8.5.1 Staircase and Corridor Lighting
a. The staircase and corridor lighting shall be independently connected, so as it could be operated by one switch installation on the ground floor, easily accessible to firefighting staff at any time irrespective of the position of the individual control of the light points, if any.
b. Staircase and corridor lighting shall also be connected to alternate supply from parallel high-tension supply or to the supply from the stand-by generator.
c. Emergency lights shall be provided in staircase and corridor/ passageway, horizontal exits, refuge area; and all wires and other accessories used for emergency light shall have fire retardant property.
8.5.2 Electrical Services
a. The electric distribution cables/wiring shall be laid in separate duct which shall be sealed at every floor with non- combustible materials having the same fire resistance as that of the duct. Low and medium voltage wiring running in shaft and in false ceiling shall run in separate conduits.
b. Water mains, telephone lines, intercom lines, gas pipes or any other service line shall not be laid in the duct for electric cables. Use of bus ducts/solid rising mains instead of cables is preferred.
c. Separate circuits for water pumps, lifts, staircases and corridor lighting and blowers for pressurizing system shall be provided directly from the main switchgear panel (for detailed specifications refer NBC).
8.5.3 Alternate Source of Electric Supply
A stand-by electric generator shall be installed to supply power to staircase and corridor lighting circuits, fire lifts, the stand-by fire pumps, pressurization fans and blowers, smoke extraction and damper system in case of failure of normal electric supply. The generator shall be capable of taking starting current of all the machines and circuits stated above simultaneously. If the stand-by pump is driven by diesel engine, the generator supply need not be connected to the stand-by pump.
8.5.4 Air-conditioning
Air-conditioning shall conform to the following:
a. Escape routes like staircases, common corridors, lift lobbies, etc. shall not be used as return air passage.
b. The ducting shall be constructed of substantial gauge metal in accordance with good practice.
c. Wherever the ducts pass through fire walls or floors, the opening around the ducts shall be sealed with materials having fire resistance rating of the compartment.
d. Wherever the duct crosses a fire rated compartment, the ducts shall be rated for same fire rating as the compartment. Further depending on services passing around the duct, which may get affected in case of fire temperature rising, the ducts shall be insulated.
e. Metallic ducts shall be used even for the return air instead of space above the false ceiling.
f. Where plenum is used for return air passage, ceiling and its fixtures shall be of non-combustible material.
g. The materials used for insulating the duct system (inside or outside) shall be of non-combustible material; glass wool shall not be wrapped or secured by any material of combustible nature.
h. Air ducts serving main floor areas, corridors, etc. shall not pass through the staircase enclosure.
i. The air-handling units shall be separate for each floor and air ducts for every floor shall be separated and in no way inter-connected with the ducting of any other floor.
j. However, if the air-handling unit serves more than one floor, the recommendations given above shall be compiled with in addition to the conditions given below:
i. Proper arrangements by way of automatic fire dampers working on smoke detector / or fusible link for isolating all ducting at every floor from the main riser shall be made.
When the automatic fire alarm operates, the respective air-handling units of the air-conditioning system shall automatically be switched off.
iii. The vertical shaft for treated fresh air shall be of masonry construction.
iv. The air filters of the air-handling units shall be of non-combustible materials or fire rated (Refer NBC)
v. The air-handling unit room shall not be used for storage of any combustible materials.
vi. Inspection panels shall be provided in the main trunking to facilitate the cleaning of ducts of accumulated dust and to obtain access for maintenance of fire dampers.
vii. No combustible material shall be fixed nearer than 0.15 m to any duct unless such duct is properly enclosed and protected with non-combustible material (glass wool or spyglass with neoprene facing enclosed and wrapped with aluminum sheeting) at least 3.2 mm thick and which would not readily conduct heat.
a. If transformers are housed in the building below the ground level it shall be necessarily in the first basement in separate fire resistance room of four hours rating. Transformer shall be dry type and shall be walls doors cut-out having fire resistance rating of four hour. The room shall necessarily be at the periphery of the basement having separate and direct access from open area at ground floor through a fire escape staircase. The entrance to the room shall be provided with a steel door of two hours fire rating. A curb of a suitable height shall be provided at the entrance in order to prevent the flow of oil from ruptured transformer into other parts of the basement. The switchgears shall be housed in a separate room separated from the transformer bays by a fire-resisting wall with fire resistance not less than four hours.
The transformer shall be protected by an automatic high-pressure water spray or a foam sprinkler system. When housed at ground floor level it/they shall be cut-off from the other portion of premises by Fire Resisting Walls of four hours fire resistance. They shall not be housed on upper floors.
c. A tank of RCC construction of adequate capacity shall be provided at lower basement level, to collect the oil from the catch pit in case of emergency. The pipe connecting the catch-pit to the tank shall be of non-combustible construction and shall be provided with a flame-arrester.
8.5.6 Gas supply
a. Town Gas / L.P.Gas Supply Pipes – Where gas pipes are run in buildings, the same shall be run in separate shafts exclusively for this purpose and these shall be on external walls, away from the staircases. There shall be no interconnection of this shaft with the rest of the floors.
b. LPG distribution pipes shall always be below the false ceiling. The length of these pipes shall be as short as possible. In the case of kitchen cooking range area, apart from providing hood, covering the entire cooking range, the exhaust system should be designed to take care of 30 cu.m per minute per sq.m of hood protected area. It should have grease filters using metallic grill to trap oil vapors escaping into the fume hood.
Note: For detailed information on gas pipe installations, refer NBC..
c. For large/ commercial kitchens, all wiring in fume hoods shall be of fiber glass insulation. Thermal detectors shall be installed into fume hoods of large kitchens for hotels, hospitals, and similar areas located in high rise buildings. Arrangements shall be made for automatic tripping of the exhaust fan in case of fire. If LPG is used, the same shall be shut off. The voltage shall be of 24V or 100V DC operated with the external rectifier. The valve shall be of the hand re-set type and shall be located in an area segregated from cooking ranges. Valves shall be easily accessible. The hood shall have manual facility for steam or carbon dioxide gas injection, depending on duty condition; and Gas meters shall be housed in a suitably constructed metal cupboard located at a well-ventilated space, keeping in view the fact that LPG is heavier than air and town gas is lighter than air.
8.5.7 Boiler Room
Further, the following additional aspects may be taken into account in the location of Boiler/Boiler Room:
a. The boiler shall not be allowed in sub-basement but be allowed only in the first basements away from the escape routes.
b. The boilers shall be installed in a fire resisting room of four hours fire resistance rating, and this room shall be situated on the periphery of the basement. Catch pit shall be provided at the low level. Entry to this room may be provided with a composite door of two hour fire resistance.
c. The boiler room shall be provided with fresh air inlets and smoke exhausts directly to the exterior.
d. Foam inlets shall be provided on the external walls of the building at the ground floor level to enable the fire services to use foam in case of fire.
e. The furnace oil tank for the boiler, if located in the adjoining room shall be separated by fire resisting wall of four hour rating. Entry to this room shall be provided with a composite door of two hour fire resistance. A curb of suitable height shall be provided at the entrance in order to prevent the flow of oil into the boiler room in case of tank rupture.