(1) Rule 27: Classes of occupancies likely to cause a risk of fire (Please refer clause 9.3 of this document)
The following classes of occupancies for the purposes of sub-section (1) of section 25 of the Act shall be construed to likely cause a risk of fire, namely:-
a) Pandal having seating capacity more than 50 persons or covered area more than 50 sq.m
b) Residential buildings (other than hotels and guest houses) having height more than 15 meters or having ground plus four upper stories including mezzanine floor.
c) Hotels and guest houses having height more than 12 meters having ground plus three upper stories including
mezzanine floor.
d) Educational buildings having height more than 9 meters or having ground plus two upper stories including mezzanine floor.
e) Institutional buildings having height more than 9 meters or having ground plus two upper stories including mezzanine floor.
f) All Assembly buildings.
g) Business buildings having height more than 15 meters or having ground plus four upper stories including mezzanine floor.
h) Mercantile buildings having height more than 9 meters or having ground plus two upper stories including mezzanine floor.
i) Industrial buildings having covered area on all floors more than 250 sq.m
j) Storage buildings having covered area on all floors more than 250 sq.m
k) All Hazardous buildings having covered area on all floors more than 100 sq.m
(2) Rule 33: Minimum standards for fire prevention and fire safety for buildings(Please refer clause 9.3 of this document)
The minimum standards for fire prevention and fire safety for buildings as may be applicable with reference to the height of the building and class of occupancy for the purposes of section 32 and section 35 of the Act shall be as are provided in the building byelaws or National Building Code of India 2005 relating to the following matters:-
a. Access to building
b. Number, Width, Type and Arrangement of exits.
c. Protection of Exits by means of fire checks door (s) and or pressurization.
d. Compartmentation.
e. Smoke Management System.
f. Fire Extinguishers.
g. First-Aid Hose Reels.
h. Automatic fire detection and alarming system. i. MOEFA.
j. Public Address System.
k. Automatic Sprinkler System.
l. Internal Hydrants and Yard Hydrants.
m. Pumping Arrangements.
n. Captive Water Storage for firefighting.
o. Exit Signage.
p. Provision of Lifts.
q. Standby power supply
r. Refuge Area.
s. Fire Control Room
t. Special Fire Protection Systems for Protection of special Risks,:
Provided that classes of occupancies or buildings or premises for which fire prevention and fire safety measures are not provided in the building bye-laws or National Building Code of India 2005, the Director may require owner or occupier of such occupancies or buildings or premises to provide fire prevention and fire safety measures in accordance with international standards as may be provided by the Fire Prevention Wing,:
Provided further that where the Government is of the opinion that it is necessary or expedient so to do, it may, by order, for reasons to be recorded in writing, relax or modify or annul any requirement concerning fire prevention and fire safety measures under these rules with respect to any class of occupancy in any building or premises in special areas or in respect of any building or premises in any area that was constructed or which was under construction prior to the date of enforcement of these rules.
(3) Where the Director is of the opinion that it is necessary or expedient so to do, it may, for reasons to be recorded in writing, require the owner or occupier of the buildings or premises to provide additional fire prevention and fire safety measures.
Note: Notwithstanding anything contained in this Annexure, in case of any repugnancy between the provisions of this Annexure and provisions of DELHI FIRE SERVICE RULES, 2010 under DELHI FIRE SERVICE ACT, 2007, shall prevail over this Annexure, as amended from time to time.