Building
The maximum height of a building shall be subject to the provisions given below:
a) Buildings on road ROW below 12 meters width shall be limited to a height of 15 meters subject to other restrictions if any.
b) Buildings on road ROW 12 meters width shall be limited to a height of 24 meters subject to other restrictions if any.
c) For buildings of road ROW above 12 meters the maximum height shall not exceed twice the total of width of the road abutting plus front open space subject to other restrictions if any.
d) If a building abuts on two or more streets of different widths, the height of building shall be regulated by the street of greater width.
e) For building in the vicinity of aerodromes, the maximum height of such buildings shall be subject to values framed by the Civil Aviation Authorities or the development permission shall be considered only after applicant produces NOC from Airport Authority.
f) In addition to (e) for Industrial Chimneys coming in the vicinity of aerodromes, it shall be of such height and character as prescribed by Civil Aviation Authorities and all Industrial Chimneys shall be of such character as prescribed by the Chief Inspector of Steam Boilers and Smoke Nuisance, and
g) Buildings intended for hazardous godowns storage of inflammable materials and storage of explosives shall be single storied structures only.
15.6 Height Exemptions
The appurtenant structures such as roof tanks and their supports, ventilation, air-conditioning, lift rooms and similar service equipment, stair cover, chimneys, mobile communication towers, and parapet walls and stilt parking shall be exempted from computation of height of building. Architectural features not exceeding 1m in height shall not be included in computation of height of building.