(1) General: The planning, design and construction of any building shall be such as to ensure safety from fire. For this purpose, unless otherwise specified in these Regulations, Fire Protection Chapter, National Building Code as amended time to time shall apply.
For high rise and special buildings, additional provisions relating to fire protection contained in Appendix I shall also apply,
(A) For proposal under regulations 33(5), 33(6),33(7),33(7)(A),33(9),33(9)(A), 33(9)(B), 33(10), 33(10)(A), 33(11), 33(15), 33(20)(A)
a) In case of rehabilitation/composite buildings having height more than 32 m up to 70 m, at least one side other than road side, shall have clear open space of 6 m at ground level, accessible from road side.
Provided, if the building abuts another road of 6 m or more, this condition shall not be insisted upon.
Provided if the building abuts on two roads having width of 6.0 m, the clear space of 9m shall be available including abutting Road in front of the building and the 6m roads shall be connected to the road of having width of at least 9m.
However, if podium is proposed it shall not extend beyond 6 m from building line so as to have clear open space of 6 m at ground level beyond podium accessible for fire appliances.
No ramps for the podium shall be provided in these side open spaces.
b) In case of rehabilitation/composite buildings having height more than 70 m, at least one side other than road side, shall have clear open space of 9 m at ground level, accessible from road side.
However if the podium is proposed it shall not extend beyond 6m from building line and shall have clear open space of 9m at ground level OR if the podium is proposed it shall not extend beyond 6m from building line and shall have clear open space of 6 m beyond podium & 9m at ground level with clear height of 4.5 m from ground to podium (below soffit of the beam) for accessibility of fire appliances.
No ramps for the podium shall be provided in these side open spaces.
(B) For the proposals, other than (A) above
(a) Buildings having height more than 32 m upto 70 m, at least one side, accessible from road side, shall have clear open space of 9 m at ground level.
Provided, if the building abuts another road of 6 m or more and clear space of 9m at ground level is available including abutting road or building abuts another road of 9m then this condition shall not be insisted upon.
However, if the podium is proposed it shall not extend beyond 6m from building line and shall have clear open space of 9m at ground level OR if the podium is proposed it shall not extend beyond 6m from building line and shall have clear open space of 6m beyond podium & 9m at ground level with clear height of 4.5 m from ground to podium (below soffit of the beam) for accessibility of fire appliances.
No ramps for the podium shall be provided in these side open spaces.
PART – IX URBAN SAFETY REQUIREMENTS
(b) Buildings having height more than 70 m, at least two sides, accessible from road side, shall have clear open space of 9 m at ground level.
However, if the podium is proposed it shall not extend beyond 6 m from building line and shall have clear open space of 9 m at ground level OR if the podium is proposed it shall not extend beyond 6m from building line and shall have clear open space of 6 m beyond podium & 9m at ground level with clear height of 4.5 m from ground to podium (below soffit of the beam) for accessibility of fire appliances.
No ramps for the podium shall be provided in these side open spaces.
(c) Courtyard/ramp/podium accessible to fire fighting appliances (fire engines and other equipment) shall be capable of taking the load up to10 Kg/cm2.
(d) These open spaces shall be free from any obstruction & shall be motorable.
Note-The additional fire safety requirements shall be as per fire manual approved by Municipal Commissioner based on the Fire Act and Fire Protection Chapter of NBC amended time to time.