| Type of Circuit | Wire Size | Number of Circuits |
|---|---|---|
| Lighting | 1.0 mm² | 2 or more |
| Socket-outlets 10 A | 2.5 mm² | Any numberAreas such askitchens andlaundries 3 ×double socket-outlets per circuit.Other areas up to12 double socket-outlets |
| Socket-outlets 15 or 20 A | 2.5 mm² | 1 |
| Water heater 3 kW | 1.5 mm² | 1 |
| Water heater 3-6 kW | 2.5 mm² | 1 |
| Free standing electric range | 6.0 mm² | 1 |
| Separate oven and/or cook top | 4.0 mm² | 1 |
| Permanently connected appliancesincluding dish-washers, heaters, etc | 2.5 mm² | 1 above 10 A. Up to 10 A can bewired as part of a socket-outlet circuit |
| Submains to garage or out-building | 2.5 mm² | 1 for each |
| Mains cable | 16 mm² | 1 |
5.6.1 Selecting and Installing Cables
5.6.1.1 Cable insulation types
| For the mains cable | Tough plastic sheathed (TPS) cable |
|---|---|
| For installation wiring | Tough plastic sheathed (TPS) cables |
| For main earth or main equipotential wire | Polyvinyl chloride (PVC) insulated conduit wire |
| Underground installation and installation in cable trench, feeders between buildings etc., | PVC insulated, PVC sheathed armoured cables or XLPE insulated, PVC sheathed cables armoured cables |
| Installation in plant rooms, switch rooms etc, on cable tray or ladder or protected trench, where risk of mechanical damage to cable does not exist. | PVC insulated, PVC sheathed or XLPE insulated, PVC sheathed unarmoured cables |
For the purposes of this Code cables above 1 mm2 must have stranded conductors. All cables when installed, must be adequately protected against mechanical damage. This can be carried out by either having additional protection, such as being enclosed in PVC conduit or metal pipes, or placing the cables in a
5.6.1.2 Circuit wire sizes
suitable location that requires no additional protection. The cables for wiring circuits in electrical installation must have the appropriate wire size matching the requirement of the loads and the following table gives the recommendations for different types of loads.
| Circuits | Minimum Wire Size | Wire Colour |
|---|---|---|
| 1-way lighting | 2 + E cable wires 1.5 mm² | Red-Black-Green or Green/Yellow |
| 2-way lighting control (straps between the 2 switches) | 3-wire cable 1.5 mm² | Red-White-Blue |
| Storage water heaters up to 3 kW | 2 + E cable 1.5 mm² (stranded conductors) | Red-Black-Green or Green/Yellow |
| Storage water heaters between 3 kW and 6 kW | 2 + E cable 2.5 mm² (stranded conductors) | Red-Black-Green or Green/Yellow |
| Socket-outlets and permanent connection units | 2 + E cable 2.5 mm² (stranded conductors) | Red-Black-Green or Green/Yellow |
| Submains to garages or out buildings | 2 + E cable 2.5 mm² (stranded conductors) | Red-Black-Green or Green/Yellow |
| Cooking hobs | 2 + E cable 4 mm² | Red-Black-Green or Green/Yellow |
| Separate ovens | 2 + E cable 4 mm² (stranded conductors) | |
| Electric range | 2 + E cable 6 mm² (stranded conductors) | Red-Black-Green or Green/Yellow |
| Mains | 2 wire cable 16 mm² (stranded conductors) | Red-Black |
| Main equipotential bonding wire | Conduit wire 4 mm² (stranded conductors) | Green or Green/Yellow |
| Main earth wire | Conduit wire 6 mm² (stranded conductors) | Green or Green/Yellow |
2 + E is also known as twin and earth
Switch or isolator controlling a water heater or geyser should not be located within 1 m from the location of a shower or bath tub, to avoid a person in wet condition reaching the switch or isolator. It is preferable to provide the control switch outside the bathroom near
the entrance and provide an indication at the water heater. A socket or a connector block with suitable protection against water spray should be provided to connect the water heater. The above considerations apply to switches for outdoor lights and other
appliances, with the object of avidance of operation of a switch when a person is wet. Sockets in kitchen, bathroom, toilet, garage etc, should not be provided within a height of 1 m from the ground level. Similar care has to be taken for installations involving fountains, swimming pools etc. Light fittings in such areas should be fed at low voltage, preferably through an isolating transformer with a proper earth leakage protection.