6.1 Damp Sites:
Wherever the dampness of a site or the nature of the soil renders such precautions necessary, the ground surface of the site between the walls of any building erected thereon shall be rendered damp-proof to the satisfaction of the Authority.
6.2 Distance from Electric Line:
The distance in accordance with the current electricity rules and its amendments from time to time is to be provided between the building and overhead electric supply line.
192–
TABLE-VII. 3
| Vertically | Horizontally | |
|---|---|---|
| a) Low and medium voltage lines and service | 2.50 m. | 1.20 m. |
| lines | ||
| b) High voltage lines up to and including | 3.70 m. | 1.20 m. |
| 11,000 volts | ||
| c) High voltage lines above 11,000 volts and | 3.70 m. | 2.00 m. |
| up to and including 33,000 volts | ||
| d) Extra high voltage lines additional 33,000 | Plus 0.3 mt. for every | Plus 0.3 m. for |
| volts | additional 33,000 V or part thereof | every additional 33,000 V or part thereof |
6.3 Minimum size of site:
The minimum size of sites for the construction of different types of building or different use groups shall be in accordance with provisions of the Plan and any land development Rules and Regulations.
7. Means of Access:
7.1 No Building shall be erected as to deprive any other building of its means of access.
7.2 Every person who erects a building shall not at any time erect or cause or permit to erect or re-erect any building, which in any way encroaches upon or diminishes the area set apart as means of access.
7.3 For buildings identified in these Regulations-9, the following provisions of means of access shall be applicable.
(a) The width of the main street on which the building abuts shall not be less than 12.0m.
(b) If there are any bends or curves in the approach road, sufficient width shall be permitted at the curve to enable the fire tenders to turn, the turning circle shall be at least of 9.0 m. radius.
(c) The approach to the building and open spaces on its all sides up to 6.0 m. width and the layout for the same shall be done in consultation with the 282[Director, Directorate of Fire and Emergency Services] and the same shall be of hard surface capable of taking the weight of fire tender, weighing up to 22 tones for low rise building and 45 tones for building 15 m., and above in height. The said open space shall be kept free of obstructions and shall be motorable.
(d) Main entrance to the premises shall be of adequate width to allow easy access to the fire tender and in no case it shall measure less than 5 m. The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior access way within the plot free for movement of the fire service vehicles. If-archway is provided over the main entrance, the height of the archway shall not be of height less than 5.0m.
282 Substituted vide Amendment Regulations, 2023.
193–
(e) For multi-storeyed group housing schemes on one plot, the approach road shall be 20.0 m. or as per Master Plan/Development Plan provisions and between individual buildings, there shall be 6.0 m. space around.
(f) In case of basement extending beyond the building line, it shall be capable of taking load of 45 tones for a building of height 15.0 m. and above and 22 tones for building height less than 15.0 m.
(g) The external window shall not be blocked by louvers etc. In such case provisions shall be made so that one can enter the building to be rescued through the window by using hydraulic platform etc.