19.1 General - The following general requirement shall apply to exits.
a) Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants in case of fire or other emergency;
b) In every building, exits shall comply with the minimum requirements of this part, except those not accessible for general public use;
c) All exits shall be free of obstructions;
d) No building shall be altered to reduce the number, width or protection of exits to less than that required;
e) Exits shall be clearly visible and the routes to reach the exits shall be clearly marked and sign posted to guide the occupants to the floor concerned;
f) All exit ways shall be properly illuminated;
g) Fire fighting equipment where provided along exits shall be suitably located and clearly marked but must not obstruct the exit way and yet there should be clear indication about its location from either side of the exit way;
h) Alarm devices shall be installed for buildings above 15m in height, to insure prompt evacuation of the occupants concerned through the exits;
i) All exits shall provide continuous means of egress to the exterior of a building or to an exterior open space leading to a street and;
j) Exits shall be so arranged that they shall be reached without passing through another occupied unit.
19.2 Type of Exits
Exits shall be either of horizontal or vertical type. An exit may be doorway, corridor, and passageways to an internal staircase or external staircase, ramps or to a verandah and/or terraces which have access to the street or to roof of a building. An exit may also include a horizontal exit leading to an adjoining building at the same level. Lifts and escalators shall not be considered as exits.