Use water efficient plumbing fixtures (as applicable) whose flow rates meet the baseline criteria in aggregate. The total annual water consumption of the building should not exceed the total base case water consumption computed. The baseline criteria are as below:
| S. No. | Fixture Type | Maximum Flow Rate / Consumption | Duration Estimated Daily Uses per FTE** |
|---|---|---|---|
| 1 | Water Closet (Full Flush) | 6 LPF | 1 for male 1 for female |
| 2 | Water Closet (Half Flush) | 3 LPF | 2 for female |
| 3 | Urinals | 4 LPF | 2 for male |
| 4 | Faucets / Taps* | 6 LPF | 4 |
| 5 | Health Faucet* | 6 LPF | 1 |
| 6 | Shower Head / Handheld Spray* | 10 LPF | 0.1 |
Source: Uniform Plumbing Code – India
-
LPF: Litre per flush
-
*Reporting pressure for these fixtures shall be at 3 bar.
-
**Full Time Equivalent (FTE) represents a regular building occupant who spends 8 hours per day in the building. Part-time or overtime occupants have FTE values based on their hours per day divided by 8.
-
Plumbing fixtures certified by IGBC under Green Product Certification Programme can be used by the project to show compliance, as and when certified fixtures are available
As per MoEF&CC guidelines, water reduction can be achieved up to 36% using water conserving fittings with sensors, auto valves, pressure reducing device wherever possible which can result in significant reduction in water consumption.
i. Water closets (WCs):
Conventional toilets use 9 litres of water per flush. Low flush toilets are available with flow rate of 6.0 litres and 3.0 litres of water per flush.
Dual flush adapters can be used for standard flushing for solid waste and a modified small flush for liquid waste
Flush valves with 20-25 mm inlets can be used for restricting the water flow