Annexure VIMaster Plan Delhi- 2021, Development Control (DC)
MPD 2021, provides the guide for the preparation of Layout Plans under the various regulations including norms for facilities and circulation system whereas Service Plans for the provision of physical infrastructure like, Water supply, Sewage, Drainage etc. have to conform to the Municipal Bye Laws as provided in the National Building Code. In case of Integrated Plan the Development Control as applicable to different land uses, are applicable on the total plot and subdivisions are for development purposes. While applying developmental polices and development controls for preparation of integrated schemes, MPD-2021 provisions are to be followed.
Where development control are not given for any use premises, the same can be formulated by the authority.
# These have been reproduced from MPD 2021 and convenience/ reference only. MPD 2021 is amended by issue of Notification from Central Government from time to time. Thus, for the current status for any legal, official purpose the Notification issued by the Central Government to be followed.
Master Plan for Delhi -2021(MPD): –The Development Code applicable for development is given in Master Plan Delhi (MPD)- 2021.The purpose of the code is to promote quality of built environment by organizing the appropriate development of the land in accordance with the development policies and land use proposals contained in the Plan. The layout plans are prepared based on Development Control (DCs)/planning norms given in MPD
Shelter (MPD 2021-Chapter 4)
4.4.3Control for building/buildings within residential premises
Terms and conditions:
i. The additional number of dwelling units would be subject to payment of levy for the augmentation of civic infrastructure.
ii. The total coverage and FAR permissible in any plot in a category, shall not be less than that permissible and available to the largest plot in the next lower category.
iii. Height: the maximum height for building shall be 15m in plots without stilt parking and 17.5m in plots with stilt parking. Such residential building shall not be considered as high rise building. For purpose of fire and life safety requirements, clearance of Fire Department will be obtained by the individual plot owner.
iv. Subdivision of plots is not permitted. However, if there are more than one buildings in one residential plot, the sum of the built up area and ground coverage of all such buildings, shall not exceed the built up area and ground coverage permissible in that plot.
v. The mezzanine floor, and service floor, if constructed, shall be counted in the FAR.
vi. Basement: Basement shall not be counted towards FAR if used for purposes permissible under building bye laws namely household storage and parking. Basement area shall not extend beyond the coverage on the ground floor as per permissible and sanctioned built up area, but may extend to the area below the internal courtyard and shaft. Basement if used in terms of chapter 15.0 Mixed Use Regulations (MPD- 2021) shall count towards FAR and shall be liable to payment of appropriate charges, if it exceeds the permissible FAR.
vii. Stilts: If the building is constructed with stilt area of non-habitable height(less than 2.4 m), used for parking, such stilt area shall not be included in FAR but would be counted towards the height of the building.
viii. Parking: parking space shall be provided for within the residential plot as follows:
a. 2 Equivalent Car Space (ECS) in plots of size 250-300sq.m.
b. 1 ECS for every 100sq.m. built up area, in plots exceeding 300 sq.m, provided that, if the permissible coverage and FAR is not achieved with the above mentioned parking norms in a plot, the parking norms of the preceding category shall be allowed.
ix. Density: for the purpose of density calculations, the dwelling unit shall be considered to accommodate 4.5 persons and the servant quarter to accommodate 2.25 persons.
x. The minimum setbacks shall be as given in the following table:
S.No.
Plot size (in sq.m.)
Minimum Setbacks ( in meter)
Front
Rear
Side(1)
Side(2)
1
Below 100
0
0
0
0
2
Above 100 and up to 250
3
0
0
0
3
Above 250 and up to 500
3
3
3
0
4
Above 500 and up to 2000
6
3
3
3
5
Above 2000 and up to 10000
9
6
6
6
6
Above 10000
15
9
9
9
a. In case the permissible coverage is not achieved with the above mentioned setbacks in a plot, the setbacks of the preceding category may be allowed.
b. In the case construction in the future, a minimum 2mx2m open courtyard shall be provided for in residential plots of area of 50 sq.m to 100 sq.m.
xi. Number of servant quarters shall be provided as per approved layout plan and shall be constructed within the stipulated height. However, if the garage block space is merged with the main building, no separate servant quarter block or servant quarter as part of main building shall be allowed. However, provision for a servant’s room as part of the dwelling unit within the permissible coverage FAR shall be allowed.
xii. Each servant quarter shall comprise of one habitable room of area not less than 11 sq.m. Floor area exclusive of cooking, verandah, bathroom and lavatory. The maximum size of the servant quarter shall be 25 sq.m If larger in size, the servant’s quarter shall be counted in density as a full dwelling unit.
xiii. Plot owners/allottees seeking extra coverage, additional floor or part thereof over above gazette notification dated 23.07.98 as per above mentioned norms shall be charged betterment levy (or additional FAR charges) at the rates notified with the approval of the Government from time to time. This is an addition to the levy payable on the additional FAR allowed vide notification dated 23.07.98 and over the FAR allowed vide notification dated 15.05.95.
xiv. Plot owners/allottees seeking regularization of construction in terms of the additional coverage allowed under this
notification shall have to pay a penalty and compounding charges notified with the approval of the Government, over and above the betterment levy referred in Para xiii above.
xv. Plot owners/allottees seeking regularization of additional height in this notification, will have to pay penalty and special compounding charges notified with the approval of the Government, in addition to betterment levy referred to in Para (xiv). – UBBL no 2.15
xvi. The amount so collected be deposited in an escrow account by the local body concerned for incurring expenditure for developing parking sites, augmentation of amenities/infrastructure and environmental improvement programmers’ and a quarterly statement of the income and expenditure of the account shall be rendered by the local bodies to the Government.
xvii. Encroachment on public land shall not be regularized and shall be removed before the local body grants sanction for regularization of additional construction or height except following:
a. Projections/chajjas/covered chajjas built up portion which existed before 7.2.2007 up to 1 m above 3 m height from the ground level shall be regularized for plot size up to 175 sq. m on roads below 24 m. ROW on pre 1962 colonies (except for A and B category) already notified by MCD, in unplanned areas (including special areas, village abadi and unauthorized regularized colonies) and resettlement colonies. The owner/occupier shall have to obtain structural safety certificate and fire clearance within a reasonable period of time notified by Government. Such projections/built-up portion thereon shall be counted in FAR and in case of excess FAR over and above permissible FAR, such FAR in excess shall be regularized subject to payment of appropriate charges as approved by the Government.
b. The Local body concerned shall carry out survey within a period of two months from the date of notification of all such projections eligible to be regularized and put such a list in public domain for objections from the occupiers/owners and any person of the public against inclusion /exclusion of such projection in the list and the list thereafter will be finalized within a period of one month after considering such objections received in writing.
xviii. Every applicant seeking sanction or regularization of additional FAR and /or height shall submit a certificate of structural safety obtained from a structural engineer. Where such certificate is not submitted or the Building is otherwise found to be structurally unsafe, formal notice shall be given to the owner by the local body concerned, to rectify the structural weakness with a reasonable stipulated period, falling which the building shall be declared unsafe by the local body concerned and shall be demolished by owner or the local body.
xix. Standard Plan: - There are number of standard building plan design and approved by the authority/ Concerned Local Bodies, such plans would be given relaxation wherever applicable. However, these may be modified as per the applicable Development Control Regulations.
xx. Amalgamation of the two plots up to 64 sq.m maximum will be permitted with following conditions:
Local Body will simultaneously modify the Layout Plan.
The maximum Ground Coverage, setbacks, parking, Dwelling Units etc. shall be for the amalgamated plot size.
The maximum FAR permissible shall not be less than the permissible is case of two individual plots.
A. Residential plot- plotted housing
Maximum ground coverage, FAR, number of dwelling units for different size of residential plots shall be as per the following table:
Sl. No.
Area of the Plot (sq. m.)
Maximum Ground Coverage%
FAR
Number of DUs
1.
Below 32
90*
350
3
2.
Above 32 to 50
90*
350
3
3.
Above 50 to 100
90*
350
4
4.
Above 100 to 250
75**
300**
4
5.
Above 250 to 750
75
225
6
6.
Above 750 to 1000
50
200
9
7.
Above 1000 to 1500
50
200
9
8.
Above 1500 to 2250
50
200
12
9.
Above 2250 to 3000
50
200
15
10.
Above 3000 to 3750
50
200
18
11.
Above 3750
50
200
21
The Local Body concerned shall be competent to disregard variation up to 2% in plot size, arising from conversion of area from sq. yard to sq.m. and to grant the norms applicable to the lower category of plot size in accordance to Para (ii) below
*100% ground coverage shall be eligible for regularization of construction, already existing as on 22.09.06 on payment of charges as notified.
Minimum size of the residential plot shall be 32 sq.m. However, in case of Government sponsored economically weaker section schemes, size could be reduced further.
**100% ground coverage and 350 FAR shall be eligible for regularization of construction already existing as on 22.09.06 on payment of charges as per the notification, in respect plot size between 100 to 175 sq.m.
Permissible FAR and dwelling units shall not be less than MPD – 2001 norms.