Karnataka Energy Conservation Building Code 2018 Compliance Forms
| Project Address Date: | |||||||
| The following information is necessary to check a building permit application for compliance with the mechanical requirements in the Energy Conservation Building Code. | |||||||
| Applicability | Code Section | Component | Information Required Location on Plan Building Department Notes | ||||
| s Ye | No | A/N | |||||
| Comfort Systems and Control | |||||||
| Mandatory Provisions (Section 5.2) | |||||||
| 5.2.1 | Ventilation | Indicate all habitable spaces are ventilated with outdoor air in accordance with § 5.2.1 and guidelines specified in NBC | |||||
| 5.2.2 | Minimum Space Conditioning Equipment Efficiencies | Provide equipment schedule with type, capacity, efficiency | |||||
| 5.2.3 | Controls | ||||||
| 5.2.3.1 | Time clock | Indicate thermostat with night setback, 3 different day types per week, and 2-hour manual override, capable of retaining programming and time setting during loss of power for a period of at least 10 hours | |||||
| 5.2.3.2 | Temperature Controls | Indicate temperature control with 3°C dead band minimum if the system provides both heating and cooling. | |||||
| Indicate thermostats are interlocked to prevent simultaneous heating and cooling, where separate heating and cooling systems are there | |||||||
| Indicate separate thermostat control for space types mentioned in § 5.2.3.2.(c) | |||||||
| 5.2.3.3 | Occupancy Controls | Indicate occupancy controls for space types mentioned in§ 5.2.3.3 | |||||
| 5.2.3.4 | Fan Controls | Indicate two-speed motor, pony motor, or variable speed drive to control the fans and controls shall be capable to reduce the fan speed to at least two third of installed fan power | |||||
| 5.2.3.5 | Dampers | Indicate all air supply and exhaust equipment's having VFD shall have dampers that automatically close upon the situations mentioned in § 5.2.3.5 | |||||
| 5.2.4 | Piping & ductwork | Indicate sealing, caulking, gasketing, and weather stripping | |||||
| 5.2.4.1 | Piping insulation | Indicate R-value of insulation | |||||
| 5.2.4.2 | Ductwork and Plenum insulation | Indicate R-value of insulation | |||||
APPENDIX D: COMPLIANCE FORMS
APPENDIX D: COMPLIANCE FORMS
| 5.2.5 | System Balancing | Show written balance report for HVAC systems serving zones with a total conditioned area exceeding 500 m2 | |||
| 5.2.6 | Condensers | Indicate location of condenser and source of water used for condenser | |||
| 5.2.7 | Service Hot Water Heating | ||||
| 5.2.7.1 | Solar Water Heating | Indicate all Hotels and hospitals have solar water heating equipment installed for hot water design capacity as per§ 5.2.9.1 | |||
| 5.2.7.2 | Heating Equipment Efficiency | Indicate service water heating equipment shall meet the performance and efficiency as per § 5.2.9.2 | |||
| 5.2.7.3 | Other Water Heating System | Indicate supplementary heating system is designed in consideration with § 5.2.9.3 | |||
| 5.2.7.4 | Piping Insulation | Indicate the Piping insulation is compliant with § 5.2.6.1. | |||
| 5.2.7.5 | Heat Traps | Indicate vertical pipe risers serving water heaters and storage tanks are as per § 5.2.9.5 | |||
| 5.2.7.6 | Swimming Pools | Indicate the heated pools are provided with a vapor retardant pool cover on the water surface and temperature control and minimum insulation value as per § 5.2.9.6 | |||
| Prescriptive Compliance Option (Section 5.3) | |||||
| 5.3.1 | Chillers | Indicate chiller type, capacity, CoP & IPLV | |||
| 5.3.2 | Pumps | Indicate pump type (Primary, secondary, and condenser), its total installed capacity and efficiency | |||
| 5.3.3 | Cooling Towers | Indicate cooling tower type and installed capacity | |||
| 5.3.4 | Boilers | Indicate boiler type, capacity & efficiency | |||
| 5.3.5.1 | Air-Economizer(ECBC/ECBC+/SuperECBC) | Indicate air economizer is capable of modulating outside-air and return-air dampers to supply 50% of design supply air quantity as outside-air for respective building type. | |||
| 5.3.5.1 | Water-economizer(ECBC/ECBC+/SuperECBC) | Indicate water economizer is capable of providing 50% of the expected system cooling load at outside air temperatures of 10°C dry-bulb/7.2°C wet-bulb and below, if the designed building is a respective building type. | |||
| 5.3.5.4 | Testing | Indicate air-side economizers have been tested as per the requirement specified | |||||
| 5.3.6 | Variable Flow Hydronic Systems | ||||||
| 5.3.6.1 | Variable Fluid Flow | Indicate design flow rate of HVAC pumping system | |||||
| 5.3.6.2 | Isolation Valves | Indicate water cooled air-conditioning have two-way automatic isolation valves and pump motors greater than or equal to 3.7 kW is controlled by variable speed drives | |||||
| 5.3.6.3 | Variable Speed Drives | Indicate Chilled water or condenser water systems comply with either § 5.3.5.1 or § 5.3.5.2 | |||||
| 5.3.7 | Unitary, Split, Packaged Air- Conditioners | Indicate the type of system, cooling capacity. | |||||
| 5.3.8 | Controls for ECBC+ & SuperECBC Building | ||||||
| 5.3.8.1 | Centralized Demand Shed Controls | Indicate the building has a Building Management System, with all Mechanical cooling and heating systems having PLC to the zone level shall have the control capabilities mentioned in § 5.2.4.1 | |||||
| 5.3.8.2 | Supply Air temperature reset | Indicate multi zone mechanical cooling and heating systems shall have controls to automatically reset supply air temperature in response to building loads or outdoor air temperature by at least 25% of the difference between design supply air temperature and the design room air temperature. | |||||
| 5.3.8.3 | Chilled Water Temperature | Indicate chilled water systems exceeding 350 kW shall have controls to automatically reset supply water temperatures by representative building loads or by outdoor air temperature | |||||
| 5.3.9 | Controls for SuperECBC Building | Indicate that the mechanical systems comply with § 5.2.4 and § 5.2.5 | |||||
| 5.3.9.1 | Variable Air Volume Fan Control | Indicate Fans in VAV systems shall have controls or devices to limit fan motor demand as per § 5.2.5.1 | |||||
| 5.3.10 | Heat Recovery | Indicate for all Hospitality and Healthcare, heat recovery effectiveness, and efficiency of oil and gas fired boilers | |||||
| 5.3.11 | Service Water Heating | Indicate all Buildings, Hotels and hospitals have solar water heating equipment installed for hot water design capacity as per § 5.3.11. | |||||
APPENDIX D: COMPLIANCE FORMS
APPENDIX D: COMPLIANCE FORMS