The HVAC system type and related performance parameters for the Standard Design shall be determined from Table 9 -2 and the following rules:
(a) Other components: Components and parameters not listed in Table 9-2 or otherwise specifically addressed in this subsection shall be identical to those in the Proposed Design.
Exception to § 9.4.2(a): Where there are specific requirements in §5.2.2, the component efficiency in the Standard Design shall be adjusted to the lowest efficiency level allowed by the requirement for that component type.
(b) All HVAC and service water heating equipment in the Standard Design shall be modeled at the minimum efficiency levels, both part load and full load, in accordance with §5.2.2.
(c) Where efficiency ratings, such as EER and COP, include fan energy, the descriptor shall be broken down into its components so that supply fan energy can be modeled separately.
(d) Minimum outdoor air ventilation rates shall be the same for both the Standard Design and the Proposed Design except for conditions specified in §9.4.2.1.
(e) The equipment capacity for the standard design shall be based on sizing runs for each orientation and shall be oversized by 15% for cooling and 25% for heating, i.e., the ratio between the capacities determined by the sizing runs shall be 1.15 for cooling and 1.25 for heating.
(f) Unmet load hours for the Proposed Design shall not differ from unmet load hours for the Standard Design by more than 50 hours. Maximum number of unmet hours shall not exceed 300 for either case.
Minimum Outdoor Air Rates:9.4.2.1
Minimum outdoor air rates shall be identical for both the Standard Design and Proposed Design, except
(a) when modelling demand-controlled ventilation (DCV) in the Proposed Design (DCV is not required in the Standard Design as per §5.2.1.3.
(b) when the Proposed Design has a ventilation flow higher than the minimum required by the applicable code, the Standard Design shall be modelled as per the minimum ventilation rate required by the applicable code and the Proposed Design shall be modelled as per actual design (higher than Standard Design)
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD
Fan Schedules9.4.2.2
Supply and return fans shall operate continuously whenever the spaces are occupied and shall be cycled to meet heating and cooling loads during unoccupied hours.
Fan Power9.4.2.3
(a) For Systems Types A, B and D,
Design Airflow Rates9.4.2.4
Design airflow rates for the Standard Design shall be sized based on a supply air to room air temperature difference of 1 1 ° C for cooling and 1 8 ° C for he ating. The Proposed Design airflow rates shall be as per design.
Economizers (airside and waterside)9.4.2.5
Airside economizers shall be modelled in the Standard Design as per the requirements of §5.3.5.
Exception to §9.4.2.5: Airside economizer shall not be modelled for Standard Design HVAC System Type A.
Energy Recovery9.4.2.6
Energy recovery shall be modelled in the standard design as per the requirement of §5.3.
Chilled Water Design Supply Temperatures9.4.2.7
Chilled water design supply temperature shall be modelled at 6 . 7 ° C and return temperature at 1 3 . 3 ° C
Chillers9.4.2.8
Only electric chillers shall be modelled in the Standard Design for System C. Chillers shall meet the minimum efficiency requirements indicated in Table 5-1 and Table 5-2. Chillers in the Standard Design shall be selected as per Table 9-4 below:
| Peak Building Cooling Load (kWr) | Chiller Type |
|---|---|
| < 1,055 | 1 Water Cooled Screw Chiller |
| 1,055 to 2,110 | 2 Water Cooled Screw Chillers equally sized |
| > 2,110 | 2 or more Water Cooled Centrifugal Chillers equally sized such that no Chiller is greater than 2,813 kW<sub>r</sub> |
Exception to 9.4.2.8: Air cooled chillers are allowed to be modelled in the Standard Design if the Proposed Design has air cooled chillers. If the proposed building has a mix of air and water-cooled chillers, then the Standard Design shall be modelled with a mix of air and watercooled chillers in the same proportion as in the Proposed Design.
Chilled Water Pumps9.4.2.9
Chilled and condenser water pumps for the Standard Design shall be modelled as per power and efficiency limits specified in Table 5-16.
Standard Design chilled water pumps shall be modelled as primary-secondary with variable secondary flow.
Cooling Tower9.4.2.10
Standard Design cooling tower shall be modelled as an open circuit axial flow tower with power and efficiency as per §5.3.3. The fans shall be modelled as two speed.
Condenser water design supply temperature shall be 29.4°C or 5 . 6 ° C approach to wet bulb temperature, whichever is lower, with a design temperature rise of 5 . 6 ° C
Boiler9.4.2.11
Standard Design boilers shall be modelled as natural draft boilers and shall use the same fuel as the Proposed Design. Boiler efficiency shall be modelled as per the table 5-6.
Hot Water Design Supply Temperatures9.4.2.12
Hot water design supply temperature shall be modelled at 8 2 ° C and return temperature at 5 4 ° C ,
WHOLE BUILDING PERFORMANCE METHOD
WHOLE BUILDING PERFORMANCE METHOD
Hot Water Pumps9.4.2.13
The Standard Design hot water pumps shall be modelled with a minimum efficiency of 70% and a pump power of 300 W/l-s-1. Standard Design hot water pumps shall be modelled as primary-secondary with variable secondary flow.
Campus/District Cooling Systems9.4.2.14
All district cooling plants shall be assumed to be on grid electricity, unless otherwise specified and supported through pertinent documents. New district plants shall comply with the mandatory requirements of ECBC irrespective of who owns and/or operates the district plant.
Projects may choose either option A or option B given below for modelling campus/district cooling systems.
Option A
The cooling source shall be modelled as purchased chilled water in both the Standard Design and Proposed Design. For the Standard Design, Table 9-2 shall be modified as follows:
(a) For System Type C; purchased chilled water sha ll be modelled as the cooling source.
(b) System Types A and B shall be replaced with a two -pipe fan coil system with purchased chilled water as the cooling source.
The chilled water/thermal energy consumption simulated by the software shall be converted to units of kWh and added to the overall building energy consumption. The following conversion factors shall be used to convert chilled water/thermal energy consumption to units of kWh.
1 ton hour = 0.85 kWh
1 MBtu = 1,000,000 Btu = 293 kWh
Option B
The Standard Design shall be modelled as per Table 9-2 HVAC Systems Map. For the Proposed Design, model a virtual onsite chilled water plant with Chiller, Pumps and cooling towers modelled at minimum efficiency levels as per §9.4.2.7 to §9.4.2.10. Airside/low side capacities shall be modelled as per design and the plant capacities shall be auto-sized by the software.