(I) General:
(A) The requirements of number of staircases shall supplement the requirement of different occupancies as per clause 6.1 to 6.9 of Part 4 of the National Building Code of India, 2016.
(B) All buildings, as specified in regulation 15.2.1 shall have a minimum of two staircases. The actual number of staircases shall comply with the requirement of 15.9.3.
(C) All exit staircases shall discharge, at the level of exit discharge, to the exit discharge, either,—
(i) directly, or
(ii) through an exit passageway, or
(iii) through a large lobby.
(D) At least 50 percent of the staircases shall discharge as per (i) and/or (ii) above.
(E) The minimum width of tread without nosing shall be 250 mm for staircase of residential buildings. This shall be minimum 300 mm for assembly, hotels, educational, institutional, business and other buildings. The treads shall be constructed and maintained in a manner to prevent slipping. The maximum height of riser shall be 150 mm.
(F) The number of risers shall be limited to 12 per flight. The staircases may be internal staircases or external staircases.
(G) Only enclosed staircase including its door of required fire resistance and rating shall be considered for the purpose of this part of regulations (and shall have details as per regulation 15.9.7 (f).
(II) Internal Staircases:
The internal staircases may be constructed with an external wall, or otherwise, and shall comply with the following requirements, namely:-
(a) Internal stairs shall be constructed of non-combustible materials throughout, and shall have fire resistant rating of minimum 120 minutes.
(b) A staircase shall not be arranged round a lift shaft.
(c) Exits shall not be used as a portion of a supply, return or exhaust air system serving adjoining areas. Any opening(s) shall not be permitted in walls or in doors, separating exits from adjoining areas.
(d) No flue chimney, electromechanical equipment, air conditioning units, gas piping or electrical panels shall be allowed in the stairway.
(e) Notwithstanding the detailed provision for exits in accordance with Regulations 15.8 and 15.9. The following minimum width shall be provided for staircases for respective occupancies:
(i) Residential (A-2): 1.00 meters
125–
(ii) Residential (A-1, A-3 and A-4): 1.25 meters
(iii) Residential Hotel (A-5 and A-6): 1.50 meters
(iv) Assembly : 2.00 meters
Note:– The width of stairs may be accepted to be 1.50 meter in case of assembly occupancy having less than 150 persons.
(v) Educational : 1.50 meters
(vi) Institutional : 2.00 meters
(vii) All other occupancies : 1.50 meters.
(f) A handrail shall be provided on one side of the staircase of width less than 1,500 mm, and on both sides of the staircase of width 1,500 mm and more. The projection of handrail(s) in the staircase width shall not be more than 115 mm.
(g) Handrails may project inside the measured width by not more than 90 mm.
(h) The design of staircase shall also take into account,—
(i) The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 meters.
(ii) Access to exit staircase shall be through a fire door of a minimum 120 minutes fire resistance rating.
(iii) Openings if any shall have a fire rating of atleast 120minutes. The staircase shall be pressurized/Naturally ventilated or cross ventilated as per provisions of Table 6 of clause 4.4.2.5. of Part 4 of the National Building Code of India, 2016. For buildings having height more than 30 meters they shall have cross ventilation (through opposite/adjacent walls or the same shall be ventilated through the corridor) or pressurized.
(iv) No living space, store or other fire risk shall open directly into staircase.
(v) The exit (including staircases) shall be continuous from refuge floors or terrace level, as applicable, to the level of exit discharge.
(vi) No electrical shafts/air conditioning ducts or gas pipes, etc, shall pass through or open in the staircases.
(vii) Lifts shall not open in staircase.
(viii) No combustible material shall be used for decoration/wall paneling in the staircase.
(ix) Beams/columns and other building features shall not reduce the head room/width of the staircase.
(x) The floor indication board, indicating the location/designated number of staircase, respective floor number and direction to exit discharge shall be placed inside the staircase, on the wall nearest to the fire door. It shall be of size not less than 300 mm x 200 mm (see Sketch No. 14.).
126–
(xi) Individual floors shall be prominently indicated on the wall outside the staircase and facing it.
(xii) All staircases shall terminate at the level of exit discharge. The access to the basement shall be by a separate staircase. However, in case of separation of stairs leading from ground (exit discharge) to the upper floors and stairs leading to the basement by fire protection wall and both the stair flights are accessible by separate entries, then access to the basement need not be by a separate staircase.
(xiii) Scissors type staircases shall not be treated as part of exit.
(III) Curved Stairs:
Curved stairs shall not be treated as part means of egress. However, these may be used as part of exit access provided the depth of tread is not less than 280 mm at a point 350 mm from the narrower end of the tread and the smallest radius is not less than twice the stair width.
(IV) External Staircases:
The external staircases are the staircases provided on the external wall/façade, which shall comply with the following requirements, namely:—
(a) External stairs shall always be kept in sound and usable condition.
(b) All external stairs shall be directly connected to the ground.
(c) Entrance to the external stairs shall be separate and remote from the internal staircase.
(d) Where an external staircase is provided, it shall be ensured that the use of it at the time of fire is not prejudiced by smoke and flame from openings (for example, windows, doors) in the external face of the building. Care shall be taken to ensure that no external wall or window opening opens on to or close to an external stair. If such openings exists within 3 meters from an external staircase, they shall be protected with fire rated doors/window assemblies with rating of at least 60 minutes.
(e) The external stairs shall be constructed of non-combustible materials, and any doorway leading to it shall have minimum 120 minutes fire resistance.
(f) The light and ventilation for the staircase shall be provided from an external wall by providing openings of not less than 1/10th of the area of the staircase and such openings shall be provided at each landing stage. The openings shall have a fire rating of atleast 120 minutes.
(g) No external staircase flight of steps shall be inclined at an angle greater than 45 degrees from the horizontal.
(h) External stairs shall have straight flight not less than 1,500 mm wide.
127–
(i) Handrails, to be provided on both sides, shall be of a height not less than 1,000 mm and not exceeding 1,200 mm. There shall be provisions of balusters with maximum gap of 150 mm.
(V) Spiral Stairs:
The use of spiral staircase shall be limited to low occupant load and to a building not exceeding 9 m in height. A spiral staircase shall be not less than 1,500 mm in diameter and shall be designated to give adequate headroom.
15.9.10. Ramps.— (a) In addition to the provisions contained in clause 6 of Part 4 of the National Building Code of India, 2016, ramps shall comply with all the applicable requirements for staircases regarding enclosure, capacity (see Table XXII as specified in regulation 15.9.5) and limiting dimensions.
(b) The slope of a ramp shall not exceed 1 in 12 (8 percent).
(c) Ramps shall be surfaced with approved slip resistant materials that are securely attached. No perforations are permissible on the ramp floors.
(d) Any changes in travel direction in ramp shall be preceded by landings of 1.5 meters x 1.5 meters size.
(e) Ramps and intermediate landings shall continue with no decrease in width along the direction of egress travel.
(f) Outside ramps and landings shall be designed to minimize water accumulation on their surfaces.
(g) Ramps shall have landings located at the top, at the bottom, and at doors opening onto the ramp.
(h) Every landing shall be not less than 1,500 mm long in the direction of travel.
(i) Where the ramp is not part of an accessible route, the ramp landings shall not be required to exceed 1,250 mm in the direction of travel, provided that the ramp has a straight run.
(j) Handrails shall be provided on all ramps on both sides [see regulation 15.9.9 (IV) (i)].
(k) The Minimum width of vehicular ramp to basement shall be 3.60m wide, atleast two ramps shall be provided, located preferably at opposite ends and the maximum gradient of vehicular ramp shall be 1 in 8 (12.5%).
Note: Above requirements at (a) to (j) shall not be applicable to basement car parking ramps.
15.10. Fixed Fire Fighting Installations.—These shall be provided in all buildings depending upon the occupancy use and height in accordance with the provisions of clause 5 of Part 4 of the National Building Code of India, 2016.
15.11. Miscellaneous.—Wherever applicable, Lightning protection of buildings, Compartmentation, Smoke Control, and Additional Occupancy Wise Requirements shall be as per clause 3.4.6.5, 4.5, 4.6 and 6 of Part 4 of the National Building Code of India, 2016. Fire Requirements for Basement and Building Services shall be as per Annexure-III, 27.III. Lightning Protection shall be required for buildings specified in regulation
128–
15.2.1 and also for buildings having Ground or Stilt + 2 floors or more, or for buildings having height 9 meters and above when measured from adjoining Ground. Lightning protection of building shall be installed to the satisfaction of the Electricity Department.].
236[16. Facilities for the Persons with Disabilities and elderly persons.—
16.1. All buildings and recreational spaces including beaches under the occupancies listed below at (i) to (vii) which have access to the public, shall be provided with facilities for persons with disabilities and elderly persons.
(i) Assembly Building.
(ii) Business/commercial/office building/mercantile building.
(iii) Educational buildings.
(iv) Industrial buildings (Arrangement for employees with disabilities are directly related to the type of work they perform. Arrangement for persons with disabilities need not be considered in heavy manufacturing Industry. Arrangement for all persons with disabilities should be incorporated into the design of new light manufacturing factories where persons with disabilities may be employed).
(v) Institutional buildings.
(vi) Residential buildings with 24 dwelling units and more or having 2,000 sq. mts. of built up area and more, at least 20% of the number of units shall comply with the space standards and facilities as per the Harmonised Guidelines and Space Standards for Barrier Free Built Environment for Persons with Disability and Elderly Persons.
(vii) Recreational (Playground, parks, gardens and beaches).