Any buildings of 15m and above height shall be considered as high rise building. For the buildings categorized as High Rise, clearance from Delhi Fire Service shall be mandatory. These provisions shall be in addition to the general building requirements (low/ high) given in Chapter 7 of this document and structural safety given in Chapter 9.
8.1 Plot Area
Plots to be used for high rise development should be located in a Layout plan, Comprehensive plans or sub division plans as prepared and approved by competent authorities/ as per policy of Government of INDIA or Government of NCT Delhi.
8.2Means of Access
To be read along with ‘Means of Access, clause 2.0.4.j.(iv)’of these building bye laws.
a. A building shall abut on a street or upon spaces directly connected from the street by a hard surface approach road; width of the approach road is 18.0 m ROW (7.5 m ROW for the Redevelopment Areas/ Rehabilitation Colonies/ Special Area/ Village [Lal Dora/ Firni]/ Extended Lal Dora).
b. The hard surface approach road to the building all around shall be capable of taking the weight of fire engine, weighing upto 45 ton having 6.0 m width (with 9.0 m turning circle at the corners) for building upto 40.0 m in height and 9.0 m width (with 12.0 m turning circle at the corners) in case of buildings more than 40.0 m in height shall be provided and the layout for the same shall be done in consultation with Delhi Fire Service. The said open space shall be kept free of obstructions and shall be motorable.
Main entrance to the premise shall be of adequate width to allow easy access to the fire tender and in no case it shall measure less than 6.0 m. The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior access way within the plot free for the movement of the fire service vehicle. If archway is provided over the main entrance the height of the archway shall not be of less than 5.0 m in height.
8.3 Parking Spaces
a. The parking spaces shall be provided as per the provisions of MPD or Zonal Plan as prevalent. The location of parking spaces shall be well ventilated.
b. In case of high-rise buildings parking would be permitted at any or all of the following:
i. Open Area : 23 sq.m per E.C.S
ii. Basements : 32 sq.m per E.C.S
iii. Stilts: 28 sq.m per E.C.S
iv. Podium: 28 sq.m per E.C.S
v. Roof top:28 sq.m per E.C.S
c. Stacked Parking: 16 sq.m / Multi-level (with ramp): 30 sq.m/ Multi level- Automated parking: 16 sq.m per E.C.S is also permitted.
8.4Building Components
8.4.1 Doorways
a. Every doorway shall open into an enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress.
b. No exit doorway shall be less than as required under clause 7.12.2.
c. Exit doorways shall open outwards, that is, away from the room but shall not obstruct the travel along any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 0.9 m, overhead or sliding doors shall not be installed.
d. Exit door shall not open immediately upon a flight or stairs. A landing equal to at least the width of the door shall be provided in the stairway at each doorway. Level of landing shall be the same as that of the floor which it serves.
e. Exit doorways shall be openable from the side which they serve without the use of a key.
f. Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.
8.4.2 Revolving Doors
Revolving door shall not be provided as exit doors for required exits.
8.4.4Lifts
General requirements of lifts shall be as follows:
a. All the floors shall be accessible for 24 hours by the lifts. The lifts provided in the buildings shall not be considered as a means of escape in case of emergency. In a dual line arrangement (lifts opposite to each other) the lobby shallbe between 1.5 times to 2.5 times the depth of one car. For in-line (single line) arrangements the lobby shall be typically half of the above recommendations.
b. Grounding switch shall be provided at ground floor level; to enable the fire service to ground the lift shall also be provided.
c. The lift machine room shall be separate and no other machinery shall be installed therein.
d. Walls of lift enclosures and lift lobby shall have fire rating of two hour; (Refer NBC Part 4, Fire and Life safety). Lifts shall have a vent at the top of area not less than 0.2 sq.m
e. Lift car door shall have a fire resistance rating of half an hour.
f. Lift lobby doors in lift enclosures shall have fire resistance (Refer NBC Part 4, Fire and Life safety).
g. Collapsible gates shall not be permitted for lifts and shall have solid doors with fire resistance of at least one hour.
h. If the lift shaft and lobby is in the core of the building, a positive pressure between 25 and 30 Pa shall be maintained in the lobby and a positive pressure of 50 Pa shall be maintained in the lift shaft. The mechanism for pressurization shall act automatically with the fire alarm. It shall be possible to operate this mechanically also.
i. Lifts if communicating with the basement, the lift lobby of the basements shall be pressurized as suggested in clause 8.5.4(f) and 8.5.4(h) with self-closing door with fire resistance rating (Refer NBC Part 4, Fire and Life safety). Telephone or other communication facilities shall be provided in lift cars and to be connected to fire control room for the building.
j. Exit from the lift lobby, if located in the core of the building, shall be through a self-closing fire door of half an hour fire resistance.
k. Slope shall be provided on the floor of lift lobby, to prevent water used during firefighting, etc., at any landing from entering the lift shafts.
l. A sign shall be posted and maintained on every floor at or near the lift indicating that in case of fire, occupants shall use the stairs unless instructed otherwise. The sign shall also contain a plan for each floor showing the locations of the stairways. Alternate source of power supply shall be provided for all the lifts through a manually operated changeover switch.
m. For Pressurization Specifications of various building components refer NBC Chapter 4 Fire and Life Safety Clause 4.10 (Pressurization of Staircases- Protected Escape Routes).
8.4.5Basements
a. Basement will be permitted within the setback lines subject to clearance from Authority/ concerned local body/ any other departments concerned, and Delhi Fire Service. Where there are no setbacks, basement should be permitted after leaving 2.0 m and where there is setback of 6m and above, it should be after leaving required 6.0 m from plot boundary ( as per provisions of development control norms of MPD).
b. Each basement shall be separately ventilated. Vents with cross-sectional area (aggregate) not less than 2.5 percent of the floor area spread evenly round the perimeter of the basement shall be provided in the form of grills or breakable stall board lights or pavement lights or by way of shafts. Alternatively, a system of air inlets shall be provided at basement floor level and smoke outlets at basement ceiling level. Inlets and extracts shall be terminated at ground level with stall board or pavement lights as before, but ducts to convey fresh air to the basement floor level have to be laid. Stall board and pavement lights should be in positions easily accessible to the fire brigade and clearly marked ‘SMOKE OUTLET’ or ‘AIR INLET’ with an indication of area served at or near the opening.
c. The staircase of basements shall be of enclosed type having fire resistance rating (Refer NBC Part 4, Fire and Life safety). The staircase shall be situated at the periphery of the basement to be entered at ground level only, from outside open air. The staircase shall communicate with basement through a lobby with self-closing doors with fire resistance rating as per relevant NBC code mentioned above.
d. For travel distance table 8.2 given below should be followed. If travel distance exceeds that given in the table below, additional staircases shall be provided.
Table 8.2-Travel Distance for Occupancy and Type of Construction
S No
Group of Occupancy
Maximum Travel Distance Construction (m) See NBC.
Type 1 & 2
Type 3 & 4
i.
Residential (A)
30.0
22.5
ii.
Educational (B)
30.0
22.5
iii.
Institutional (C)
30.0
22.5
iv.
Assembly (D)
30.0
30.0
v.
Business (E)
30.0
30.0
vi.
Mercantile (F)
30.0
30.0
vii.
Industrial (G)
45.0
Construction type 3 and 4 not permitted.
viii.
Storage (H)
30.0
Construction type 3 and 4 not permitted.
ix.
Hazardous (J)
22.5
Construction type 3 and 4 not permitted.
For fully sprinkled building, the travel distance may be increased by 50% of the values specified in above table
Ramps shall be counted as one of the means of escape wherever permitted in National Building Code.
e. In multi-story basements, intake ducts may serve all basement levels, but each basement level and basement compartment shall have separate smoke outlet duct or ducts. Ducts so provided shall have the same fire resistance rating as the compartment itself. Fire rating may be taken as the required smoke extraction time for smoke extraction ducts.
f. Mechanical extractors for smoke venting system from lower basement levels shall also be provided. The system shall be of such design as to operate on actuation of heat / smoke sensitive detectors or sprinklers, if installed, and shall have a considerably superior performance compared to the standard units. It shall also have an arrangement to start it manually.
g. Mechanical extractors shall have an internal locking arrangement, so that extractors shall continue to operate. Supply fans for HVAC shall stop automatically with the actuation of fire detectors.
h. Mechanical extractors shall be designated to permit air changes per hour as required by NBC Part 4, Fire and Life Safety in case of fire or distress call. However, for normal operation, air changes schedule shall be as given in Part 8, Building Services, Section 3, Air-conditioning, Heating and Mechanical Ventilation of National Building Code.
i. Mechanical extractors shall have an alternative source of supply.
j. Ventilating ducts shall be integrated with the structure and made out of brick masonry or reinforced cement concrete and in case, duct crosses the transformer area or electrical switchboard, fire dampers shall be provided.
k. Use of basements for kitchens working on gas fuel shall not be permitted, unless air conditioned. The basement shall not be permitted below the ward block of a hospital/nursing home unless it is fully sprinkled. Building services such as electrical sub-stations, boiler rooms in basements shall comply with the provisions of the Indian Electricity Rules 1956. Boiler room shall be provided at the first basement along the periphery wall with fire resistance rating (Refer NBC Part 4, Fire and Life safety) or shall be separated with the blast wall.
l. If cutouts are provided from basements to the upper floors or to the atmospheres, all side cutout openings in the basements shall be protected by sprinkler head at close spacing so as to form a water curtain in the event of a fire.
m. It is essential to make provisions for drainage of any such water on all floors to prevent or minimize water damage of the contents. The drain pipes should be provided on the external wall for drainage of water from all floors. On large area floors, several such pipes may be necessary which should be spaced 30 m apart. Care shall be taken to ensure that the construction of the drain pipe does not allow spread fire / smoke from floor to floor.
8.4.6 Compartmentation
The building shall be suitably compartmentalized so that fire/smoke remains confined to the area where fire incident has occurred and does not spread to the remaining part of the building. All floors shall be compartmented as per NBC (Part 4, Fire and Life safety) as amended from time to time.
8.4.3Stairways
a. A staircase shall not be arranged around a lift shaft.
b. The staircase shall be ventilated to the atmosphere at each landing and a vent at the top; the vent openings shall be of0.5 sq.m in the external wall and the top. If the staircase cannot be ventilated, because of location or other reasons, a positive pressure 50 Pa shall be maintained inside. The mechanism for pressurizing the staircase shall operate automatically with the fire alarm. The roof of the shaft shall be 1 m above the surrounding roof. Glazing or glass bricks if used in staircase, shall have fire resistance rating of minimum two hour.
c. The minimum width of staircase shall be as table given below:
Table 8.1Minimum width of staircase for different types of buildings (clear width excluding handrail and balustrade)
Type of Building
Minimum Width
Residential buildings (Group Housing)
1.5m
Hotel buildings
1.5m
Assembly buildings like auditorium, theatres, cinemas etc.
2.0m
Educational buildings up to 30 m in height
1.5m
Above 30 m
2.0 m
Institutional buildings like hospitals etc.
2.0m
All other buildings including commercial
1.5m
Industrial building
1.5m
d. The minimum width of treads without nosing shall be 0.3m. The treads shall be constructed and maintained in a manner to prevent slipping. The maximum height of riser shall be 0.15 m in the case of other buildings and shall be limited to 15 risers per flight.
e. For Handrails and Grab Bars refer 11.5.3. The balusters/ railing shall not reduce the width of staircase.
f. The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
g. Access to main staircase shall be gained through adequate fire resistance rating (Refer NBC Part 4, Fire and Life safety Table no1 to 18) Automatic closing doors placed in the enclosing walls of the staircases. It shall be a swing type door opening in the direction of the escape.
h. No living space, store or other fire risk, shall open directly into the staircase or staircases.
i. External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a draught lobby.
j. The exit sign with arrow indicating the way to the escape route shall be provided at a suitable height from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be flushed with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipment’s. Further all landings of floor shall have floor indication boards indicating the number of floor. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5x0.5m and it shall be prominently placed on the wall facing the staircase.30
k. In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. However, the second staircase shall lead to basement levels provided the same is separated at ground level by either a ventilated lobby with discharge points at two different ends or through enclosures with fire resistance rating door (Refer NBC Part 4, Fire and Life safety) or through a fire protected corridor.
8.4.7Ramps
a. The ramp to basement and parking floors shall not be less than 7.2 m wide for two way traffic and 4.0 m wide for one way traffic, provided with gradient of 1:10 for cars and 1:15 for heavy vehicles. At curved portions of the ramp or for circular ramps the slope should not be more than 1:12.
b. Ramp may also be provided in setback area which can be sloped considering unhindered movement of fire Engine and in no case the gradient shall be less than 1: 10.
c. All structural design/safety aspects as per latest BIS Codes & NBC, shall be complied along with consideration of weight of Fire Engine & its maneuverings.
d. The minimum width of the ramps in hospitals shall be 2.4 m for stretcher and not for vehicular movement In this case, handrails shall be provided on both sides of the ramp.
e. Ramps shall lead directly to outside open space at ground level or courtyards or safe place.
f. In basement one entry and exit shall be provided for the floor area of 10,000sqm for each basement and if the basement area is more than 10,000sqm. in each basement, one more entry & exit ramp should be provided.
g. For plots less than 3000sqm. car lift/s can be provided in place of ramp/s subject to the approval of the Fire Department. For plot/s above 3000sqm. Ramp/s are mandatory, if used for parking.
Minimum size of the car lift shall be as per NBC norms. The lift car width should be selected such that in case of emergency, while the automobile is in the car-lift, the driver should be able to open the automobile door and come out of the automobile.
8.4.8 Corridors
a. Exit corridors and passageways shall be of width not less than the aggregate required width of exit doorways leading from them in the direction of travel to the exterior.
b. For the minimum width of a corridor, See7.11.2.
8.4.9Glass Façade/ Service Ducts/Shafts/ Refuge Area/ Vents
a. An opening to the glass façade of minimum width 1.5 m and height 1.5 m shall be provided at every floor at a level of
1.2 m from the flooring facing compulsory open space as well as on road side. Construction that complies with the fire rating of the horizontal segregation and has any gap packed with a non-combustible material that will withstand thermal expansion and structural movement of the walling without the loss of seal against fire and smoke.
b. Mechanism of Opening: The openable glass panel shall be either left or right shall have manual opening mechanism from inside as well as outside. Such openable panels shall be marked conspicuously so as to easily identify the openable panel from outside.
c. Fire seal to be provided at every floor level between the external glazing and building structure.
d. The glazing used for the façade shall be of toughened (tempered) safety glass as per I.S.2553.
e. To avoid fire propagation vertically from lower floor to upper floor, a continuous glass facade must be separated internally by a spandrel which:
i. is not less than 0.9 m in height; and
ii. Extends to not less than 0.6 m above the upper surface of the intervening floor; and
f. Distance between the external wall (glass/brick) and glass façade shall not be more than 0.3 m., which will be within the Building Line.
g. To avoid fire propagation vertically from one floor to another floor, a continuous glass facade must be separated internally by a smoke/ fire seal which is of non-combustible material having a fire resistance rating of not less than two hours.
h. Service ducts and shafts shall be enclosed by walls and doors with fire resistance rating (Refer NBC). All such ducts/ shafts shall be properly sealed and stopped fire ingress at all floor levels.
i. A vent opening at the top of the service shaft shall be provided having an area between one- fourth and one-half of the area of the shaft.
j. The openable vent of minimum 2.5% of the floor area shall be provided. The openable vent can be pop out type or bottom hinged provided with fusible link opening mechanism and shall also be integrated with automatic Smoke Detection System.
OR
• Alternate vertical glass panels of the façade shall be openable type with the mechanism mentioned above in order to ventilate the smoke.
Refuge areas covered with the glass façade shall have all the panels fully openable (either left or right hinged) both from inside as well as outside.
k. Glass quality shall be as per IS Codes given below in Table 8.3:
Table 8.3
2553 (Part 1):1990
Specification for safety glass: Part 1 General purpose (third revision)
2835:1987
Specification for flat transparent sheet glass (third revision)
438:1994
Specification for silvered glass mirrors for general purposes (second revision)
5437:1994
Specification for figured rolled and wired glass (first revision).
14900:2000
Specification for transparent float glass.
16231:2014(Part 4)
Code of Practice on use of Glass in Buildings - Safety Related to Human Impact.
Note: BIS Codes &National Building Code of India concerning standards, as amended from time to time; unless otherwise specified in these bye –laws shall be followed.