(a) Every habitable room shall have for the admission of light and air, one or more apertures, such as windows, fan-lights, etc., opening directly to external air or into balcony or verandah and of aggregate area inclusive of frames of not less than 1/10th of the carpet area, excluding doors, except in case of hospital wards, dormitories and schools when such apertures are to be not less than 1/6th of the floor area.
Note: No portion of a room shall be assumed to be lighted if it is more than 7.50 meters away from the external façade. However, this rule on 7.50 meters shall not be applicable in case of cultural and institutional buildings and buildings of commercial offices, banks etc. In such cases 1/6th of the floor area shall be kept for the window openings inclusive of frames and exclusive of doors.
(b) Cross ventilation 214[may] be provided in at least one habitable room of a dwelling, either by means of window or ventilator in opposite or adjacent walls.