15.1.1 General Provisions:
Buildings specified in regulation 15.2.1 shall be planned, designed and constructed to ensure adequate fire safety of the buildings, property and inhabitants and this shall be carried out in accordance with the provisions of Part 4 of the National Building Code of India, 2016 except clauses 3.2 and 3.4.4 thereof and any other provisions of the fire safety made in these regulations. Fire Fighting requirement arrangement and installations required in the building shall also be as per the provisions of the Part 4 of the National Building Code of India, 2016. All the technical terms shall have the meaning as defined in Part 4 of the National Building Code of India, 2016 except the terms which are defined in these regulations.
15.1.2. Notwithstanding anything contained in regulation 4.2. (g) and 4.4.2 for high rise buildings, the following provisions of means of access and open spaces (setbacks) shall be ensured:
(a) The width of the main street on which the building abuts shall not be less than 10 meters;
(b) The approach to the building and open spaces on all its sides shall be not less than 6 meters in width, the layout for the same shall be done to the satisfaction of the Directorate of Fire and Emergency Services and the open space shall be of hard surface capable of taking the mass of fire engine weighing up to 45 tonnes. A turning radius of atleast 9 meters shall be provided for movement of fire service vehicles. The said open
235Regulation 15 substituted vide Amendment Regulations, 2023.
116–
space shall be kept free of obstructions and shall be motorable, further no projections shall be allowed in the said open spaces. In case of buildings with no side set backs or setbacks with 1.5 meters or less, a clear height of atleast 5meters shall be maintained below the bottom of lowest structural member and the open space as aforesaid shall be made available through the building on all sides for movement of fire service vehicles.
(c) The main entrance of the plot shall be of adequate width to allow easy access to the fire service vehicles and in no case it shall measure less than 6 meters. The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior access way within the plot free for movement of fire service vehicle. If the main entrance at the boundary wall is built over, the minimum clearance shall be 5 meters.