36. Occupancy Load
Space requirements of various parts of Buildings, etc.-This Part sets out the standard space requirements of various parts of a building and those of light and ventilation, the building services, fire safety, etc. Some of these items depend on the number of persons who would normally occupy the building, for which the occupant load should be worked out from Table No 13 hereunder:
Table No: 13
Occupant Load
| Serial No.(1) | Type of Occupancy(2) | Occupant load per 100 sq. m. of plinth or covered area(3) |
|---|---|---|
| 1 | Residential | 8 |
| 2 | Educational | 25 |
| 3 | Institutional | 6.6* |
| 4 | Assembly : (a)With fixed or loose seats and dance floor (b)without seating facilities including dining rooms | 166.6**66.6** |
| 5 | Mercantile : (a)Street floor and sales basement (b)Upper sales floors | 33.316.6 |
| 6 | Business and Industrial | 10 |
| 7 | Storage, Wholesale establishment | 3.3 |
| 8 | Hazardous | 10 |
*The occupant load in dormitory portions of homes for the aged, orphanages or mental hospitals, etc. where sleeping accommodation is provided shall be calculated at not less than 13.3 persons per 100 sq m.
** The plinth or covered area shall include, in addition to the main assembly room or space, any occupied connecting room or space in the same storey or in the storeys above or below, where entrance is common to such rooms and spaces and they are available for use by the occupants of the assembly place. No deductions shall be made in the plinth/covered area for corridors, closets and other sub-divisions; that area shall include all space serving the particular assembly occupancy.
37. Requirements of parts of buildings
(1) Plinth: The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured.
(i) Main Building: The height of the plinth shall not be less than 30 cm with respect to the surrounding ground level or plinth shall not be less than 15 cm with respect to the surrounding ground level in case
of stilt/covered parking spaces. In areas subject to flooding, the height of the plinth shall be at least 60 cm above the high flood level or shall be at least 45 cm above the high flood level in case of stilt/covered parking spaces. Architect on record shall certify that the plinth has been proposed after taking due cognizance of High Flood Level (HFL) with reference to available Contour map.
(ii)Interior court-yards, covered parking spaces and garages: These shall be raised at least 15cmabove the surrounding ground level and shall be satisfactorily drained.
(2) Habitable Rooms/Rooms:
(i) Size and Width: The minimum size and width shall be as given in the Table No 14 hereunder.