For buildings to qualify as ECBC+ and Super ECBC Buildings, the WBP Method shall be followed for the Standard Design as detailed above. The Proposed Design for ECBC+ and Super ECBC Buildings shall meet the mandatory provisions of §4.2, §5.2, §6.2, and §7.2.
The EPI Ratio for ECBC+ and Super ECBC Buildings shall be equal to or less than the EPI Ratios listed under the applicable climate zone in Table 9-5 through Table 9-9 of §9.5.
Maximum Allowed EPI Ratios9.5
| Building Type Composite | |||
| ECBC | ECBC+ | Super ECBC | |
| Hotel (No Star and Star) | 1 | 0.91 | 0.81 |
| Resort | 1 | 0.88 | 0.76 |
| Hospital | 1 | 0.85 | 0.77 |
| Outpatient | 1 | 0.85 | 0.75 |
| Assembly | 1 | 0.86 | 0.77 |
| Office (Regular Use) | 1 | 0.86 | 0.78 |
| Office (24Hours) | 1 | 0.88 | 0.76 |
| Schools and University | 1 | 0.77 | 0.66 |
| Open Gallery Mall | 1 | 0.85 | 0.76 |
| Shopping Mall | 1 | 0.86 | 0.74 |
| Supermarket | 1 | 0.81 | 0.70 |
| Strip retail | 1 | 0.82 | 0.68 |
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD
| Building Type Hot and Dry | |||
| ECBC | ECBC+ | Super ECBC | |
| Hotel (No Star and Star) | 1 | 0.90 | 0.81 |
| Resort | 1 | 0.88 | 0.76 |
| Hospital | 1 | 0.84 | 0.76 |
| Outpatient | 1 | 0.85 | 0.75 |
| Assembly | 1 | 0.86 | 0.78 |
| Office (Regular Use) | 1 | 0.86 | 0.78 |
| Office (24Hours) | 1 | 0.88 | 0.76 |
| Schools and University | 1 | 0.77 | 0.66 |
| Open Gallery Mall | 1 | 0.85 | 0.77 |
| Shopping Mall | 1 | 0.84 | 0.72 |
| Supermarket | 1 | 0.73 | 0.69 |
| Strip retail | 1 | 0.82 | 0.68 |
| Building Type Temperate | |||
| ECBC | ECBC+ | Super ECBC | |
| Hotel (No Star and Star) | 1 | 0.90 | 0.80 |
| Resort | 1 | 0.88 | 0.75 |
| Hospital | 1 | 0.82 | 0.73 |
| Outpatient | 1 | 0.85 | 0.75 |
| Assembly | 1 | 0.85 | 0.76 |
| Office (Regular Use) | 1 | 0.85 | 0.75 |
| Office (24Hours) | 1 | 0.87 | 0.74 |
| Schools and University | 1 | 0.77 | 0.66 |
| Open Gallery Mall | 1 | 0.83 | 0.74 |
| Shopping Mall | 1 | 0.84 | 0.71 |
| Supermarket | 1 | 0.81 | 0.69 |
| Strip retail | 1 | 0.81 | 0.67 |
| Building Type Warm and Humid | |||
| ECBC | ECBC+ | Super ECBC | |
| Hotel (No Star and Star) | 1 | 0.91 | 0.81 |
| Resort | 1 | 0.88 | 0.75 |
| Hospital | 1 | 0.86 | 0.77 |
| Outpatient | 1 | 0.86 | 0.76 |
| Assembly | 1 | 0.88 | 0.80 |
| Office (Regular Use) | 1 | 0.86 | 0.76 |
| Office (24Hours) | 1 | 0.88 | 0.76 |
| Schools and University | 1 | 0.77 | 0.66 |
| Open Gallery Mall | 1 | 0.86 | 0.77 |
| Shopping Mall | 1 | 0.85 | 0.72 |
| Supermarket | 1 | 0.82 | 0.70 |
| Strip retail | 1 | 0.83 | 0.68 |
| Building Type Cold | |||
| ECBC | ECBC+ | Super ECBC | |
| Hotel (No Star and Star) | 1 | 0.91 | 0.82 |
| Resort | 1 | 0.88 | 0.75 |
| Hospital | 1 | 0.88 | 0.80 |
| Outpatient | 1 | 0.85 | 0.75 |
| Assembly | 1 | 0.87 | 0.81 |
| Office (Regular Use) | 1 | 0.88 | 0.80 |
| Office (24Hours) | 1 | 0.87 | 0.75 |
| Schools and University | 1 | 0.85 | 0.73 |
| Open Gallery Mall | 1 | 0.82 | 0.73 |
| Shopping Mall | 1 | 0.96 | 0.93 |
| Supermarket | 1 | 0.80 | 0.68 |
| Strip retail | 1 | 0.80 | 0.66 |
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD