14.1 Water Supply and Sanitary Installation:
14.1.2 Water Supply:
(a) All premises intended for human habitation, occupancy or use group shall be provided with the supply of pure and wholesome water, neither connected with polluted or unsafe water supply nor subject to the hazards of back flow or back siphonage;
225 Omitted vide notification No. 21/1/TCP/2011/Part file/3252 dated 1-8-2011.
226 Inserted vide notification No. 21/1/TCP/2011/Part file/3252 dated 1-8-2011.
227 Substituted vide Amendment Regulations, 2023.
106–
(b) No connection from any source of public water supply to any water supply installation in any new construction/re-construction/alteration as specified in these rules shall be sanctioned by the P.W.D. (Water Supply) Division without prior sanction of construction licence/occupancy certificate by the Competent Authority.
(c) Application for the supply of water supply connection may however, be entertained without insisting on production of a No Objection Certificate from Competent Authority as prescribed at (b) above, provided that the applicant fulfils all the formalities as required by the PWD–Water Supply Division and tenders an undertaking to the effect that connection so granted shall in no way give any legitimacy to any such construction or structure, which if unauthorized or illegal shall continue to be so even after such connection is released.
(d) The design of the pipe system shall be such that there is no possibility of back-flow towards the source of supply from any cistern or appliance whether by siphonage or otherwise and reflux or non-return valves shall not be relied upon to prevent such back flow.
(e) Where a supply of wholesome water is required as an alternative or standby to a supply of less satisfactory water or is required to be mixed with the latter, it shall be delivered only into a cistern and by pipe or fitting discharging into an air gap at a height above the top edge of the cistern equal to twice its nominal bore and in no case less than 15 centimeters. In all appliances or taps used in water closets a definite air cap shall be maintained.
(f) The bottom of the water service-pipe at all points, shall be at least 30 centimeters above the top of the sewer-line at its highest point, if laid closer than 30 meters horizontally from the building sewer.
(g) No pipe, carrying wholesome water, shall be laid or fixed so as to pass into or through any pipe or fitting, secure outlet or drain or any manhole, connected therewith nor through any ash pit, manure pit, fouled, soiled or porous material or any material of such nature that is likely to cause deterioration of the pipe. Provided that where the laying of such pipe is unavoidable, the piping shall be properly, protected from contact with such soil, material or surrounding matter by being carried through an exterior cast-iron tube or by some other suitable protective covering as approved by Panchayat or P.W.D. (Water Supply) Division. Provided further that any existing piping or fitting laid or fixed which does not comply with the above requirements, shall be removed immediately by the owner and re-laid by him in conformity with the above requirements and to the satisfaction of the P.W.D. (Water Supply) Division.
(h) All pipes including all bends, junctions, tees and elbows and all fittings used in connection with, or forming part of the sanitary installations of a building shall be made of such material and be of such weight and pattern be fixed, joined and painted in such a manner as per specifications laid down by P.W.D.
107–
(i) The planning design and installation of water supply system shall conform to Part IX–Plumbing Services, Section I-Water Supply of National Building Code of India, 2005 unless otherwise specified in these rules.
(j) The per capita requirement of water supply for various occupancies shall be determined as specified in TABLE-XIX below. The overhead tanks shall have adequate capacity of storage for flushing as well as domestic storage.
TABLE-XIX
| Per Capita requirements - | ||
|---|---|---|
| Group | Type of occupancy | Consumption per head per day in liters |
| Group | Residential | 135 |
| A1 | ||
| Group | Special Residential | 180 |
| A2 | ||
| Group B | Educational a) Day schools b) Boarding schools | 45135 |
| Group C | Institutional/Medical a) No. of beds not exceeding 100 b) No. ofbeds exceeding 100 c) Medical quarters and hostels | 340450135 |
| Group D | a) Assembly (per seat of accommodation) other than restaurants b) Assembly (per seat of accommodation) for restaurants | 1570 |
| Group E | Government or Semi-Public | 45 |
| Group F | Mercantile business (Commercial) a) Restaurants (per seat) b) Hotels with lodging accommodation (per bed) c) Other business buildings | 7018045 |
| Group G | Industrial | 45 |
| Group H | Storage (including Warehousing) | 30 |
| Group I | Hazardous | 30 |
(k) A tank or cistern for storage of water shall be water tight properly covered over and shall be constructed of reinforced concrete; G.I. steel, stone masonry or brick work in cement mortar and shall be rendered inside with cement mortar.
(l) In the case of underground storage tanks, the design of the tank shall be such as to provide for the drainage of the tank when necessary and water shall not be allowed to collect round about the tank.
(m) The tank shall be provided with, an overflow pipe, tap or other apparatus, the invert of which shall not be less than 5 centimeters higher than the bottom of the tank.
(n) The tank shall be provided with a draw off which shall-
(i) be so located and fitted as to prevent entry of animals and insects;
108–
(ii) not be connected to a drain or sewer;
(iii) have an open end to permit the overflow pipe to serve as a warning pipe.
(o) All water mains, communication pipes, service and distribution pipes used for water for domestic purposes shall be thoroughly and efficiently disinfected before being taken into use and also after every major repair.
(p) Overhead water tanks and sumps should be provided with mosquito proof lids and their vents shall be covered with mosquito proof nylon mesh. All the structures created for water supply i.e. over head tanks/loft over head tanks and sumps has to abide by the provisions of the design and specifications as laid down in Goa Public Health Act, 1985 (Goa Act 25 of 1985) for prevention of Vector Borne Diseases.
(q) The extent of water to be stored for the fire fighting purpose in the case of multi-storeyed buildings shall be in accordance with Part IV, Fire Prevention and Fire Protection of National Building Code of India, 2005 or as amended from time to time.
14.1.3 Wells:
(a) Wells intended to supply water for human consumption or for domestic purpose shall be–
(i) Not less than 15 meters away from any ash pit, refuse pit, soak pit, earth closet or privy and shall be located on a site upward from the earth closet or privy;
(ii) so situated that contamination by the movement of sub-soil of other water is unlikely;
(iii) of a minimum internal diameter of not less than 1.00 meter;
(iv) of permanent and sound quality construction throughout.
(b) Wells without internal lining shall be permitted only in fields and gardens for purpose of irrigation.
(c) The parapet wall on the head of all wells shall be raised to height not less than 1 meter above the level of the adjoining ground to form a parapet or kerb with a minimum thickness of 20.00 centimeters and shall be surrounded with a paving constructed of impervious material which shall extend for a distance of not less than 1.00 meter in every direction from the parapet framing the well head and the surface of such a paving shall be sloped outward from the well. All such structures created has to abide by the provisions of the design and specifications as laid down in Goa Public Health Act, 1985 (Goa Act 25 of 1985) for prevention of Vector Borne Diseases.
(d) The interior surface of the well or lining of the well shall be rendered impervious to a depth of 3.00 meters measured from the level of the ground immediately adjoining the well head.
109–
(e) A well from which water is drawn by means of a bucket or other similar means shall be provided with a stand for the bucket raised not less than 15.00 centimeters above the level of the paving.
14.1.4 Drainage and Sanitation:
(a) No person shall install or carry out any water-borne sanitary installation or drainage installation or any work in connection with any existing or new building or any other premises without obtaining the previous sanction of the Competent Authority.
(b) Every sanitary/drainage installation from any existing building shall be connected to a public sewer wherever available. All the structures created for Drainage and Sanitary installation i.e. inspection chambers and septic tank has to abide by the provisions of the design and specifications as laid down in Goa Public Health Act, 1985 (Goa Act 25 of 1985) for prevention of Vector Borne Diseases.
(c) No connection to any public sewer line from any new construction/ /reconstruction/alteration as specified in these rules shall be sanctioned by the PWD-Sewerage Division prior to the sanction of building permit/Occupancy Certificate by the Competent Authority.
(d) Wherever public sewer is not available, the sanitary installation shall be connected to septic tank/soak pit and the drainage of waste water to a soak pit or any other waste water recycling/treatment unit of adequate size, to be located within the plot in such manner that it is away from any existing well or water body 228[indicated on the survey plan].
(e) The drainage from the water closet compartment shall be connected to the septic tank through a system of pipes and inspection chambers, laid to a slope sufficient enough to ensure smooth flow.
(f) The drainage of waste water from the bathrooms, kitchen and any other source shall be connected to the soak pit or any other waste water recycling/ /treatment unit through a system of pipes and inspection chambers, laid to a slope sufficient enough to ensure smooth flow.
(g) The size of septic tank and soak pit should be proportionate to the number of users. Following design criteria are recommended by the Directorate of Health Services for the Septic Tank:-
(i) Capacity-A capacity of 20 to 30 gallons (2.5 cft to 5 cft) per person is recommended for household septic tanks. The minimum capacity should be 500 gallons. Septic tanks are not recommended for large communities.
(ii) Length/Breadth-The length shall usually be twice the breadth.
228 Inserted vide notification No. 21/1/TCP/2011/Part file/3252 dated 1-8-2011.
110–
(iii) Depth-It should vary from 1.50 mts to 2.00 mts.
(iv) Liquid depth-The recommended liquid depth is only 1.20 mts.
(v) Air space-There should be a minimum air space of 30 cm. between the level of liquid in the tank and the under surface of the cover.
(vi) There should be an inlet and outlet pipe which would be submerged.
(vii) Cover-The septic tank shall be covered by a concrete slab of suitable thickness and provided with a manhole.
(h) The planning, design and installation of all drainage of waste water and sanitary installation shall conform to Part IX, Plumbing Services, Section 2, Drainage and sanitation, of National Building Code of India, 2005, as amended from time to time, unless otherwise specified in these rules.