Number and Type of Lifts Required for Different Occupancies and Space for Electrical Installations (Please refer clause 9.4.2 of this document)
- The number and type of lifts required depending on the capacity of lift, desired speed nature of operation are as given in table below.
Table: Number and types of lifts for non-residential Multistoried Building
| S. No | No. of floors | Capacity of lifts in person | No. of persons that can be carried by a lift | No. of persons that can be carried by a lift | No. of persons that can be carried by a lift | No. of persons that can be carried by a lift | No. of persons that can be carried by a lift | No. of persons that can be carried by a lift | No. of persons that can be carried by a lift | No. of persons that can be carried by a lift | |
| S. No | No. of floors | Capacity of lifts in person | Speedm/s | In 6 min | In 6 min | In 30 mins | In 30 mins | In 50 mins | In 50 mins | In 60 mins | In 60 mins |
| S. No | No. of floors | Capacity of lifts in person | Speedm/s | Manually operated | Auto matic | Manually operated | Auto matic | Manually operated | Automatic | Manually operated | Automatic |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
| 1 | 7 | 6 | 0.6-0.75 | 17 | - | 102 | - | 170 | - | 204 | - |
| 2 | 7 | 8 | 0.6-0.75 | 22 | - | 132 | - | 220 | - | - | - |
| 3 | 7 | 10 | 0.6-0.75 | 26 | - | 156 | - | 260 | - | 312 | - |
| 4 | 7 | 10 | 1.0 | 30 | - | 180 | - | 300 | - | 360 | - |
| 5 | 7 | 13 | 1.0 | 37 | - | 122 | - | 370 | - | 444 | - |
| 6 | 11 | 6 | 0.6-0.75 | 11 | - | 70 | - | 115 | - | 140 | - |
| 7 | 11 | 8 | 0.6-0.75 | 15 | - | 90 | - | 150 | - | 180 | - |
| 8 | 11 | 10 | 0.6-0.75 | 18 | - | 108 | - | 180 | - | 216 | - |
| 9 | 11 | 13 | 0.6-0.75 | 22 | - | 132 | - | 220 | - | 264 | - |
| 10 | 11 | 10 | 1.0 | 21 | - | 126 | - | 210 | - | 252 | - |
| 11 | 11 | 10 | 1.5 | 24 | - | 144 | - | 240 | - | 288 | - |
| 12 | 11 | 13 | 1.5 | 28 | - | 156 | - | 260 | - | 312 | - |
| 13 | 11 | 13 | 1.5 | 32 | - | 180 | - | 300 | - | - | - |
| 14 | 16 | 10 | 1.0 | 17 | - | 100 | 126 | 170 | 210 | - | 252 |
| 15 | 16 | 13 | 1.5 | 20 | 24 | 120 | 145 | 200 | 240 | 248 | 290 |
| 16 | 16 | 13 | 1.5 | 23 | 30 | 138 | 180 | 230 | 300 | - | 360 |
| 17 | 16 | 16 | 1.5 | 25 | 33 | 150 | 198 | 250 | 330 | 300 | 356 |
| 18 | 21 | 10 | 1.5 | 18 | 32 | 108 | 132 | 180 | 220 | 214 | 264 |
| 19 | 21 | 13 | 1.5 | 21 | 26 | 126 | 156 | 210 | 250 | 250 | 312 |
| 20 | 21 | 14 | 1.5 | 23 | 28 | 138 | 168 | 230 | 280 | - | - |
Note-1:
a) For all non-residential buildings, the traffic cleared in 50 minutes is considered adequate and is approved by Authority/ concerned local body. As such for calculation the number of lifts required, the rate of the clearance of traffic in column 9 and 10 and the population shallbe taken into consideration.
b) In addition to total number of lifts required as above, provision of one lift of the same capacity shallbe considered to serve as stand-by.
Note-2: The population shall be worked out on the basis of useful carpet area which the person occupies (excluding area of Verandah, Lobbies, Halls, Passages, Lavatory blocks, etc.)
Note-3: The population on ground and first floor may not be taken into consideration since these floors are not generally served by lifts.
Note-4:
0.75 meter per sec. Equivalent to 150 ft. per Min.
1.00 meter per sec. Equivalent to 200 ft. per Min.
1.5 meter per sec. Equivalent to 300 ft. per Min.
Note-5: The height of buildings for lift installation i.e. the travel on the lift presumed in the above statements is as below:
7 floors- 21.0 m
11 floors- 33.0 m
16 floors- 48.0 m
21 floors- 64.0 m
Table: Number and types of lifts for Residential Building
| S.no | No. of floors | No | Passenger unit capacity Persons | Speed in m/s | Landing Gate Type | Central System | Service Lift No. | Capacity Persons | Type of Gate | Central System |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 5 to 8 | 2 | 6 | 0.0 to 0.5 | - | Automatic push button operation both from car and landing | - | - | - | - |
| 2 | 9 to 11 | 2 | 8 | 1.6 to 1 | - | -do- | 1 | 8 | - | Push button car handle switch control |
| 3 | 11 to 13 | 21 | 86 | 1.6 to0.74 | -Power operated doors | do- and without collection system -do- | 1 | 8 | - | -do- |
| 4 | 13 to 19 | 22 | 88 | 11 | -Power operated doors | -do- | 1 | 8 | - | -do- |
* For buildings more than 15 m in height collapsible gates shall not be permitted.
The dimensions and relevant information for lift installations like lift well, pit depth, machine room, clearance from top floor landing to machine room flooring is given in table below:
Dimensions and required information for Lift Installation in Building.
| Carrying capacity of lift (person) number | Load(kg) | Lift speed | Dimension of lift well front depth(in cm.) | (Cm) | Leading pit entrance (cm) | Dimension of machine room | Clearance from top floor landing to machine room flooring cm | Imposed load in tones on top of lift well due to installation. it may be noted that figures do not include weight of the machine from floor and well etc. |
|---|