ECBC+ building shall comply with requirements of § 5.3.8 in addition to complying with requirements of §5.2.3.
5.3.8.1 Centralized Demand Shed Controls
ECBC+ and SuperECBC Buildings with built up area greater than 20,000 m² shall have a building management system. All mechanical cooling and heating systems in ECBC+ and SuperECBC Buildings with any programmable logic controller (PLC) to the zone level shall have the following control capabilities to manage centralized demand shed in noncritical zones:
(a) Automatic demand shed controls that can implement a centralized demand shed in non-critical zones during the demand response period on a demand response signal.
(b) Controls that can remotely decrease or increase the operating temperature set points by four degrees or more in all noncritical zones on signal from a centralized control point
(c) Controls that can provide an adjustable rate of change for the temperature setup and reset
The centralized demand shed controls shall have additional capabilities to
(i) Be disabled by facility operators
(ii) Be manually controlled from a central point by facility operators to manage heating and cooling set points
5.3.8.2 Supply Air Temperature Reset
Multi zone mechanical cooling and heating systems in ECBC+ and SuperECBC Buildings shall have controls that automatically reset the supply-air temperature in response to building loads or to outdoor air temperature. Controls shall reset the supply air temperature to at least 25% of the difference between the design supply air temperature and the design room air temperature.
Exception to § 5.3.8.2: ECBC+ and SuperECBC Buildings in warm humid climate zone.
5.3.8.3 Chilled Water Temperature Reset
Chilled water systems with a design capacity exceeding 350kWr supplying chilled water to comfort conditioning systems in ECBC+ and SuperECBC Buildings shall have controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature.
Exceptions to §5.3.8.3 Controls to automatically reset chilled water temperature shall not be required where the supply temperature reset controls causes improper operation of equipment.
5.3.9 Controls for SuperECBC Buildings
SuperECBC Buildings shall comply with requirements of § 5.3.9 in addition to complying with requirements of §5.2.3 and §5.3.8.
5.3.9.1 Variable Air Volume Fan Control
Fans in Variable Air Volume (VAV) systems in SuperECBC Buildings shall have controls or devices that will result in fan motor demand of no more than 30% of their design wattage at 50% of design airflow based on manufacturer's certified fan data;
5.3.10 Energy Recovery
All Hospitality and Healthcare, with systems of capacity greater than 2,100 litres per second and minimum outdoor air supply of 70% shall have air-to-air heat recovery equipment with minimum 50% recovery effectiveness.
At least 50% of heat shall be recovered from diesel and gas fired generator sets installed in Hospitality, Healthcare, and Business buildings with built up area greater than 20,000 m ² .