5.3.5.1 Economizer for ECBC, ECBC+ and Super ECBC Building
Each cooling fan system in buildings with built up area greater than 20,000 m² , shall include at least one of the following:
a) An air economizer capable of modulating outside-air and return-air dampers to supply 50% of the design supply air quantity as outside-air.
b) A water economizer capable of providing 50% of the expected system cooling load at outside air temperatures of 10° C dry-bulb/ 7.2° C wet-bulb and below.
Exception to §5.3.5.1:
a) Projects in warm-humid climate zones
b) Projects with only daytime occupancy in the hot-dry
c) Individual cooling or heating fan systems less than 3,200 litres per second
5.3.5.2 Partial Cooling
Where required by §5.3.5.1 economizers shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the cooling load.
5.3.5.3 Economizer Controls
Air economizer shall be equipped with controls
a) That allows dampers to be sequenced with the mechanical cooling equipment and not be controlled by only mixed air temperature.
b) Capable of automatically reducing outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy usage.
c) Capable of high-limit shutoff at 24 °C dry bulb temperature.
5.3.5.4 Testing
Air-side economizers shall be tested in the field following the requirements in § 12 Appendix C to ensure proper operation.
Exception to §5.3.5.4: Air economizers installed by the HVAC system equipment manufacturer and certified to the building department as being factory calibrated and tested per the procedures in §12.