(i) The basement may be allowed to be constructed beyond building line in the required front open space under the provision of these regulations provided clear distance of 3.0 m between plot boundary/edge of road and basement line is maintained. The open spaces from the other boundaries of the plot except front open space shall not be less than 1.5 m. Basement may be at one level or more.
Provided further that if total depth of basements exceed beyond 8.4 m then the open spaces from the boundaries of the plot shall be increased by 1.5 m for every 8.4 m or fraction thereof beyond the open spaces as described above.
(ii) Height- The height of the basement from the floor to the underside of the roof-slab or ceiling or under side of a beam when the basement has a beam shall not be less than 2.4 m. The height of basement below soffit of the slab shall not be more than 3.9 m. In case of mechanical parking more height as per the requirement may be allowed.
(iii) Ventilation- The extent of ventilation shall be the same as required by the particular occupancy for which the basement is used. Any deficiency must be made good by resort to a mechanical system, viz. blowers, exhaust fans, air-conditioning system, according to the standards in Part VIII Building Services Section I-Lighting and Ventilation, NBC.
(iv)Uses permitted – A basement may be put to the following uses only:
(a)(i) Storage of household or other non-hazardous goods;
(ii) Store rooms, bank lockers or safe deposit vaults;
(b) Air conditioning equipment/AHU and other machines used for services and utilities of the building;
(c) Parking spaces;
(d) DG set, meter room and Electric substation (which will conform to specified safety requirements);
(e) Effluent Treatment Plant, suction tank, pump room, Water Treatment Plant, Sewerage Treatment Plant, Laundry Room, Boiler Room;
(f) MRI, Cancer Radiation Area, X-Ray rooms and other uses allowed by GoM. from time to time;
(g) Shops and offices, recording studio;
(h) Commercial user except kitchen with flame. (kitchen without flame may be permitted)
(i) Sanitary facility
(j)Play area for school if other ancillary uses have not been proposed at that level of basement.
Provided that the uses mentioned at (a), (g), (h) & (j) above shall be permitted in the 1st basement and the uses as mentioned in (f) above shall be permitted in lower basement only by counting in FSI subject to compliance of requirements of habitable rooms subject to following conditions:
i) All requirements regarding access, safety (including fire safety), ventilation, etc. shall be complied with.
ii) All the planning standards (particularly as regarding parking) should be strictly adhered to.
(v) Other Requirements-Every basement shall meet the following specifications:
(a) The ceiling of an upper basement shall be at least 0.6 m and not more than 1.2 m above the average surrounding ground level within the building line & may be flush with the average surrounding ground level beyond building line, Provided further that the height of basement above average surrounding ground level within building line may be reduced up to 0.15 m case of stilt and 0.30 m in case ground floor, when basement beyond building line is flush with average surrounding ground level, subject to provision of artificial light and ventilation.
(b)Adequate arrangements shall be made to ensure that surface drainage does not enter the basement.
(c)The walls and floors of the basement shall be water-tight and the effect of the surrounding soil and moisture, if any, should be taken into account in design and adequate damp-proofing treatment shall be given.
(d) Any access to the basement through a staircase or pedestrian ramp shall meet requirements of clause (16) of this Regulation. Open ramps may be permitted in the open spaces except in the front open space within plot boundary, subject to (b) above and the fire protection requirements.
(e)Any access to the basement through vehicular ramps shall meet the requirements of item, (ii)of clause (16) of this Regulation.
(8) Cabin: Where cabins are provided, a clear passage not less than 0.9 m wide will be maintained. The size of a cabin shall not be less than 3 sq. m and the distance from the farthest space of cabin to the nearest exit shall not be more than18.5 m. If the cabin does not derive direct light and ventilation from any open spaces/mechanical means, its maximum height shall be 2.2 m.
(9) Office Room: In every residential / non-residential building, constructed or proposed to be constructed for the use of a co-operative society or an apartment owners’/lessee’s association, an office room one for each society will be permitted on any floor or parking floors or stilt floor. In an already developed property, it may be on an upper floor. The area of the room inclusive of toilet shall be limited to 20 sq. m.
(10)(a) Letter Box Room: A separate letter box room of appropriate dimensions shall be provided on the ground floor /stilt floor/over podium or any other convenient location in residential, commercial and industrial occupancy in each wing.
(b)Letter Boxes- Letter boxes of appropriate dimensions shall be provided at a convenient location on the ground floor/stilt floor/over podium or any other convenient location for every unit of residential, commercial and industrial occupancy in each wing.
(11) Electric Meter/Service Utility Room: An independent and ventilated Electric meter/Service utility room directly accessible from the outside common areas shall be provided on ground floor and/or on upper floors/Podium/Parking floor and in the first basement floor with proper ventilation, according to the requirements of the electric supply undertaking. The door to the room shall have fire resistance of not less than two hours.
(12) Refuse Chute/Garbage Chute: In all residential buildings, refuse chutes/garbage chute may be provided with openings on each floor or on mid-landing. Design and specifications of refuse chutes shall be in accordance with provisions of IS 6924.
(13) Corridor: The minimum width of a common corridor shall be as shown in Table No 16 hereunder. Provided that any corridor identified as an exit (vide Regulations 47) shall also conform the requirements therein.
(14) Door: Doors shall conform to the under mentioned provisions. In addition, in order to satisfy firefighting requirements, any doorway identified as an exit shall conform to the requirements stipulated in Regulation 47,
(i) Width- A door shall be at least 0.9 m wide, except that doors to bathrooms, water-closets or stores may at least be 0.7 m wide.
(ii) Height-The minimum height of a doorway shall be 2 m.
(15) Stairway: Stairways shall conform to the following provisions in addition to items (i) to (ix) below. In addition, in order to satisfy fire-fighting requirements, any stairway identified as an exit stairway shall conform to the requirements stipulated in Regulation 47
(i) Width- The minimum width of a staircase other than a fire escape shall be as given in Table No 16 hereunder.