The simulation software shall be a computer-based program for the analysis of energy consumption in buildings and be approved by the authority having jurisdiction. The simulation program shall, at a minimum, have the ability to model the following:
a) Energy flows on an hourly basis for all 8,760 hours of the year,
b) Hourly variations in occupancy, lighting power, miscellaneous equipment power, thermostat set points, and HVAC system operation, defined separately for each day of the week and holidays,
c) Thermal mass effects,
d) Ten or more thermal zones,
e) Part-load and temperature dependent performance of heating and cooling equipment,
f) Air-side and water-side economizers with integrated control.
In addition to the above, the simulation tool shall be able to produce hourly reports of energy use by energy source and shall have the capability to performing design load calculations to determine required HVAC equipment capacities, air, and water flow rates in accordance with §5 for both the proposed and Standard building designs.
The simulation program shall be tested according to ASHRAE Standard 140 Method of Test for the Evaluation of Building Energy Analysis Computer Programs (ANSI approved) and the results shall be furnished by the software provider.
9.3.2 Climate Data
The simulation program shall use hourly values of climatic data, such as temperature and humidity, from representative climatic data for the city in which the Proposed Design is to be located. For cities or urban regions with several climate data entries, and for locations where weather data are not available, the designer shall select available weather data that best represent the climate at the construction site.
9.3.3 Compliance Calculations
The Proposed Design and Standard Design shall be calculated using the following:
a) Same simulation program,
b) Same weather data, and
c) Identical building operation assumptions (thermostat set points, schedules, equipment and occupant loads, etc.) unless an exception is allowed by this Code or the authority having jurisdiction for a given category.
Calculating Energy Consumption of Proposed Design and Standard9.4 Design