The specified facilities for the buildings for persons with disabilitiesshall be as follows:
11.5.1 Approach to Plinth Level
Every building should have at least one entrance accessible to the persons with disabilitiesand shall be indicated by proper signage. This entrance shall be approached through a ramp together with the stepped entry.
a. Ramped approach:Ramp shall be finished with non-slip material to enter the building. Minimum width of ramp shall be 1.8 m. The landing shall have a level platform of not less than 1.5m. For minimum specification for Ramps see Table 11.1.
| Level difference | Minimum gradient of Ramp | Ramp Width | Handrail on both sides | Comments |
|---|---|---|---|---|
| ≥ 150 mm ≤ 300 mm | 1:12 | 1200 mm | √ | |
| ≥ 300 mm ≤ 750 mm | 1:12 | 1500 mm | √ | Landings every 5 meters of ramp run. |
| ≥ 750 mm ≤ 3000mm | 1:15 | 1800 mm | √ | Landings every 9 meters of ramp run. |
| ≥ 3000 mm | 1:20 | 1800 mm | √ | Landings every 9 meters of ramp run. |
Note : A ramp run with a vertical rise greater than 150 mm should have handrails that
• are on both sides
• are placed at a height as per 11.5.3.
• handrails must be continuous on both sides & even at landings and end of handrails to be rounded off or grounded in the ground.
b. Stepped Approach: For stepped approach size of tread shall not be less than 300mm and maximum riser shall be 150mm. Provision of hand rail on both sides of the stepped approach similar to the ramped approach.
c. Accessible Exit/Entrance Door: Minimum& clear opening of the accessible entrance door shall be 900mm and it shall not be provided with a step that obstructs the passage of a wheel chair user. Threshold shall not be raised more than 10 mm. The width of the corridors or passageways leading to and from such access door shall not be less than 1500 mm. In multi-storey buildings, the accessible entrance shall have an accessible route leading to the lifts {See 11.4.2 (e)}. All external doors shall have warning blocks installed 300 mm before the entrances for aid of visually impaired users.
Note: For Details of Doors, Windows, Operational Control and devices and other building requirements, Signages, Escalators etc. the standards specified in NBC Chapter 3 - Clause 13 Requirements for accessibility inBuilt environment for elders and persons with disabilities andAnnex B: Anthropometrics and Requirements for Accessibility in Built-Environment for Elders and Persons with Disabilities shall have to be followed as amended from time to time.
d. Entrance Landing: Entrance landing shall be provided adjacent to ramp with the minimum dimension 1.8 m x2.0 m. The entrance landing that adjoins the top end of a slope shall be provided with floor materials to attract the attention of visually impaired person’s (limited to coloured floor material whose colour and brightness is conspicuously different from that of the surrounding floor material or the material that emits different sound to guide visually impaired persons. Finishes shall have a non-slip surface with a texture traversable by a wheel chair. Curbs wherever provided should blend to a common level.
11.5.2 Corridor Connecting the Entrance/Exit for persons with disabilities.
The corridor connecting the entrance / exit for persons with disabilitiesleading directly outdoors to a place where information concerning the overall use of the specified building can be provided to visually impaired persons either by a person or by signs, shall be provided as follows:
a. Guiding floor materials’ shall be provided or device that emits sound to guide visually impaired persons.
b. The minimum width shall be 1.5 m.
c. In case there is a difference of level, slope ways shall be provided as specified in Table 11.1.
d. Handrails shall be provided for ramps/slope ways as per Handrails and Grab Bars (refer 11.5.3). The balusters/ railing shall not reduce the width of corridor.
11.5.3 Handrails and Grab Bars
For stepped path, stairs and ramps, handrails shall meet the following requirements:
a) They shall be provided on both the sides;
b) They shall be continuous, even at the landings;
c) They shall extend at least 300 mm beyond the first and last nosing. A handrail shall not project into a transverse circulation path unless it is continuous and intended to formpart of the guidance along that path. The endof the horizontal extension should be turnedtowards the wall on the closed side of the ramp or stairs, or be turned down and terminate at the floor or ground level.
d) They shall have aminimum clear spaceof 50 mm from the walls;
e) The height to the top of a handrail shall be 900 mm above the surface of a ramp, the pitch line of a stair, and the surface of a landing. A second handrail, with a lower profile than the first one, shall be provided. The height to the top of the second handrail shall be 760 mm above the surface of a ramp, the pitch line of a stair, and the surface of a landing. There shall be sufficient distance between the two handrails (say, 100 mm).
f) In case the handrail is enclosed in a recess, the recess shall be 50mm deep.
11.5.3.1 Handrails shall
a) be securely fixed and rigid; the fastenings and the materials shall be able to withstand a minimum point load, both vertical and horizontal of 1.7 KN;
b) be slip-resistant with round ends;
c) have a circular section of 38mm in diameter;
d) be free of any sharp or abrasive elements;
e) have continuous gripping surfaces, without interruptions or obstructions that may break a hand hold; f) contrast with the wall behind;
g) shall be provided with Braille/tactile markings at the beginning and at the end to give information to people with visual impairment.
11.5.3.2 Grab Bars shall,
a) be securely fixed and rigid;
b) be slip-resistant with round ends;
c) Preferably have knurled surfaces;
d) have a circular section of 38mm in diameter;
e) be free of any sharp or abrasive elements;
f) have a minimum clear space of 50 mm to 65 mm from the wall;
g) be installed at a height of 760 mm to 900 mm;
h) be able to bear a weight of 1.7 kN;
i) contrast with the wall/surface behind.