All fenestration with U-factors, SHGC, or visible light transmittance determined, certified and labelled in accordance ISO 15099 shall be assigned those values.
10.2.1 Unrated Vertical Fenestration.
For unrated vertical fenestration, both operable and fixed, the glass VLT reported by manufacturer must meet or exceed 0.37 (as it accounts for framing). The SHGC values reported by glass manufacturer must meet or exceed the prescriptive requirements in Table 4-10 and Table 4-11 for compliance.
U-factors for unrated vertical fenestration, both operable and fixed, sha ll be assigned as per Table 10-1.
| Frame Type | Glazing Type | U-Factor (W/m<sup>2</sup>.K) |
|---|---|---|
| All frame types | Single Glazing | 7.1 |
| Wood, vinyl, or fiberglass frame or metal frame with thermal break | Double Glazing (COG U value >1.6 W/m<sup>2</sup>.K) | 3.4 |
| Wood, vinyl, or fiberglass frame or metal frame with thermal break | Double Glazing (COG U value <1.6 W/m<sup>2</sup>.K) | 3.0 |
| Metal and other frame type | Double Glazing | 5.1 |
Typical Roof Constructions10.3
For calculating the overall U-factor of a typical roof construction, the U-factors from the typical wall construction type and effective U -factor for insulation shall be combined according to the following equation:
Where,
UTotal, Roof
Total U -factor of the roof with insulation
UTypical Roof
U-factor of the roof
UTypical Insulation
U-factor of the effective insulation