4.1 Acceptable Indoor Noise Levels in Buildings
The generally acceptable noise levels inside buildings are given in Table 4.
| Sl Location Noise Level No. dB(A)(1) (2) (3) |
|---|
| i) Auditoria and concert halls 20-25 ii) Radio and TV studios 20-25 iii) Cinemas 25-30 iv) Music rooms 25-30 v) Hospitals and cinema theatres 35-40 vi) Apartments, hotels and homes 35-40 vii) Conference rooms, small offices and 35-40 libraries viii) Court rooms and class rooms 40-45 ix) Large public offices, banks and stores 45-50 x) Restaurants 50-55 |
4.2 Vulnerable Buildings
Some buildings or parts of buildings are specially vulnerable to noise, for example, recording and radio studios, hospitals and research laboratories. These should not be sited near loud noise sources. Most vulnerable buildings contain some areas which are themselves noisy and in such buildings the less vulnerable elements should be planned to act as noise buffers. Most noisy buildings also contain quiet accommodation, which equally may be planned to act as a buffer between the noisy part of the building and adjoining vulnerable buildings.
4.3 The details of site and internal planning and insulation requirements are covered under individual occupancies (5 to 12) as applicable to the respective character and sources of noise in different buildings.
4.4 Sound Insulation of Non-Industrial Buildings by Constructional Measures
The desired (acceptable) noise levels and the recommended insulation values for the various areas may be achieved by providing sound insulation treatments by constructional measures. The details of the same are given in Annex F. The recommendations given in Annex F are applicable to non-industrial buildings like residences, educational buildings, hospitals and office buildings.
4.5 Special Problems Requiring Expert Advice — (see 3.8 and Annex E).