The building plans for buildings covered under Rule 27 of Delhi Fire Service Rules shall be marked fire and life safety measures as per the National Building Code of India concerning minimum standards for fire prevention and fire protection as covered under Rule 33 of the Delhi Fire Service Rules as amended from time to time; unless otherwise specified in these bye –laws.
9.3.1 Fire Escape Staircase
a. Fire Escape will be an additional external stair case and shall not to be taken in to account for calculating the evacuation of the occupants of a specific floor. It shall not be inclined at an angle greater than 450 from the horizontal.
b. All fire escapes shall be continuous from ground to terrace.
c. Entrance to fire escape shall be separate and remote from the internal staircase.
d. The route and enclosure to fire escape shall be free of obstructions at all times, except a doorway leading to the fire escape which shall have the required fire resistance. (refer NBC Part 4).
e. Fire escape shall be constructed of non-combustible materials of required fire resistance (refer NBC Part 4). Unprotected steel frame staircase will not be accepted as fire escape.
f. Handrails shall be as per Chapter 11.
g. Scissors staircase can also be used as fire escape subject to the condition that the two entrances to the scissors staircase are not less than 9.0 m apart.
h. In case the provision is for a single staircase, the same shall be separated at the ground floor level to have an access to the basement (if provided).
i. The staircase enclosure if on external wall of the building shall be ventilated to atmosphere at each landing or in case it is in the core of the building it shall be maintained at a positive pressure as mentioned in NBC part IV, Fire and Life Safety, with both automatic and manual operation facilities and fire alarm systems.
j. Fire escape staircases shall have straight flight not less than 1.5 m wide with 30 cm treads and risers not more than 15 cm. The number of risers shall be limited to 12 per flight.
k. Spiral stairs can be used subject to, the use of spiral staircase shall be limited to low occupant load and to a building of height 9.0 m. further a spiral fire escape shall not be less than 1.5 m in diameter and shall be designed to adequate head room.
9.3.2 Pressurization of Staircases (Protected Escape Routes)
For pressurization specifications of various building components refer NBC Chapter 4 Fire and Life Safety.
9.3.3.Lifts
a. Slope in the floor of lift lobby shall be made to prevent water, used during firefighting, etc., at any landing, from entering the lift shafts.
b. A sign shall be posted and maintained on every floor at or near the lift indicating that in case of fire, occupants shall use the stairs unless instructed otherwise. The sign shall also contain a plan for each floor showing the locations of the stairways. Alternate source of power supply shall be provided for all the lifts through a manually operated changeover switch.
c. Fire Lifts– Following details shall apply for a fire lift:
i. To enable fire services personnel to reach the upper floors with the minimum delay, one fire lift per 1200 sq.m of floor area shall be provided and shall be available for the exclusive use of the firemen in an emergency.
ii. It shall have loading capacity of not less than 545 kg (8 persons lift) with automatic closing doors of minimum 0.8 m width.
iii. The electric supply shall be on a separate service from electric supply mains in a building and the cables run in a route safe from fire, that is, within the lift shaft. Lights and fans in the elevators having wooden paneling or sheet steel construction shall be operated on 24 V supply.
iv. Firefighting lift should be provided with a ceiling hatch for use in case of emergency, so that when the lift car gets stuck up, it shall be easily openable.
v. In case of failure of normal electric supply, it shall automatically trip over to alternate supply. For apartment houses, this changeover of supply could be done through manually operated change over switch also. Alternatively, the lift shall be so wired that in case of power failure, it comes down at the ground level and comes to stand-still with door open.
vi. The operation of a fire lift is by a simple toggle or two-button switch situated in a glass fronted box adjacent to the lift at the entrance level. When the switch is on, landing call points will become inoperative and the
lift will be on car control only or on a priority control device. When the switch is off, the lift will return to normal working. This lift can be used by the occupants in normal times.
vii. The words ‘Fire Lift’ shall be conspicuously displayed in fluorescent paint on the lift landing doors at each floor level.
viii. The speed of the fire lift shall be such that it can reach the top floor from ground level within1 minute.
9.3.4 Basement
Refer clause 8.4.5 for details of basement.
9.3.5 Refuge Chutes
a. Hoppers to refuse chutes shall be situated in well ventilated positions and the same shall be continued upwards shall have opening at least 1.0 m above roof level for venting purpose and they shall have an enclosure
b. Wall of non-combustible material with fire resistance of not less than two hour. They shall not be located within the staircase enclosure or service shafts, or air-conditioning shafts inspection panel and doors shall be tight fitting with one hour fire resistance; the chutes should be as far away as possible from exit.
c. Refuge chambers shall have walls and floors of roofs constructed of non-combustible and impervious material and shall have a fire resistance of not less than two hours. They shall be located at a safe distance from exit routes.
9.3.6 Refuge Area
a. For buildings more than 24.0 m in height, refuge area of 15.0 sq.m or an area equivalent to 0.3 sq.m per person to accommodate the occupants of two consecutive floors whichever is higher shall be provided as under:
i. For floors above 24.0 m and up to 39.0 m – One refuge area on the floor immediately above 24.0 m.
ii. For floors above 39.0 m – One refuge area on the floor immediately above 39.0 m and so on after every 15.0 m.
b. The refuge area shall be provided on the periphery of the floor on a cantilever projection and open to air at least on one side protected with suitable railings.
c. Where if it is not possible to cantilever, a refuge area can be provided within the building as per DFS provision and it should be free from FAR.
d. Use of Refuge area :
i. The refuge area shall be earmarked exclusively for the use of occupants as temporary shelter and for the use of Delhi Fire Service or any other agency dealing with fire or other emergencies when occur in the building and also for exercises/ drills if conducted by the Delhi Fire Service.
ii. The refuge areas shall not be allowed to be used for any other purpose and it shall be the responsibility of the owner/ occupier to maintain the same clean and free of encumbrances and encroachments at all times.
iii. Facilities to be provided at refuge area: Adequate emergency lighting facility shall be provided.
Note: Residential flats on multistoried buildings with balcony need not be provided with refuge area. However, flats without balcony or with enclosed balconies shall be provided with refuge area, as given above.
9.3.7 Manner of Providing Refuge Area
a. The refuge area shall be so located that it shall preferably face the access road(s) or otherwise face the wider open space on the side of the building perpendicular to the main access road.
b. The refuge area shall necessarily be of RCC Type.
c. The refuge area up to 54.0 m height shall be provided with railing / parapet of 1.10 m height and 1.50 m above height of 54.0 m.
d. The refuge area shall have access through a two hour rated fire door which shall be painted with a sign in luminous paint mentioning ‘Refuge Area’.
e. The lifts shall only be permitted to open into Fire Tower wherever constructed.
f. Drenchers shall be provided in refuge areas above 70.0 m height.
All refuge areas shall have direct access to the nearest staircase in such a way that occupant can reach the staircase without reentering the building. The refuge area shall be free from F.A.R.
9.3.8 Fire Check Floor/ Fire Cut off Floor
a. A high rise building having height more than 70 m shall be provided with fire check floor (entire floor) above 70m at immediate habitable floor level and so on after every 60 meters.
b. The fire check floor shall not be used for any purpose and it shall be the responsibility of the owner/occupier/ registered society to maintain the same clean and free of encumbrances and encroachments at all times. Drinking water facility and toilet facility shall be provided.
c. Periphery of the Fire Check floor shall not be enclosed.
d. Fire Drenchers shall be provided at the periphery of the each fire check floor externally.
e. Fire Check Floor/ Fire Cut off Floor shall be free of FAR.
9.3.9 Provision of First Aid, Fixed Fire Installation and Fire Fighting Appliances
The firefighting measures shall be provided on all floor including basements, occupied terrace, lift rooms etc. as per the National Building Code of India, Part 4, Fire and Life Safety, (Minimum requirement for firefighting appliances) as applicable with reference to the height and class of occupancy.
9.3.10 Fire Control Room
For all buildings with a height of 15 m and above and Group Housing with a height of 30m and above, there shall be a control room on the entrance floor of the building with communication system (suitable public address system) to all floors and facilities for receiving the message from different floors. Details of all floor plans along with the details of firefighting equipment and installations shall be maintained in the fire control room. The fire control room shall also have facilities to detect the fire on any floor through indicator board connections; fire detection and alarm systems on all floors.
The fire staff in-charge of the fire control room shall be responsible for the maintenance of the various services and firefighting equipment and installations in co-ordination with security, electrical and civil staff of the building.
9.3.11 Fire Notices
Fire notices/orders shall be prepared to fulfill the requirements of the firefighting and evacuation from the building in the event of fire and other incidents. The occupants shall be made thoroughly conversant with their action in the event of the emergency, by displaying fire notices at vantage points. Such notices should be displayed prominently in broad lettering.
9.3.12 Fire Dampers
a. These shall be located in conditioned air ducts and return air ducts/ passages at the following points:
i. At the fire separation wall.
ii. Where ducts/passages enter the central vertical shaft.
iii. Where the ducts pass though floors.
iv. At the inlet of supply air duct and the return air duct of each compartment on every floor.
b. The dampers shall operate automatically and shall simultaneously switch off the air-handling fans. Manual operation facilities shall also be provided. (Note: For blowers, where extraction system and duct accumulators are used, dampers shall be provided).
c. Fire/smoke dampers (for smoke extraction shafts) for buildings more than 24 m in height.
i. For apartment houses in non-ventilated lobbies / corridors operated by fusible link / smoke detectors and with manual control.
ii. For other buildings on operation of smoke detection system and with manual control.
d. Automatic fire dampers shall be so arranged as to close by gravity in the direction of air movement and to remain tightly closed on operation of a fusible link / smoke detector.
Note: The use of type of detectors shall be to the satisfaction of Delhi Fire Service.
9.3.13 Fire Tower
a. Fire towers are escape routes for multistoried buildings and these shall be considered as the safest route for escape. Their number, location and size shall depend on the building concerned, and its associated escape routes. A fire lift, internal hydrant, hose reel etc. shall be providedin the fire tower.
b. In high rise buildings with over 8 stories or 24.0 m in height, at least 50% required means of egress shall preferably be a fire tower(s).
c. The fire towers shall be constructed of walls with a two hour fire resistance rating without openings other than the exit doorways, with platforms, landings and balconies having the same fire-resistance rating.
d. The area of the lobby shall be subject to a minimum of 6.0 sq.m area and such that no side of the lobby is less than 2.0 m.
9.3.14 Provision for Fire Safety officer
Every owner and occupier or an association of such owners and occupiers of the following classes of buildings or premises shall appoint a fire safety officer who shall ensure the compliance of all fire prevention and fire safety measures and effective operation thereof as provided in Delhi Fire Service Act and the rules made there under, namely:-
a. Cinema houses with seating capacity of more than 1000 persons and having commercial complex with built- up area more than 10000 sq. m and building having multiple cinema with seating capacity, taken together, of 1000 persons, or more, whether, having commercial complexes or not;
b. Hotels with 100 rooms and above;
c. Underground shopping complexes, district centres, sub-central business districts, including the basement with build-up area more than 25000 sq.m
d. Multistoried non-residential buildings above 50.0 meters in height;
e. Large oil and natural gas installations such as refineries, LPG bottling plants and similar other facilities;
f. Open stadia with seating capacity more than 50,000 persons and indoor stadia with seating capacity more than 25,000 persons;
g. Hospital and nursing homes with more than 500 beds;
h. Public and semi-public buildings like large surface and sub-surface railway stations, interstate bus terminus, airports, amusements parks and other similar buildings:
Provided that Government may, by notification in the official Gazette, from time to time, include any other premises which, in its opinion, require appointment of fire safety officers.