(a) Every bathroom or water closet compartment shall—
214 Substituted vide notification No. 21/1/TCP/2011/Part file/3252 dated 1-8-2011.
99–
(i) Be so situated that at least one of its walls shall be open to external air or open verandah/open balcony not more than 2.00 meters in width or interior open air space as prescribed in these Regulations.
(ii) In case of bathroom inclusive of water closet compartment the floor area shall not be less than 3.00 m2 for which the smallest side shall not be less than 1.25 meters.
(iii) In case of a bathroom exclusive of water closet compartment the floor area shall not be less than 1.50 m2 and the smallest side shall not be less than 1.00 meters.
(iv) In case of separate water closet compartment the floor area shall not be less than 1.25 m2 and the smallest side not less than 1.00 meter.
(v) Have a window or a ventilator open to external air, of a superficial area of not less than 215[0.60 m2] for bathrooms, not less than 0.50 m2 for the water closet if separate and not less than 216[0.80 m2] for bathroom inclusive of water closet.
(vi) Have a ceiling height of not less than 2.20 meters.
(vii) In case of cultural and educational institutions, cinema and hotels buildings, water closet compartments and bathrooms may be allowed without any of their sides directly abutting to an external air provided they are placed within the room, one side of which shall open to external air with a total opening of at least 1/10th of the floor area of the room and provided the ceiling height of such a room is not less than 2.50 meters and the partition height of the water closet compartment and the partition height of the water closet compartment as bathrooms are not more than 2.20 meters from the floor level.
217[(viii) In case of industrial estates/industrial areas, for each industrial unit, minimum one toilet block each for ladies and gents shall be provided separately in addition as required under the Factories Act, 1948 (Central Act 63 of 1948) and the rules made thereunder.]
(b) Every bathroom or water closet compartment shall—
(i) not be directly over or under any room other than another bathroom or water closet compartment, washing place, terrace or bathroom unless it has water tight floor;
(ii) be closed by walls or partitions of bricks or stones or other similar materials. The surface of every such wall or partition shall be finished with a smooth impervious surface up to the height of 1 meter above the floor level or by glazed tiles or any other suitable materials to a height of one meter above the floor level of such room;
215 Inserted vide notification No. 21/1/TCP/2011/Part file/3252 dated 1-8-2011.
216 Inserted vide notification No. 21/1/TCP/2011/Part file/3252 dated 1-8-2011.
217 Inserted vide Amendment Regulations, 2018.
100–
(iii) have an impermeable floor having a suitable drainage towards the building sewer.
(c) No room containing a water closet compartment shall be used for any purpose other than a lavatory and no such room shall open directly into any kitchen or cooking space. Every room containing water closet shall have a door completely closing the entrance to the water closet;
Note:
(1) In the case of hotels, bathrooms and water closet compartments may abut on to and obtain ventilation from an internal passage having width of not less than 1.80 meters. Provided that the bathrooms and water closet compartments have an exhaust ventilation through a duct whose smaller side shall not be less than 0.80 meters, and the other side not less than 1.50 meters, and provided such duct is ventilated at the top and bottom and the duct is accessible from the ground floor level except where mechanical ventilation is used.
(2) RCC slab or loft over a bath and WCC may be permitted above the height of 2.20 meters.
(d) Minimum number of bathrooms, water closet compartments and urinals to be provided for various types of buildings shall be:-
(i) For a single dwelling unit, one bathroom and one WCC either independent or combined;
(ii) For shops, one WCC and one urinal for every 6 shops or part thereof and one additional WCC for ladies.
(iii) For go-downs, service repair garages, workshops, petrol pumps with or without service station, one WCC and one urinal for each building.
(iv) For cinemas, theatres, public assembly halls, 1 WCC for 100 seats or part thereof, 2 urinals for 75 seats or part thereof at each sitting level. In each sanitary block at least 2 washbasins shall be provided. The above facilities shall be suitably apportioned between males and females.
(v) For schools, colleges and other institutional buildings 1 WCC for 100 students or part thereof and 2 urinals for 150 students or part thereof; besides wash basins.
(vi) For markets, business buildings, office buildings, banks, restaurants, etc. 1 WCC and 1 urinal for every 100.00 square meters of floor area or part thereof.
(vii) For residential hotels, lodging houses, etc., 1 WCC and 1 bathroom for every 50.00 square meters of floor area or part thereof besides wash basins.
(viii) For hospitals, nursing homes, one WCC and one bathroom for every 50.00 square meters of floor area or part thereof; besides wash basin.
(ix) For industrial premises, one WCC for every 150.00 square meters of floor area or part thereof; besides wash basin.
101–