8.1 Structural Stability related provisions in Buildings
(i) To ensure that all the safety related provisions pertaining to the structural stability of the building w.r.t earthquake / soil instability / liquefaction / soft storey/ any alteration or addition to the existing structure by any mechanical or technological means etc. have been incorporated as per the relevant byelaws, the Empanelled Structural Engineer shall prepare structural drawings as mentioned in column 2 of table-9.1 AND shall furnish the certification on the structural plans as mentioned in Annexure-1, clause A-1: 3(iii) AND shall submit the technical report for the same.
(ii) To ensure the construction of building as per the structural drawings mentioned in clause 8.1 (i) supervising engineer as mentioned in column 3 of table-27, shall furnish the plinth level / fourth floor level / last floor level / completion notice Forms. (form III; form VI(B))
| S. No. | Categories of Construction works | Structural Engineer | Supervising engineer |
| (a) | Building height In plain areas6.0 to 9.0 mt. and in hill area- 4.0 to 7.50 mt. (for all types of buildings) | The Architect OR theEmpanelled structural Engineer (Grade-1,2 or 3)may furnish the certification as mentioned in 8.1(i) | theArchitect who has prepared the planOR the Empanelled structural Engineer (Grade-1,2 or 3) |
| (b) | Stilts | The Empanelled structural Engineer (Grade-1 or 2) shall furnish the certification as mentioned in 8.1(i) | Only Empanelled structural Engineer (Grade- 1 or 2) |
| Basements | |||
| Building height In plain areas more than 9.0 to 15.0 mt.and in hill area- more than 7.50 to 12.0 mt. (for all types of buildings) | |||
| (c) | Building height In plain areas more than 15.0 mt.to 30.0 mt. (for all types of buildings) | The Empanelled structural Engineer (Grade-1) shall furnish the certification as mentioned in 8.1(i) The structural drawings prepared by the Empanelled structural Engineer shall be checked and signed by the third party auditors. | The supervision work shall be done only by the structural engineer (Grade-1) |
table: 27 : Structural and \supervising engineers
(iii) Seismic strengthening / retrofitting
Prior to seismic strengthening / retrofitting of any existing structure, evaluation of the existing structure as regards structural vulnerability in the specified wind / seismic hazard zone shall be carried out by Empanelled Structural Engineer. If as per the evaluation the seismic resistance is assessed to be less than the specified minimum seismic resistance as given in the note below, action will be initiated to carry out the upgrading of the seismic resistance of the building as per applicable standard guidelines.
a. For masonry buildings reference shall be made to IS 4326 and IS 13935
b. For concrete buildings and structures reference shall be made to IS15988: 2013 Seismic evaluation and strengthening of existing RCC buildings.
(iv) Buildings with Soft Storey
In case buildings with a flexible storeys, such as the ground storey consisting of open spaces for parking that is “Stilt buildings” or any other storey with open halls, special arrangements are to be made to increase the lateral strength and stiffness of the soft / open storey such as Steel bracing / Shear walls / Brick infills between columns.
8.2 Relevant Codes for Structural Safety in the Naturally Hazardous Areas
Requirements specified in the following Indian Standards, Byelaws and guidelines and other documents needs to be observed for structural safety and natural hazard protection of building etc.:
(i) For General Structural Safety
a. IS: 456:2000 “Byelaws of Practice for Plain and Reinforced Concrete.
b. IS: 800-2007 “Byelaws of Practice for General Construction in Steel.
c. IS: 801-1975 “Byelaws of Practice for Use of Cold Formal Light Gauge Steel Structural Members in General Building Construction.
d. IS 875 (Part 2):1987 Design loads (other than earthquake) for buildings and structures Part2 Imposed Loads. (Reference to Table 4.1- “Occupant Load” may be considered for design load)
e. IS 875 (Part 3):1987 Design loads (other than earthquake) for buildings and structures Part 3 Wind Loads.
f. IS 875 (Part 4):1987 Design loads (other than earthquake) for buildings and structures Part 4 Snow Loads.
g. IS 875 (Part 5):1987 Design loads (other than earthquake) for buildings and structures Part 5 special loads and load combination.
h. IS: 883:1994 Byelaws of Practice for Design of Structural Timber in Building.
i. IS: 1904:1986 (R 2005) “Byelaws of Practice for Structural Safety of Buildings: Foundation”
j. IS 1905:1987 “Byelaws of Practice for Structural Safety of Buildings: Masonry Walls.
k. IS 2911(Part 1): Section 1: 2010 “Byelaws of Practice for Design and Construction of Pile Foundation Section 1
Part 1: Section 2 Bored Cast-in-situ Piles
Part 1: Section 3 Driven Precast Concrete Piles
Part 1: Section 4 Bored Precast Concrete Piles
Part 2: Timber Piles
Part 3: Under Reamed Piles
Part 4: Load Test on Piles
(ii) For Cyclone / Wind Storm Protection
a. IS 875 (3):1987 "Byelaws of Practice for Design Loads (other than Earthquake) for
b. Buildings and Structures, Part 3, Wind Loads"
c. Guidelines (Based on IS 875 (3)-1987) for improving the Cyclonic Resistance of Low rise houses and other building.
(iii) For Earthquake Protection
a. IS: 1893 (Part 1)-2002 "Criteria for Earthquake Resistant Design of Structures (Fifth Revision)"
b. IS:13920-1993 "Ductile Detailing of Reinforced Concrete Structures subjected to Seismic Forces - Byelaws of Practice"
c. IS:4326-2013 "Earthquake Resistant Design and Construction of Buildings - Byelaws of Practice (Second Revision)"
d. IS:13828-1993 "Improving Earthquake Resistance of Low Strength Masonry Buildings Guidelines"
e. IS:13827:1993 "Improving Earthquake Resistance of Earthen Buildings- Guidelines"
8.3 Fire Safety
(i) Fire protection measures provided in Part IV of National Building Code of India,dealing with the fire protection measures as amended from time to time, shall be incorporated in the building plan by the Architect / fire safety consultant, as the case maybe.
(ii) All group housing buildings (flatted)and buildings of public congregation like Educational Buildings, Cinema Theatres, Function Halls and other Assembly Buildings having ground coverage of 500sq. mt.and above or of height above 6mt.and buildings of height more than 12m,are required to obtain prior clearance on the Plan prepared by fire consultant showing fire safety provisions, from the Uttarakhand Fire Services Department.
(iii) Appointment of fire safety officer: Every owner and occupier of the following classes of buildings or premises shall appoint a fire-safety officer, who shall ensure the Compliance of all fire prevention and fire safety measure and effective operation there of as provided in the relevant Act and the regulations made there under, namely:
a. Cinema houses and Multiplexes with seating capacity of more than 1000 persons and commercial complex with built-up area more than 10,000 sq. mt.
b. Hotels and hostel with 100 rooms and above;
c. Multistoried residential buildings of 500 residential Flats or more than that;
d. Oil refineries, LPG bottling plants and similar other institutions;
e. Open stadium with seating capacity more than 50,000 persons and indoor stadium with seating capacity more than 25,000 persons;
f. Hospitals and nursing homes with more than 250 beds;
g. Industries where more than 1000 are employed;
h. Public and semi-public buildings like large surface and sub-surface railway stations, interstate bus terminuses, airports, amusement parks and other similar buildings:
i. Provided that the Government may, by notification in the official Gazette, from time to time, include any other public and private premises which, in its opinion, require appointment or removal of Fire Safety Officers.
The owner / occupier of the building or Campus (mentioned in 4 above) shall obtainNo Objection Certificate annually in relation to effective operations of fire and safety measures from The Chief Fire Officer / Fire officer as the case may be. If, The Chief Fire Officer / Fire officer of the concerning district as the case may be, does not receive the application from the owner of such buildings till last date of the month of March, shall inquire buildings / campus and issue No Objection Certificate and shall impose fine also at the rate as fixed whose recovery shall be made as per provision of The Uttarakhand Fire Services Act.
(v) In addition to above buildings the owners shall get renewed the fire clearance in respect of the medium and high risk buildings mentioned in clause 4.2.
8.4 Procedure for clearance from fire service
(i) The concerned Competent Authority shall refer the building plans to the Chief Fire Officer for obtaining clearance in respect of building identified in clause 8.2 (3)-- of these Bye- Laws.
(ii) The Authority shall furnish three sets of complete building plans along with prescribed fee to the Chief Fire Officer, after ensuring that the proposals are in line with Master Plan / Zonal Plan of the area.
(iii) The plans shall be clearly marked and indicate the complete fire protection arrangements and the means of access / escape for the proposed building with suitable legend along with standard signs and symbols on the drawings. The same shall be duly signed / certified by a licensed Fire Consultant / Architect. The information regarding fire safety measures shall be furnished along with details.
(iv) The Chief Fire Officer shall examine these plans to ensure that they are in accordance with the provisions of fire safety and means of escape as per these bye-laws and shall forward two sets of plans duly signed for implementation to the building sanctioning Authority.
(v) After completion of fire-fighting installations as approved and duly tested and certified by the licensed Fire Consultant / Architect, the Owner / Builder of the building shall approach the Chief Fire Officer through the concerned Authority for obtaining clearance from fire safety and means of escape point of view. The concerned Authority shall ensure that clearance from Chief Fire Officer has been obtained for the building before granting the occupancy certificate.
(vi) On receipt of the above request, the Chief Fire Officer shall issue the No Objection Certificate from fire safety and means of escape, point of view after satisfying himself that the entire fire protection measures are implemented and functional as per approved plans.
(vii) Any deficiencies observed during the course of inspection shall be communicated to the Authority for rectification and a copy of the same shall be forwarded to the concerned building owner / builder
(viii) The following norms shall be adhered to in addition to other provisions mentioned in Part IV of National Building Code of India
a. Access to fire appliances / vehicles with details of vehicular turning circle / and clear motor-able access way around the building; which shall not be less than 6.0 mt for high rise buildings of height more than equal to 15 mt. The turning radius at corners shall not be less than 9.0 mt.
b. Size (width) of main and alternate staircase along with balcony approach, corridor ventilated lobby approach;
c. Location and details of lift enclosures;
d. Location and size of fire lift;
e. Smoke stop lobby / door where provided;
Refuse chutes; refuse chamber, services duct, etc.
g. Vehicular parking spaces;
h. Refuge area if any;
i. Service ducts / refuge chutes