a. Interior stairs shall be constructed of non-combustible material throughout.
b. Interior stairs shall be constructed as a self-contained unit and shall be mechanically ventilated if completely enclosed in low rise residential buildings.
c. A staircase shall not be arranged round a lift shaft.
d. Hollow combustible construction shall not be permitted.
e. The minimum width of internal staircase shall be as given in bye-law No. 7.11.2.
f. The minimum width of treads without nosing shall be 25 cm for an internal staircase for low rise residential buildings. In the case of other buildings including high rise residential, the minimum tread shall be 30 cm. The treads shall be constructed and maintained in a manner to prevent slipping. Winders shall be allowed in low rise residential buildings provided they are not at the head of a downward flight.
g. The maximum height of riser shall be 150mm in the case of low rise residential buildings, other buildings including high rise residential building and maximum number of risers per flight shall be limited to 12 per flight.
h. For Handrails and Grab Bars refer 11.5.3. The balusters/ railing shall not reduce the width of staircase i.e. clear width should be 1.5 m.
i. The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
j. For building 15m in height or more, access to main staircase shall be through a fire check door having minimum two hours fire resistance rating, which may be reduced to one hour for residential buildings (except hotel/ starred hotels).
k. No living space, store or other fire risk shall open directly into the common staircase or staircases, in case of group housing.
l. External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a draught lobby.
m. The main staircase and fire escape staircase shall be continuous from ground floor to the terrace level.
n. No electrical shafts/ AC ducts or gas pipe etc. shall pass through the staircase. However, ducting in staircase may be permitted if it is of 1 hour fire resistance rating.
o. Lift shall not open in staircase landing. Adequate Lift Lobby shall be provided. (Refer Clause 8.4.4 and Annexure VIII). (except for low rise residential plotted development upto 500 sqm.)
p. No combustible material shall be used for decoration/wall panelling in the staircase.
q. Beams/columns and other building features shall not reduce the head room/width of the staircase.
r. The exit sign with arrow indicating the way to the escape route shall be provided at a suitable height from the floor level on the wall and shall be illuminated by electric light or glow sign or florescent, connected to corridor circuits. All exit way marking sign should be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipment’s. Further all landings of floor shall have floor-indicating boards indicating the number of floor as per these bye-laws. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5 m x 0.5 m.
s. Individual floors shall be prominently indicated on the wall facing the staircase.
t. In case of single staircase, it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. However, the second staircase may lead to basement levels provided the same is separated at ground level either by ventilated lobby with discharge points at two different ends through enclosures.
u. For details of FAR and Ground Coverage refer 7.17.2.n.
v. Spiral Stairs (fire escape) –
i. The use of spiral staircase shall be limited to low occupant load and to a building of height 9 m.
ii. A spiral fire escape shall be not less than 1.5 m in diameter and shall be designed to give adequate head room.
7.11.1 Minimum Width Provisions for Stairways
The following minimum width provisions shall be made for each stairway:
a. Other residential building e.g. flats, hostels, group housing, guest houses etc. minimum 1.5 m. For details refer chapter 11.
b. Assembly buildings and Institutional building -2.0 m.
c. All other buildings including hotels and Educational building 1.5 m.
d. For high rise buildings refer table no. 8.1
7.11.2 Minimum Width Provisions for Passageway/Corridors (clear width excluding handrail and balustrade)
The width of corridor/passageway/foyer as the case may be, shall be determined such that it shall accommodate the entire population of the floor subject to minimum width depending upon the class of occupancy as under:-
a. Residential buildings (low rise), dwelling unit type 1 m for single loaded and 1.5 m for double loaded.
b. Residential buildings, e.g., hostels, group housing etc. 1.5m for single loaded and 1.8m for double loaded.
c. Assembly buildings like auditorium theatres and cinemas 2.0 m.
d. All other buildings like commercial, institutional and hotels 1.5 m for single loaded and 1.8m for double loaded.
e. Hospital, Nursing Homes, etc. 2.4 m for both single and double loaded.
f. Ramps- for applicability in all other building types refer Chapter 8 (Clause 8.4.7)
g. Where staircase discharges through corridors and passageways, the height of corridors and passageways shall be not less than 2.4 m.
h. All means of exit including staircases lifts lobbies and corridors shall be naturally/mechanically ventilated.
i. The area of passageway/corridor including the additional area constructed over and above the prescribed/ permissible limit, should not be counted towards FAR but shall be counted in Ground Coverage (See 7.17.2.t.). The width of the additional area shall not be more than the double of the prescribed /permissible limit.