12.1 Definitions
a. Non-ambulatory Disabilities: Impairments that, regardless of cause of manifestation, for all practical purposes, confine individuals to wheelchairs.
b. Semi-ambulatory Disabilities: Impairments that cause individuals to walk with difficulty or insecurity. Individuals using braces or crutches, amputees, arthritics, spastics, and those with pulmonary and cardiac ills may be semi-ambulatory.
c. Hearing Disabilities: Deafness or hearing handicaps that might make an individual insecure in public areas because he is unable to communicate or hear warning signals.
d. Sight Disabilities: Total blindness or impairments affecting sight to the extent that the individual, functioning in public areas, is insecure or exposed to danger.
e. Wheelchair: Chair used by disabled people for mobility. The standard size of wheelchair shall be taken as 1050 mm x 750 mm.
12.2 Scope
a. These regulations are applicable to all buildings and facilities used by the public such as educational, institutional, assembly, commercial, business, mercantile buildings, multi-units and group housing. It shall not apply to single unit residential dwellings.
b. For accessible buildings, at least one entrance and exit per facility should be accessible to a wheelchair user and persons with disabilities such as visually impaired, etc. For new buildings, the accessible entrance(s) should be the main entrance(s), and not side or back entry, intended for use of public.
c. Wherever waiting areas, coffee shops, display areas, merchandising departments, service areas, ticket counters, refreshment stands etc. are provided for public use, these facilities should be accessible to ‘all persons with disabilities’ and not just wheelchair user only.
d. In all buildings at least one unisex accessible washroom/toilet should be provided. In multi-level buildings, all floors should have one such facility near the general washrooms.
12.3 Site Development Specifications
Level of the roads, access paths and parking areas shall be described in the plan (in different colors) along with specification of the materials.
12.3.1 Access Path/ Walkway
Access path from plot entry and surface parking to Building entrance shall be minimum of 1800 mm. wide having even surface without any steps. Slope, if any, shall not have gradient greater than 5%. Selection of floor material shall be made suitably to attract floor material shall be made suitably to attract or to guide visually impaired persons (limited to coloured floor material whose colour and brightness is conspicuously different from that of the surrounding floor material or the material that emit different sound to guide visually impaired persons hereinafter referred to as "guiding floor material" (explained below). Finishes shall have a non-slip surface with a texture traversable by a wheelchair. Curbs wherever provided should blend to a common level.
Guiding/warning floor material - The floor material to guide or to warm the visually impaired persons with a change of colour or material with conspicuously different texture and easily distinguishable from the rest of the surrounding floor materials is called guiding or warning floor material. The material with different texture gives audible signals with sensory warning when a person moves on this surface with
walking stick. The guiding/warning floor material is meant to give the directional effect or warn a person at critical places. This floor material shall be provided in the following areas:
a. The access path to the building and to the parking area.
b. The landing lobby towards the information board, reception, lifts, stair-cases ad toilets.
c. Immediately at the beginning/end of walkway where there is a vehicular traffic.
d. At the location abruptly changing in level or beginning/end of a ramp.
e. Immediately in front of an entrance/exit and the landing.
Proper Signage - Appropriate identification of specific facilities within a building for the handicapped persons should be done with proper signages. Visually impaired persons make use of other senses such as hearing and touch to compensate for the lack of vision. Whereas visual signals benefit those with hearing disabilities. Signs should be designed and located so that they are easily legible by using suitable letter size (not less than 20 mm high). For visually impaired persons, information board in braille should be installed on the wall at a suitable height and it should be possible to approach them closely. To ensure safe walking there should not be any protruding sign which creates obstruction in walking. Public Address System may also be provided in busy public areas. The symbols/information should be in contrasting colour and properly illuminated because people with limited vision may be able to differentiate amongst primary colours. International symbol mark for wheelchair as shown below be installed at the lift, toilet, staircase, parking areas etc., that have been provided for the handicapped.
12.3.2 Parking
For parking of vehicles of disabled persons, following provisions shall be made:
a. Surface parking for at least two car-spaces shall be provided near the entrance of building/ premises with a maximum travel distance of 30.0 meter from building entrance. In case the access is through lift, the parking shall be located within 30.0 meter of the lift lobby.
b. The width and length of parking bay shall be minimum 3.6 m X 5.0m. where the minimum width includes transfer area beside the car with a minimum of 1200 mm. Where there are two accessible parking bays adjoining each other, then 1200mm side transfer bay shall be shared by two parking bays.
c. The information stating that the space is reserved for wheelchair users shall be conspicuously displayed (that is in big and clear letters).
d. Guiding floor materials shall be provided or a device which guides visually impaired persons with audible signals or other devices which serves the same purpose shall be provided.
e. Space should be provided for passenger drop-off / alighting points for taxis, public transport and for large vehicles such as vans, etc., as near as possible to the main accessible entrance. Vehicle drop-off areas should be a minimum of 9000 mm in length, have a minimum width of 3600 mm and be served by a kerb ramp.
f. At least one accessible route marked by tactile pavers leading to an accessible entrance of the building shall be provided from the alighting and boarding point of taxi stands and car park lots for people with disabilities.
12.4 Building Requirements
Specified facilities shall be provided in buildings for physically disabled persons with due regard to (a) access route to plinth level, (b) corridor connecting entry/exit for disabled, (c) stairway, (d) lift, (e) toilet, and (f) drinking water, as follows:
12.4.1 Approach to the plinth level.
Every building should have at least one entrance accessible to the handicapped and shall be indicated by proper signage. This entrance shall be approached through a ramp together with the stepped entry.
a) Ramped approach: Ramp shall be finished with non-slip material to enter the building. Minimum width of ramp shall be 1800 mm. with maximum gradient 1:12, length of ramp shall not exceed 9.0 meter having 800 mm high handrail on both sides extending 300 mm. beyond top and bottom of the ramp. Minimum gap from the adjacent wall to the handrail shall be 50 mm.
b) Stepped approach: For stepped approach size of tread shall not be less than 300 mm. and maximum riser shall be 150 mm. Provision of 800 mm. high handrail on both sides of the stepped approach similar to the ramped approach.
c) Exit/ Entrance Door: Minimum clear opening of the entrance door shall be 900 mm. and it shall not be provided with a step that obstructs the passage of a wheelchair user. Threshold shall not be raised more than 12 mm.
d) Entrance Landing: Entrance landing shall be provided adjacent to ramp with the minimum dimension 1800 mm x 2000 mm. The entrance landing that adjoins the top end of a slope shall be provided with floor materials to attract the attention of visually impaired persons (limited to coloured floor material whose colour and brightness is conspicuously different from that of the surrounding floor material or the material that emit different sound to guide visually impaired persons hereinafter referred to as 'guiding floor material" (see paragraph 11.3.1). Finishes shall have a non-slip surface with a texture traversable by a wheelchair. Curbs wherever provided should blend to a common level.
12.4.2 Corridor connecting exit/entrance for the disabled.
The corridor connecting the entrance/exit for handicapped leading directly outdoors to a place where information concerning the overall use of the specified building can be provided to visually impaired persons either by a person or by signs, shall be provided as follows:
a. Guiding floor material or devices that emit sound shall be provided, to guide visually impaired persons,
b. The minimum width shall be 1500 mm.
c. In case there is a difference of level slope ways shall be provided with a slope of 1:12.
d. Handrails shall be provided for ramps/slope ways.
12.4.3 Stairways
One of the stairways near the entrance/exit for the disabled shall have the following provisions: