2.0 For the purpose of this Section the following definitions shall apply.
2.1 Air Conditioning — The process of treating air so as to control simultaneously its temperature, humidity, purity, distribution and air movement and pressure to meet the requirements of the conditioned space.
2.2 Atmospheric Pressure — The weight of air column on unit surface area of earth by atmospheric column. At sea level, the standard atmospheric or barometric pressure is 760 mm of mercury (1 033 mm of water column/101.325 kPa).
Generally atmospheric pressure is used as a datum for indicating the system pressures in air conditioning and accordingly, pressures are mentioned above the atmospheric pressure or below the atmospheric pressure considering the atmospheric pressure to be zero. A ‘U’ tube manometer will indicate zero pressure when pressure measured is equal to atmospheric pressure.
2.3 Buildings Related Illnesses (BRI) — The illness attributed directly to the specific air-borne building contaminants like the outbreak of the Legionnaire’s disease after a convention and sensitivity pneumonitis with prolonged exposure to the indoor environment of the building.
Some of the other symptoms relating to BRI are sensory irritation of eyes, ears and throat, skin irritation, headache, nausea, drowsiness, asthma like symptoms in non-asthmatic persons. The economic consequences of BRI is decreased productivity, absenteeism and the legal implications if occupants IAQ complaints are left unresolved.
2.4 Dewpoint Temperature — The temperature at which condensation of moisture begins when the air is cooled at same pressure.
2.5 Dry-Bulb Temperature — The temperature of the air, read on a thermometer, taken in such a way as to avoid errors due to radiation.
2.6 Duct System — A continuous passageway for the transmission of air which, in addition to the ducts, may include duct fittings, dampers, plenums, and grilles and diffusers.
2.7 Enthalpy — A thermal property indicating the quantity of heat in the air above an arbitrary datum, in kilo Joules per kg of dry air (or in Btu per pound of dry air).
2.8 Evaporative Air Cooling — The evaporative air cooling application is the simultaneous removal of sensible heat and the addition of moisture to the air. The water temperature remains essentially constant at the wet-bulb temperature of the air.
2.9 Fire Damper — A closure which consists of a normally held open damper installed in an air distribution system or in a wall or floor assembly and designed to close automatically in the event of a fire in order to maintain the integrity of the fire separation.
2.10 Fire Separation Wall — The wall providing complete separation of one building from another or part of a building from another part of the same building to prevent any communication of fire or heat transmission to wall itself which may cause or assist in the combustion of materials of the side opposite to that portion which may be on fire.
5
2.11 Global Warming Potential (GWP) — The potential of a refrigerant to contribute to global warming.
Global warming can make our planet and its climate less hospitable and more hostile to human life, thus necessitating reduction in emission of green house gases such as CO₂, SOx, NOx and refrigerants. Long atmospheric life time of refrigerants results in global warming unless the emissions are controlled.
GWP values of some of the refrigerants are given below:
| Sl No. | Refrigerant | GWP Values |
|---|---|---|
| (1) | (2) | (3) |
| i) | R-12 | 10 600 |
| ii) | R-22 | 1 900 |
| iii) | R-134a | 1 600 |
| iv) | R-123 | 120 |
| v) | R-407c | 1 980 |
| vi) | R-407a | 2 340 |
| vii) | R-410a | 2 340 |
The values indicated above are for an integration period of 100 years.
2.12 Hydronic Systems — The water systems that convey heat to or from a conditioned space or process with hot or chilled water. The water flows through piping that connects a chiller or the water heater to suitable terminal heat transfer units located at the space or process.
2.13 Indoor Air Quality (IAQ) — Air quality that refers to the nature of conditioned air that circulates throughout the space/area where one works or lives, that is, the air one breathes when indoors.
It not only refers to comfort which is affected by temperature, humidity, air movement and odours but also to harmful biological contaminants and chemicals present in the conditioned space. Poor IAQ may be serious health hazard. Carbon dioxide has been recognized as the surrogate ventilation index.
2.14 Infiltration/Exfiltration — The phenomenon of outside air leaking into/out of an air conditioned space.
2.15 Ozone Depletion Potential (ODP) — The potential of refrigerant or gases to deplete the ozone in the atmosphere.
The ODP values for various refrigerants are as given below:
| R-11 | 1.000 |
|---|---|
| R-12 | 0.820 |
| R-22 | 0.050 |
| R-123 | 0.012 |
| R-134a | 0.000 |
| R-407a | 0.000 |
| R-407c | 0.000 |
| R-410a | 0.000 |
Due to high ODP of R-11, R-12 and R-22, their use in the air conditioning and refrigeration is being phasedout. R-123 is also in the phase-out category of refrigerants.
2.16 Plenum — An air compartment or chamber to which one or more ducts are connected and which forms part of an air distribution system.
The pressure drop and air velocities in the plenum should be low. Generally, the velocity in plenum should not exceed 1.5 m/s to 2.5 m/s.
2.17 Positive Ventilation — The supply of outside air by means of a mechanical device, such as a fan.
2.18 Psychrometry — The science involving thermodynamic properties of moist air and the effect of atmospheric moisture on materials and human
comfort. It also includes methods of controlling thermal properties of moist air.
2.19 Psychrometric Chart — A chart graphically representing the thermodynamic properties of moist air.
2.20 Recirculated Air — The return air that has been passed through the conditioning apparatus before being re-supplied to the space.
2.21 Refrigerant — The fluid used for heat transfer in a refrigerating system, which absorbs heat at a low temperature and low pressure of the fluid and rejects heat at a higher temperature and higher pressure of the fluid, usually involving changes of state of the fluid.
2.22 Relative Humidity — Ratio of the partial pressure of actual water vapour in the air as compared to the partial pressure of maximum amount of water that may be contained at its dry bulb temperature.
When the air is saturated, dry-bulb, wet-bulb and dewpoint temperatures are all equal, and the relative humidity is 100 percent.
2.23 Return Air — The air that is collected from the conditioned space and returned to the conditioning equipment.
2.24 Shade Factor — The ratio of instantaneous heat gain through the fenestration with shading device to that through the fenestration.
2.25 Sick Building Syndrome (SBS) — A term, which is used to describe the presence of acute non-specific symptoms in the majority of people caused by working in buildings with an adverse indoor environment. It could be a cluster of complex irritative symptoms like irritation of the eyes, blockened nose and throat, headaches, dizziness, lethargy, fatigue irritation, wheezing, sinusitis, congestion, skin rash, sensory discomfort from odours, nausea, etc. These symptoms are usually short-lived and experienced immediately after exposure; and may disappear when one leaves the building.
SBS is suspected when significant number of people spending extended time in a building report or experience acute on-site discomfort. The economic consequences of SBS, like BRI, are decreased productivity, absenteeism and the legal implications if occupants IAQ complaints are left unresolved.
2.26 Smoke Damper — A damper similar to fire damper, however, having provisions to close automatically on sensing presence of smoke in air distribution system or in conditioned space.
2.27 Static Pressure — The pressure that is required to be created by the fan over the atmospheric pressure
to overcome the system resistances such as resistances in ducts, elbows, filters, dampers, heating/cooling coils, etc.
Static pressure is measured by a U tube manometer relative to the atmospheric pressure, which is considered as zero pressure. In exhaust systems, fan produces negative static pressure, which is again used to overcome the system resistances.
2.28 Supply Air — The air that has been passed through the conditioning apparatus and taken through the duct system and distributed in the conditioned space.
2.29 Supply and Return Air Grilles and Diffusers — Grilles and diffusers are the devices fixed in the air conditioned space for distribution of conditioned supply air and return of air collected from the conditioned space for re-circulation.
2.30 Thermal Transmittance — Thermal transmission per unit time through unit area of the given building unit divided by the temperature difference between the air or some other fluid on either side of the building unit in ‘steady state’ conditions.
2.31 Thermal Energy Storage — Storage of thermal energy, sensible, latent or combination thereof for use in central system for air conditioning or refrigeration. It uses a primary source of refrigeration for cooling and storing thermal energy for reuse at peak demand or for backup as planned.
2.32 Water Conditioning — The treatment of water circulating in a hydronic system, to make it suitable for air conditioning system due to its effect on the economics of air conditioning plant.
Untreated water used in air conditioning system may create problems such as scale formation, corrosion and organic growth. Appraisal of the water supply source including chemical analysis and determination of composition of dissolved solids is necessary to devise a proper water-conditioning programme.
2.33 Water Hardness — Hardness in water represented by the sum of calcium and magnesium salts in water, which may also include aluminium, iron, manganese, zinc, etc. A chemical analysis of water sample should provide number of total dissolved solids (TDS) in a water sample in parts per million (ppm) as also composition of each of the salts in parts per million.
Temporary hardness is attributed to carbonates and bicarbonates of calcium and/or magnesium expressed in parts per million (ppm) as CaCO3° The remainder of the hardness is known as permanent hardness, which is due to sulphates, chloride, nitrites of calcium and/or magnesium expressed in ppm as CaCO₃
Temporary hardness is primarily responsible for scale formation, which results in poor heat transfer resulting in increased cost of energy for refrigeration and air conditioning. Permanent hardness (non-carbonate) is not as serious a factor in water conditioning because it has a solubility which is approximately 70 times greater than the carbonate hardness. In many cases, water may contain as much as 1 200 ppm of non-carbonate hardness and not deposit a calcium sulfate scale.
The treated water where hardness as ppm of CaCO is reduced to 50 ppm or below, is recommenced for air conditioning applications.
pH is a measure of acidity, pH is a negative logaritham base 10, of the concentration of hydrogen ion in grams per litre. Water having a pH of 7.0 is neutral, a pH value less than 7 is acidic and pH value greater than 7 is alkaline. Water with pH less than 5 is quite acidic and corrosive to ordinary metals and needs to be treated.
2.34 Wet-Bulb Temperature — The temperature registered by a thermometer whose bulb is covered by a wetted wick and exposed to a current of rapidly moving air of velocity not less than 4.5 m/s.
Wet-bulb temperature is indicated by a wet bulb psychrometer constructed and used according to specifications.