General7.1
All electric and renewable energy equipment and systems shall comply with the mandatory requirements of §7.2.
Power transformers of the proper ratings and design must be selected to satisfy the minimum acceptable efficiency at 50% and full load rating. The permissible loss shall not exceed to values listed in Table 7 -1 for dry type transformers and Table 7 -2 for oil type transformers.
The BEE star rating for dry type transformer shall take precedence over this table once notified by BEE under BEE Standards and Labelling Program. For oil type transformer BEE star rated transformer (BEE Standards and Labelling Program) shall be used in all compliant buildings. Power transformers to meet compliance shall have:
(a) minimum 3 stars rating in ECBC Buildings
(b) minimum 4 stars rating in ECBC+ Buildings
(c) 5 stars rating in SuperECBC Building
| Rating kVA | Max. Losses at 50% loading W* | Max. Losses at 100% loading W* | Max. Losses at 50% loading W* | Max. Losses at 100% loading W* |
| Up to 22 kV class | 33 kV class | |||
| 100 | 940 | 2400 | 1120 | 2400 |
| 160 | 1290 | 3300 | 1420 | 3300 |
| 200 | 1500 | 3800 | 1750 | 4000 |
| 250 | 1700 | 4320 | 1970 | 4600 |
| 315 | 2000 | 5040 | 2400 | 5400 |
| 400 | 2380 | 6040 | 2900 | 6800 |
| 500 | 2800 | 7250 | 3300 | 7800 |
| 630 | 3340 | 8820 | 3950 | 9200 |
| 800 | 3880 | 10240 | 4650 | 11400 |
| 1000 | 4500 | 12000 | 5300 | 12800 |
| 1250 | 5190 | 13870 | 6250 | 14500 |
ELECTRICAL AND RENEWABLE ENERGY
ELECTRICAL AND RENEWABLE ENERGY
| 1600 | 6320 | 16800 | 7500 | 18000 |
|---|---|---|---|---|
| 2000 | 7500 | 20000 | 8880 | 21400 |
| 2500 | 9250 | 24750 | 10750 | 26500 |
*The values as per Indian Standard/BEE Standard & Labeling notification for dry type transformer corresponding to values in this table will supersede as and when the Indian standards/ BEE Standard & Labeling notification are published.
| Rating (kVA) | Impedance(%) | Max. Total Loss (W) for transformers up to 11 kV class | |||||
| ECBC Building | ECBC+ Building | SuperECBC | |||||
| 50 %Load | 100%Load | 50 %Load | 100%Load | 50 %Load | Build1in0g0%Load | ||
| 16 | 4.5 | 150 | 480 | 135 | 440 | 120 | 400 |
| 25 | 4.5 | 210 | 695 | 190 | 635 | 175 | 595 |
| 63 | 4.5 | 380 | 1250 | 340 | 1140 | 300 | 1050 |
| 100 | 4.5 | 520 | 1800 | 475 | 1650 | 435 | 1500 |
| 160 | 4.5 | 770 | 2200 | 670 | 1950 | 570 | 1700 |
| 200 | 4.5 | 890 | 2700 | 780 | 2300 | 670 | 2100 |
| 250 | 4.5 | 1050 | 3150 | 980 | 2930 | 920 | 2700 |
| 315 | 4.5 | 1100 | 3275 | 1025 | 3100 | 955 | 2750 |
| 400 | 4.5 | 1300 | 3875 | 1225 | 3450 | 1150 | 3330 |
| 500 | 4.5 | 1600 | 4750 | 1510 | 4300 | 1430 | 4100 |
| 630 | 4.5 | 2000 | 5855 | 1860 | 5300 | 1745 | 4850 |
| 1000 | 5 | 3000 | 9000 | 2790 | 7700 | 2620 | 7000 |
| 1250 | 5 | 3600 | 10750 | 3300 | 9200 | 3220 | 8400 |
| 1600 | 6.25 | 4500 | 13500 | 4200 | 11800 | 3970 | 11300 |
| 2000 | 6.25 | 5400 | 17000 | 5050 | 15000 | 4790 | 14100 |
Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS 1180 i.e., average winding temperature rise as given in Column 2 of Table 8.2 plus 3 0 ° C . An increase of 7% on total for thermal class H is allowed.
Permissible total loss values shall not exceed:
(a) 5% of the maximum total loss values mentioned in IS 1180 for oil type transform ers in voltage class above 11 kV but not more than 22 kV
(b) 7.5% of the maximum total loss values mentioned in above IS 1180 for oil type transformers in voltage class above 22 kV and up to and including 33 kV
All measurement of losses shall be carried out by using calibrated digital meters of class 0.5 or better accuracy and certified by the manufacturer. All transformers of capacity of 500 kVA and above would be equipped with additional metering class current transformers (CTs) and potential transformers (PTs) additional to requirements of Utilities so that periodic loss monitoring study may be carried out.
Voltage drop for feeders shall not exceed 2% at design load. Voltage drop for branch circuit shall not exceed 3% at design load.
| 2500 | 6.25 | 6500 | 20000 | 6150 | 18500 | 5900 | 17500 |