The simulation model for calculating the Proposed Design and the Standard Design shall be developed in accordance with the requirements in Table 9-1. The Standard Design is based on the mandatory and prescriptive requirements of the ECBC compliant building. The Standard Design will be the same for all compliance levels (ECBC, ECBC+, and Super ECBC).
| Case | Proposed Design | Standard Design |
|---|---|---|
| 1.Design Model | (a) The simulation model of the Proposed Design shall be consistent with the design documents, including proper accounting of fenestration | The Standard Design shall be developed by modifying the Proposed Design as described in this table. Unless specified in |
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD
| and opaque envelope types and area; interior lighting power and controls; HVAC system types, sizes, and controls; and service water heating systems and controls. (b)When the whole building performance method is applied to buildings in which energy-related features have not been designed yet (e.g., a lighting system), those yet-to-be-designed features shall be described in the Proposed Design so that they minimally comply with applicable mandatory and prescriptive requirements of §4.2, §5.2, §6.2, and §7.2 and §4.3, §5.3, and §6.3 respectively. | this table, all building systems and equipment shall be modelled identically in the Standard Design and Proposed Design | |
|---|---|---|
| 2.Space Use Classification | The building type or space type classifications shall be chosen in accordance with §2.5. More than one building type category may be used in a building if it is a mixed-use facility. | Same as Proposed Design. |
| 3.Schedules | Operational schedules (hourly variations in occupancy, lighting power, equipment power, HVAC equipment operation, etc.). Suitable for the building and /or space type shall be modelled for showing compliance. Schedules must be modelled as per §9.6. In case a schedule for an occupancy type is missing in §9.6, appropriate schedule may be used. Temperature and humidity schedules and set points shall be identical in the Standard and Proposed Designs. Temperature control / thermostat throttling ranges shall also be modelled identically in both the Designs. | Same as Proposed Design. Exception: Schedules may be allowed to differ between the Standard and Proposed models wherever it is necessary to model nonstandard efficiency measures and/or measures which can be best approximated by a change in schedule. Measures that may warrant a change in operating schedules include but are not limited to automatic controls for lighting, natural ventilation, demand-controlled ventilation systems, controls for service water heating load reduction. Schedule change is not allowed for manual controls under any category. This is subject to approval by the authority having jurisdiction. |
| 4.Building Envelope | All components of the building envelope in the Proposed Design shall be modelled as shown on architectural drawings or as installed for existing building envelopes. Exceptions: The following building elements are permitted to differ from architectural drawings. (a) Any envelope assembly that covers less than 5% of the total area of that assembly type (e.g., exterior walls) need not be separately described. If not separately described, the area of an envelope assembly must be added to the area of the adjacent assembly of that same type. (b) Exterior surfaces whose azimuth orientation and tilt differ by no more than 45 degrees and are otherwise the same may be described as either a single surface or by using multipliers. (c) For exterior roofs, other than roofs with ventilated attics, the reflectance and emittance of the roof surface shall be modelled in accordance with §4.3.1.1. (d) Manually operated fenestration shading devices such as blinds or shades shall not be modelled. Permanent shading devices such as fins, overhangs, and light shelves shall bemodelled. (e) The exterior roof surface shall be modelled using the solar reflectance in accordance with ASTM E903-96 and thermal | The Standard Design shall have identical conditioned floor area and identical exterior dimensions and orientations as the Proposed Design, except as noted in (a), (b), (c), (d) and (e) below. (a) Orientation. The Standard Design performance shall be generated by simulating the building with its actual orientation and again after rotating the entire building 90, 180, 270 degrees, then averaging the results. The building shall be modelled so that it does not shade itself. (b) Opaque assemblies such as roof, floors, doors, and walls shall be modelled with the maximum U-factor allowed in §4.3.1 and §4.3.2. (c) Fenestration areas shall equal that in the Proposed Design or 40% of gross above grade wall area, whichever is smaller, and shall be distributed on each face in the same proportions as in the Proposed Design No shading projections are to be modelled; fenestration shall be assumed to be flush with the exterior wall or roof. Manually operated fenestration shading devices such as blinds or shades shall not be modelled. Fenestration |
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD
| emittance determined in accordance with ASTM E408-71. Where cool roof is proposed, emittance and reflectance shall be modelled as per ASTM E408-71 and ASTM E903-96 respectively. Where cool roof is not proposed, the exterior roof surfaces shall be modeled as per §4.3.1.1 the exterior roof surface shall be modeled with a solar reflectance of 0.70 and a thermal emittance of0.75. | U-factor shall be the maximum allowed for the climate, and the solar heat gain coefficient shall be the maximum allowed for the climate and orientation. (d) Skylight areas shall equal that in the Proposed Design or 5% of gross roof area, whichever is smaller. (e) Roof Solar Reflectance and Thermal Emittance: The exterior roof surfaces shall be modeled using a solar reflectance of 0.70 and a thermal emittance of 0.75 as per §4.3.1.1 | |
|---|---|---|
| 5.Lighting | Lighting power in the Proposed Design shall be determined as follows: Where a complete lighting system exists, the actual lighting power shall be used in the model. Where a lighting system has been designed, lighting power shall be determined in accordance with either §6.3.4. Where no lighting exists, or is specified, lighting power shall be determined in accordance with the §6.3.2 or §6.3.3 for the appropriate building type. Lighting system power shall include all lighting system components shown or provided for on plans (including lamps, ballasts, task fixtures, and furniture- mounted fixtures). Lighting power for parking garages, exterior spaces and building facades shall be modelled. Minimum Lighting controls, as per the ECBC requirements of §6.2.1, shall be modelled in the Proposed case. Automatic daylighting controls shall be modelled directly in the software or through schedule adjustments determined by a separate daylight analysis approved by the authority having jurisdiction. Other automatic lighting controls shall be modelled directly in the software by adjusting the lighting power as per the table 9.3 | Interior lighting power in the Standard Design shall be determined using the same categorization procedure (building area or space function) and categories as the Proposed Design with lighting power set equal to the maximum allowed for the corresponding method and category in either §6.3.2 or §6.3.3. Power for fixtures not included in the lighting power density calculation shall be modelled identically in the Proposed Design and Standard Design. Lighting controls shall be as per the ECBC requirements of§6.2.1.Exterior lighting power in the standard design shall be set equal to the maximum allowed in §6.3.5 |
| 6.HVAC Thermal Zones | HVAC Zones Designed: Where HVAC zones are defined on design drawings, each HVAC zone shall be modelled as a separate thermal block. Exception: Identical zones (similar occupancy and usage, similar internal loads, similar set points and type of HVAC system, glazed exterior walls face the same orientation or vary by less than 45°) may be combined for simplicity. HVAC Zones Not Designed: Where HVAC zones are not defined on design drawings, HVAC zones shall be defined based on similar occupancy and usage, similar internal loads, similar set points and type of HVAC system, glazed exterior walls that face the same orientation or vary by less than 45° in combination with the following rules: Perimeter Core Zoning: Separate thermal block shall be modelled for perimeter and core spaces. |
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD
| Perimeter spaces are defined as spaces located within 5 meters of an exterior or semi exterior wall. Core spaces are defined as spaces located greater than 5 meters of an exterior or semi exterior wall. Separate thermal blocks shall be modelled for floors in contact with ground and for floors which have a ceiling/roof exposure to the ambient. | ||
|---|---|---|
| 7.HVAC Systems | The HVAC system type and all related performance parameters, such as equipment capacities and efficiencies, in the Proposed Design shall be determined as follows: (a) Where a complete HVAC system exists, the model shall reflect the actual system type using actual component capacities and efficiencies. (b)Where an HVAC system has been designed, the HVAC model shall be consistent with design documents. Mechanical equipment efficiencies shall be adjusted from actual design conditions to the rating conditions specified in §5, if required by the simulation model. (c) Where no heating system has been specified, the heating system shall be assumed to be electric. The system characteristics shall be identical to the system modelled in the Standard Design. (d)Where no cooling system has been specified, the cooling system and its characteristics shall be identical to the system modelled in the Standard Design. | The HVAC system type shall be as per Table 9-2 and related performance parameters for the Standard Design shall be determined from requirements of §9.4.2. Equipment performance shall meet the requirements of §5 for code compliant building. |
| 8.Service Hot Water | The service hot water system type and all related performance parameters, such as equipment capacities and efficiencies, in the Proposed Design shall be determined as follows: (a) Where a complete service hot water system exists, the model shall reflect the actual system type using actual component capacities and efficiencies. (b)Where a service hot water system has been designed, the service hot water model shall be consistent with design documents. (c) Where no service hot water system exists, or is specified, no service hot water heating shall be modelled | The service water heating system shall be of the same type as the Proposed Design. For residential facilities, hotels and hospitals the Standard Design shall have a solar hot water system capable of meeting 20% of the hot water demand. Systems shall meet the efficiency requirements of§5.2.7.2. |
| 9.Miscellaneous Loads | Receptacle, motor, and process loads shall be modelled and estimated based on the building type or space type category. These loads shall be included in simulations of the building and shall be included when calculating the Standard Design and Proposed Design. All end-use load components within and associated with the building shall be modelled, unless specifically excluded by this Table, but not limited to, exhaust fans, parking garage ventilation fans, exterior building lighting, swimming pool heaters and pumps, elevators and escalators, refrigeration equipment, and cooking equipment. |
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD
| 10.Modelling Limitations to the Simulation Program | If the simulation program cannot model a component or system included in the Proposed Design, one of the following methods shall be used with the approval of the authority having jurisdiction: (a)Ignore the component if the energy impact on the trade-offs being considered is not significant. (b)Model the component substituting a thermodynamically similar component model. (c) Model the HVAC system components or systems using the HVAC system of the Standard Design in accordance with Section 6 of this table. Whichever method is selected, the component shall be modelled identically for both the Proposed Design and Standard Design models. | Same as Proposed Design. |
|---|
| Hotel/Motel, Hospital Patient Rooms, Hotel Guest Rooms, Resorts, Villas, Sleeping Quarters in Mixed-use Buildings, Schools, Classrooms/ Lecture Rooms<sup>1</sup> | Buildings with Less than or Equal to 12,500 m² of Conditioned Area | Buildings with More than 12,500 m² of Conditioned Area | Data Centre/ Server/ComputerRooms | |
|---|---|---|---|---|
| Name | System A | System B | System C | System D |
| SystemType<sup>2</sup> | Split AC | VRF: Variable Refrigerant Flow | VAV: Central cooling plant with variable volume AHU<sup>3</sup> | Computer Room air conditioners |
| Fan Control | Constant Volume | Constant volume | Variable volume | Constant volume |
| Cooling Type | Direct expansion with air cooled condenser | Direct expansion with air cooled condenser | Chilled Water with water cooled condenser | Direct expansion with air cooled condenser |
| Heating Type | 1. Heat Pump: Where no heating system has been specified or where an electric heating system has been specified in the Proposed Design 2. Fossil Fuel Boiler, Fossil/Electric Hybrid: Where a heating system exists and a fossil fuel hot water boiler has been specified in the Proposed Design | 1. Heat Pump: Where no heating system has been specified or where an electric heating system has been specified in the Proposed Design 2. Fossil Fuel Boiler,Fossil/Electric Hybrid:: Where a heating system exists and a fossil fuel | 1. Electric resistance: Where no heating system has been specified or where an electric heating system has been specified in the Proposed Design 2. Fossil Fuel Boiler,Fossil/Electric Hybrid: Where a heating system exists | NA |
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD
| hot water boiler has been specified in the Proposed Design | and a fossil fuel hot water boiler has been specified in the Proposed Design | |||
| Notes: 1. Buildings of the listed occupancy types or spaces in Mixed-use Buildings with the listed occupancy types. 2. Where attributes make a building eligible for more than one system type; use the predominant condition to determine the Standard Design system type provided the non-predominant conditions apply to less than 1,000 m2 of conditioned floor area. Use additional system type for non-predominant conditions if those conditions apply to more than 1,000 m2 of conditioned floor area. Use additional system type for any space which has a substantial difference in peak loads and/or operational hours compared to the predominant space type. Such spaces may include but are not limited to computer/server rooms, retail areas in residential, or office buildings. 3. One AHU per floor at a minimum. | ||||
| Automatic Control Device | Daytime occupancy and area <300 m<sup>2</sup> | All Others |
|---|---|---|
| Programmable Timing Control | 10% | 0% |
| Occupancy Sensor | 10% | 10% |
| Occupancy Sensor and Programmable Timing Control | 15% | 10% |