but the ratios of areas as maintained in the table for different occupancies and types of construction shall be adhered to.
Advantage has been taken of the developments, particularly in fire resistance rating of materials, designating types of construction in a rational manner and relating the area limitations of different occupancies to different types of construction.
Halons (halogenated hydrocarbons) which exhibit exceptional fire fighting and explosion prevention/suppression characteristics have been found to possess high ozone depleting potential. They come under Group II of Annex A of the Montreal Protocol on Substances that Deplete the Ozone Layer, the international environmental agreement for phasing out ozone depleting substances. Due to increasing evidence that the ozone layer is getting depleted at a faster rate than thought earlier, the developed countries accelerated their phase-out schedule with a view to achieving 100 percent phase-out of halons by 1 January 1994, instead of the earlier target date of 1 January 2000 after which only essential use of halon was allowed. For developing countries like India, the total phase-out of halons is to be achieved by 1 January 2010, as per Montreal Protocol, unless a decision is taken in between to hasten up the phase-out of ozone depleting substances. India, having become a signatory to the Protocol in June 1992, is committed to abide by the Montreal Protocol decisions. In accordance with Ministry of Environment and Forests, Government of India, Ozone Depleting Substances (Regulations), Rules, 2000, the manufacture of halon based fire extinguishers and extinguishing systems has been phased out by 1 January 2001. Meanwhile, the practical implications of the phasing out of the halons cover, by and large, the following aspects:
a) Availability of halons will be restricted;
b) Non-standard halon extinguishers, like aerosol type, shall not be permitted;
c) Discharge of halons for training/testing, etc shall not be permitted;
d) All efforts shall be made for avoiding/minimizing halon emissions at various levels such as production, fire equipment manufacture, use, service and maintenance;
e) Since ‘drop-in’ substitutes for halons are not likely to be available on a commercial scale in the near future, wherever possible, instead of halon, use of suitable alternative extinguishing media/methods will be resorted to, even accepting some trade-offs, if necessary; and
Halons shall be restricted for ‘essential uses’ only, for protection of critical fire explosion risk areas which would otherwise result in serious impairment of an essential service to society, or pose an unacceptable threat to life, the environment, or national security.
NOTE — Detailed instructions which will be issued by the Government of India from time-to-time for implementation of the Country Programme for the phasing out of ozone depleting substance (ODS) and regarding permitting use of halons for applications till the availability of proper substitutes, shall have to be complied with.
The first version of this Part was formulated in 1970 and first revision was brought out in 1983. Subsequently the first revision of this Part was modified in 1997 through Amendment No. 3 to 1983 version of the Code. This modified version of this part included few tables for the fire resistance ratings of various building components, such as walls, columns, beams and floors. The requirements for wet riser, down-comer, automatic sprinkler installation, high velocity (10-15 m/s) water spray or foam generating system, etc, for buildings were modified. Annex giving guidelines for selection of fire detectors had been deleted and relevant Indian Standards on fire alarm system and smoke detectors had been referred. Also, Annex for determination of fire loads and fire load density for arriving at the classification of occupancy hazard and calorific values of some common materials were included. Annex for broad classification of industrial and non-industrial occupancies into low, moderate and high hazard had also been included.
As a result of implementation of this Part, some useful suggestions have emerged. This revision has, therefore, been prepared to take care of the same. The significant modifications incorporated include:
a) The text has now been divided into the following broad clauses:
Fire Prevention — Covering aspects of fire prevention pertaining to design and construction of buildings on passive fire protection measures, also describing the various types of building materials and their fire rating.
Life Safety — Covering life safety provisions in the event of fire and similar emergencies, also addressing construction and occupancy features that are necessary to minimize danger to life from fire, smoke, fumes or panic.
Fire Protection — covering the significant appurtenances and their related components and guidelines for selecting the correct type of equipment and installation meant for fire protection of the building, depending upon the classification and type of the building.
b) The classification of building based on occupancy has been elaborated, with:
Starred hotels now covered as a new sub-division A-6 under occupancy Group A Residential.
Heritage structures and archeological monuments now covered under sub-division D-3 occupancy Group D Assembly buildings.
Mixed assembly occupancies now covered as a new sub-division D-6 and under ground elevated railways have been covered as a new sub-division D-7 under occupancy Group D Assembly buildings.
TV stations now covered under sub-division E-5 of occupancy Group E Business buildings.
c) The minimum capacity of smoke exhaust equipment has been increased to 12 air changes per hour.
d) For the external stairs for exit requirements, the width and treads have been increased to 1 250 mm and 250 mm respectively.
e) Under the requirements for institutional buildings the clear width of all required exits which serve as egress from hospital or infirmary section has been increased from 1.5 m to 2 m. Also, provision of patient-lift has been included.
f) Due cognizance of halon phase out programme has been taken, while specifying provisions in this Part with respect to fire protection using fire extinguishers/systems.
All standards cross-referred to in the main text of this section, are subject to the revision. The parties to agreement based on this Part are encouraged to investigate the possibility of applying the most recent editions of the standards.
1Scope
This Part covers the requirements for fire prevention, life safety in relation to fire and fire protection of buildings. The Code specifies construction, occupancy and protection features that are necessary to minimize danger to life and property from fire.
2Terminology
2.0 For the purpose of this Part, the following definitions shall apply.
2.1 Automatic Fire Detection and Alarm System — Fire alarm system comprising components for automatically detecting a fire, initiating an alarm of fire and initiating other actions as appropriate.
NOTE — The system may also include manual fire alarm call points.
2.2 Automatic Sprinkler System — A system of water pipes fitted with sprinkler heads at suitable intervals and heights and designed to actuate automatically, control and extinguish a fire by the discharge of water.
2.3 Building — Any structure for whatsoever purpose and of whatsoever materials constructed and every part thereof whether used as human habitation or not and includes foundation, plinth, walls, floors, roofs, chimneys, plumbing and building services, fixed platforms, VERANDAH, balcony, cornice or projection, part of a building or anything affixed thereto or any wall enclosing or intended to enclose any land or space and signs and outdoor display structures. Tents, SHAMIANAHS, tarpaulin shelters, etc, erected for temporary and ceremonial occasions with the permission of the Authority shall not be considered as building.
2.4 Building, Height of — The vertical distance measured in the case of flat roofs, from the average level of the ground around and contiguous to the building or as decided by the Authority to the terrace of the last livable floor of the building adjacent to the external wall; and in the case of pitched roofs, up to the point where the external surface of the outer wall intersects the finished surface of the sloping roof; and in the case of gables facing the road, the mid-point between the eaves level and the ridge. Architectural features serving no other function except that of decoration, shall be excluded for the purpose of measuring heights.
2.5 Combustible Material — The material which either burns itself or adds heat to a fire, when tested for non-combustibility in accordance with accepted standard [4(1)].
2.6 Covered Area — Ground area covered by the
building immediately above the plinth level. The area covered by the following in the open spaces is excluded from covered area (see Table 19):
a) garden, rockery, well and well structures, plant nursery, waterpool, swimming pool (if uncovered), platform round a tree, tank, fountain, bench, CHABUTARA with open top and unenclosed on sides by walls and the like;
b) drainage culvert, conduit, catch-pit, gully pit, chamber, gutter and the like;
c) compound wall, gate, unstoreyed porch and portico, slide, swing, uncovered staircases, ramp areas covered by CHHAJJA and the like; and
3Fire Prevention
3.1 Classification of Building Based on Occupancy
3.1.1 General Classification
All buildings, whether existing or hereafter erected shall be classified according to the use or the character of occupancy in one of the following groups:
Group A Residential
Group B Educational
Group C Institutional
Group D Assembly
Group E Business
Group F Mercantile
Group G Industrial
Group H Storage
Group J Hazardous
3.1.1.1 Minor occupancy incidental to operations in another type of occupancy shall be considered as part of the main occupancy and shall be classified under the relevant group for the main occupancy.
Examples of buildings in each group are given in 3.1.2 to 3.1.10.
3.1.2 Group A Residential Buildings
These shall include any building in which sleeping accommodation is provided for normal residential purposes with or without cooking or dining or both facilities, except any building classified under Group C.
Buildings and structures under Group A shall be further sub-divided as follows:
Sub-division A-1 Lodging or rooming houses
Sub-division A-2 One or two-family private dwellings
Sub-division A-3 Dormitories
Sub-division A-4 Apartment houses (flats)
Sub-division A-5 Hotels
Sub-division A-6 Hotels (Starred)
a) Sub-division A-1 Lodging or rooming houses — These shall include any building or group of buildings under the same management, in which separate sleeping accommodation for a total of not more than 40 persons (beds), on transient or permanent basis, with or without dining facilities but without cooking facilities for individuals is provided. This includes inns, clubs, motels and guest houses.
A lodging or rooming house shall be classified as a dwelling in sub-division A-2 if no room in any of its private dwelling units is rented to more than three persons.
b) Sub-division A-2 One or two-family private dwellings — These shall include any private dwelling which is occupied by members of one or two families and has a total sleeping accommodation for not more than 20 persons. If rooms in a private dwelling are rented to outsiders, these shall be for accommodating not more than three persons per room.
If sleeping accommodation for more than 20 persons is provided in any one residential building, it shall be classified as a building in sub-division A-1, A-3 or A-4 as the case may be.
3.2Fire Zones
3.2.1 Demarcation
The city or area under the jurisdiction of the Authority shall for the purpose of the Code, be demarcated into distinct zones, based on fire hazard inherent in the buildings and structures according to occupancy (see 3.1), which shall be called as ‘Fire Zones’.
3.2.2 Number and Designation of Fire Zones
3.2.2.1 The number of fire zones in a city or area under the jurisdiction of the Authority depends upon the existing layout, types of building construction (see 3.3), classification of existing buildings based on occupancy (see 3.1) and expected future development of the city or area. In large cities or areas, three fire zones may be necessary, while in smaller ones, one or two may be adequate.
3.2.2.2 The fire zones shall be made use of in land use development plan and shall be designated as follows:
a) Fire Zone No. 1 — This shall comprise areas having residential (Group A), educational (Group B), institutional (Group C), and assembly (Group D), small business (Subdivisions E-1) and retail mercantile (Group F) buildings, or areas which are under development for such occupancies.
b) Fire Zone No. 2 — This shall comprise business (Sub-divisions E-2 to E-5) and industrial buildings (Sub-division G-1 and G-2), except high hazard industrial buildings (Sub-division G-3) or areas which are under development for such occupancies.
c) Fire Zone No. 3 — This shall comprise areas having high hazard industrial buildings (Subdivision G-3), storage buildings (Group H) and buildings for hazardous used (Group J)
or areas which are under development for such occupancies.
3.2.3 Change in the Fire Zone Boundaries
When the boundaries of any fire zone are changed, or when it is intended to include other areas or types of occupancies in any fire zone, it shall be done by following the same procedure as for promulgating new rules or ordinances or both.
3.2.4 Overlapping Fire Zones
3.2.4.1 When any building is so situated that it extends to more than one fire zone, it shall be deemed to be in the fire zone in which the major portion of the building or structure is situated.
3.2.4.2 When any building is so situated that it extends equally to more than one fire zone, it shall be deemed to be in the fire zone having more hazardous occupancy buildings.
3.2.5 Temporary Buildings or Structures
3.3Types of Construction
3.3.1 General
The design of any building and the type of materials used in its construction are important factors in making the building resistant to a complete burn-out and in preventing the rapid spread of fire, smoke or fumes, which may otherwise contribute to the loss of lives and property.
The fire resistance of a building or its structural and non-structural elements is expressed in hours against a specified fire load which is expressed in kcal/m2, and against a certain intensity of fire. The fire-resistance test for structural element shall be done in accordance with good practice [4(5)]. For the purpose of the Code, the types of construction according to fire resistance shall be classified into four categories, namely,
Type 1 Construction, Type 2 Construction, Type 3 Construction and Type 4 ‘Construction’. The fire resistance ratings for various types of construction for structural and non-structural members shall be as given in Table 1.
For buildings 15 m in height or above non-combustible materials should be used for construction and the internal walls of staircase enclosures should be of brick work or reinforced concrete or any other material of construction with minimum of 2 h rating. The walls for the chimney shall be of Type 1 and Type 2 Construction depending on whether the gas temperature is above 200°C or less.
3.3.2 It is required that an element/component shall have the requisite fire resistance rating when tested in acco”rdance with the accepted standard [4(1)]. Tables 2 to 18 provide available data regarding fire resistance ratings of various building components such as walls, columns, beams and floors. Fire damage assessment, post fire structural safety assessment of various structural elements of the building and adequacy of the structural repairs can be done by the fire resistance ratings mentioned in Tables 2 to 18.
Table 1Fire Resistance Ratings of Structural and Non-Structural Elements (Hours) (Clause 3.3.1)
Sl No.
Structural Element
Type of Construction
Type 1(3)
Type 2(4)
Type 3(5)
Type 4(6)
(1)
(2)
3.4General Requirements of All Individual Occupancies
3.4.1 General
All buildings shall satisfy certain requirements which contribute, individually and collectively, to the safety of life from fire, smoke, fumes and panic arising from these or similar causes. There are, however, certain general principles and common requirements which are applicable to all or most of the occupancies.
3.4.2 Exceptions and Deviations
Exceptions and deviations to the general provisions of requirements of individual occupancies are given as applicable to each type of occupancy in 6.1 to 6.9. In case of practical difficulty or to avoid unnecessary hardship, without sacrificing reasonable safety, the Authority may grant exemptions from the Code.
3.4.3 Occupation of Buildings under Construction
3.4.3.1 A building or portion of the building may be occupied during construction, repairs, alterations or additions only if all means of exit and fire protection measures are in place and continuously maintained for the occupied part of the building.
3.4.3.2 A high rise building during construction shall be provided with the following fire protection measures, which shall be maintained in good working condition at all the times:
a) Dry riser of minimum 100 mm diameter pipe with hydrant outlets on the floors constructed with a fire service inlet to boost the water in the dry riser and maintenance should be as per the requirements laid down in good practice [4(6)].
b) Drums filled with water of 2 000 litres capacity with two fire buckets on each floor; and
c) A water storage tank of minimum 20 000 litres capacity, which may be used for other construction purposes also.
3.4.4 Maximum Height
Every building shall be restricted in its height above the ground level and the number of storeys, depending upon its occupancy and the type of construction. The height shall be measured as specified in Part 3 ‘Development Control Rules and General Building Requirements’. The maximum permissible height for any combination of occupancy and types of construction should necessarily be related to the width of street fronting the building, or floor area ratios and the local fire fighting facilities available.
3.4.5 Floor Area Ratio
4Life Safety
4.1 General
Every building shall be so constructed, equipped, maintained and operated as to avoid undue danger to the life and safety of the occupants from fire, smoke, fumes or panic during the time period necessary for escape.
4.2General Exit Requirements
4.2.1 An exit may be a doorway; corridor; passageway(s) to an internal staircase, or external staircase, or to a VERANDAH or terrace(s), which have access to the street, or to the roof of a building or a refuge area. An exit may also include a horizontal exit leading to an adjoining building at the same level.
4.2.2 Lifts and escalators shall not be considered as exits.
4.2.3 Every exit, exit access or exit discharge shall be continuously maintained free of all obstructions or impediments to full use in the case of fire or other emergency.
4.2.4 Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants, in case of fire or other emergency.
4.2.5 In every building or structure, exits shall comply with the minimum requirements of this part, except those not accessible for general public use.
4.2.6 No building shall be so altered as to reduce the number, width or protection of exits to less than that required.
4.2.7 Exits shall be clearly visible and the route to reach the exits shall be clearly marked and signs posted to guide the occupants of the floor concerned. Signs shall be illuminated and wired to an independent electrical circuit on an alternative source of supply. The sizes and colours of the exit signs shall be in accordance with good practice [4(16)]. The colour of the exit signs shall be green.
NOTE — This provision shall not apply to A-2 and A-4 occupancies less than 15 m in height.
4.2.8 The floors of areas covered for the means of exit shall be illuminated to values not less than 1 ft candle (10 lux) at floor level. In auditoriums, theatres, concert halls and such other places of assembly, the illumination of floor exit/access may be reduced during period of performances to values not less than 1/5 ft candle (2 lux).
4.2.9 Fire doors with 2 h fire resistance shall be provided at appropriate places along the escape route and particularly at the entrance to lift lobby and stair well where a ‘funnel or flue effect’ may be created, inducing an upward spread of fire to prevent spread of fire and smoke.
4.2.10 All exits shall provide continuous means of egress to the exterior of a building or to an exterior open space leading to a street.
4.2.11 Exits shall be so arranged that they may be reached without passing through another occupied unit.
4.3 Occupant Load
For determining the exits required, the number of persons within any floor area or the occupant load shall be based on the actual number of occupants, but in no case less than that specified in Table 20.
4.5Arrangement of Exits
4.5.1 Exits shall be so located that the travel distance on the floor shall not exceed the distance given in Table 22.
4.5.2 The travel distance to an exit from the dead end of a corridor shall not exceed half the distance specified
in Table 22, except in assembly and institutional occupancies in which case it shall not exceed 6 m.
4.5.3 Whenever more than one exit is required for any room space or floor of a building, exits shall be placed as remote from each other as possible and shall be arranged to provide direct access in separate directions from any point in the area served.
Table 22Travel Distance for Occupancy and Type of Construction (Clauses 4.4.1, 4.5.1 and 4.5.2)
Sl No.
Group of Occupancy
Maximum Travel Distance Construction
Types 1 & 2 m
Types 3 & 4 m
(1)
(2)
(3)
(4)
i)
Residential (A)
30.0
22.5
ii)
Educational (B)
30.0
22.5
iii)
Institutional (C)
30.0
22.5
iv)
Assembly (D)
30.0
30.0
v)
Business (E)
30.0
30.0
vi)
Mercantile (F)
30.0
30.0
vii)
Industrial (G)
45.0
¹⁾
viii)
Storage (H)
30.0
¹⁾
ix)
Hazardous (J)
22.5
¹⁾
NOTES
1 For fully sprinklered building, the travel distance may be increased by 50 percent of the values specified.
2 Ramps shall be protected with automatic sprinkler system and shall be counted as one of the means of escape. ¹⁾ Construction of type 3 or 4 is not permitted.
4.9Internal Staircases
4.9.1 Internal stairs shall be constructed of non-combustible materials throughout.
4.9.2 Internal stairs shall be constructed as a self-contained unit with an external wall of the building constituting at least one of its sides and shall be completely enclosed.
4.9.3 A staircase shall not be arranged round a lift shaft.
4.9.4 Hollow combustible construction shall not be permitted.
4.9.5 No gas piping or electrical panels shall be allowed in the stairway. Ducting in stairway may be permitted if it is of 1 h fire resistance rating.
4.9.6 Notwithstanding the detailed provision for exits in accordance with 4.3, 4.4 and 4.5, the following minimum width shall be provided for staircases:
a) Residential buildings (dwellings) 1.0 m
b) Residential hotel buildings 1.5 m
c) Assembly buildings like auditorium, 2.0 m theatres and cinemas
d) Educational buildings up to 30 m in 1.5 m height
e) Institutional buildings like hospitals 2.0 m
f) All other buildings 1.5 m
4.9.7 The minimum width of tread without nosing shall be 250 mm for internal staircase of residential buildings. This shall be 300 mm for assembly, hotels, educational, institutional, business and other buildings. The treads shall be constructed and maintained in a manner to prevent slipping.
4.9.8 The maximum height of riser shall be 190 mm for residential buildings and 150 mm for other buildings and the number shall be limited to 15 per flight.
4.9.9 Handrails shall be provided at a height of 1 000 mm to be measured from the base of the middle of the treads to the top of the handrails. Balusters/railing shall be provided such that the width of staircase does not reduce (see Fig. 1).
4.9.10 The number of people in between floor landings in staircase shall not be less than the population on each floor for the purpose of design of staircase. The design of staircase shall also take into account the following:
a) The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 m.
b) For building 15 m in height or more, access to main staircase shall be through a fire/smoke check door of a minimum 2 h fire resistance rating. Fire resistance rating may be reduced to 1 h for residential buildings (except hotels and starred hotels).
c) No living space, store or other fire risk shall open directly into the staircase or staircases.
d) External exit door of staircase enclosure at ground level shall open directly to the open spaces or through a large lobby, if necessary.
4.7Doorways
4.7.1 Every exit doorway shall open into an enclosed stairway or a horizontal exit of a corridor or passageway providing continuous and protected means of egress.
4.7.2 No exit doorway shall be less than 1 000 mm in width except assembly buildings where door width shall be not less than 2 000 mm. Doorways shall be not less than 2 000 mm in height.
4.7.3 Exit doorways shall open outwards, that is, away from the room, but shall not obstruct the travel along any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 900 mm; overhead or sliding doors shall not be installed.
NOTE — In the case of buildings where there is a central corridor, the doors of rooms shall open inwards to permit smooth flow of traffic in the corridor.
4.7.4 Exit door shall not open immediately upon a flight of stairs; a landing equal to at least the width of the door shall be provided in the stairway at each doorway; the level of landing shall be the same as that of the floor which it serves.
4.7.5 Exit doorways shall be openable from the side which they serve without the use of a key.
4.7.6 Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.
4.8 Corridors and Passageways
4.8.1 Exit corridors and passageways shall be of width not less than the aggregate required width of exit doorways leading from them in the direction of travel to the exterior.
4.8.2 Where stairways discharge through corridors and passageways, the height of corridors and passageways shall be not less than 2.4 m.
4.8.3 All means of exit including staircases lifts lobbies and corridors shall be adequately ventilated.
4.6Number of Exits
4.6.1 General
The general requirements of number of exits shall supplement the requirement of different occupancies in 6.1 to 6.9.
4.6.2 All buildings, which are 15 m in height or above, and all buildings used as educational, assembly, institutional, industrial, storage, and hazardous occupancies and mixed occupancies with any of the aforesaid occupancies, having area more than 500 m2 on each floor shall have a minimum of two staircases. They shall be of enclosed type; at least one of them shall be on external walls of buildings and shall open directly to the exterior, interior open space or to an open place of safety. Further, the provision or otherwise of alternative staircases shall be subject to the requirements of travel distance being complied with.
4.11External Stairs
An external staircase is desirable to be provided for high rise buildings.
External stairs, when provided shall comply the following:
4.11.1 External stairs shall always be kept in sound operable conditions.
4.11.2 All external stairs shall be directly connected to the ground.
4.11.3 Entrance to the external stairs shall be separate and remote from the internal staircase.
4.11.4 Care shall be taken to ensure that no wall opening or window opens on to or close to an external stairs.
4.11.5 The route to the external stairs shall be free of obstructions at all times.
4.11.6 The external stairs shall be constructed of non-combustible materials, and any doorway leading to it shall have the required fire resistance.
4.11.7 No external staircase, used as a fire escape, shall be inclined at an angle greater than 45° from the horizontal.
4.11.8 External stairs shall have straight flight not less than 1 250 mm wide with 250 mm treads and risers not more than 190 mm. The number of risers shall be limited to 15 per flight.
4.11.9 Handrails shall be of a height not less than 1 000 mm and not exceeding 1 200 mm. There shall be provisions of balusters with maximum gap of 150 mm.
4.11.10 The use of spiral staircase shall be limited to low occupant load and to a building not exceeding 9 m in height.
A spiral stair case shall be not less than 1 500 mm in diameter and shall be designed to give adequate headroom.
4.11.11 Unprotected steel frame staircase will not be accepted as means of escape. However, steel staircase in an enclosed fire rated compartment of 2 h will be accepted as means of escape.
4.12Horizontal Exits
4.12.1 The width of horizontal exit shall be same as for the exit doorways.
4.12.2 A horizontal exit shall be equipped with at least one fire/smoke door of minimum 1 h fire resistance, of self-closing type. Further, it is required to have direct connectivity to the fire escape staircase for evacuation.
4.12.3 For buildings more than 24 m in height, refuge area of 1 5 m 2 or an area equivalent to 0 . 3 m 2 per person to accommodate the occupants of two consecutive floors, whichever is higher, shall be provided as under:
The refuge area shall be provided on the periphery of the floor or preferably on a cantilever projection and open to air at least on one side protected with suitable railings.
a) For floors above 24 m and Up to 39 m — One refuge area on the floor immediately above 24 m.
b) For floors above 39 m — One refuge area on the floor immediately above 39 m and so on after every 15 m. Refuge area provided in excess of the requirements shall be counted towards FAR.
NOTE — Residential flats in multi-storied building with balcony, need not be provided with refuge area, however flats without balcony shall provide refuge area as given above.
4.12.4 Where there is a difference in level between connected areas for horizontal exits, ramps, not more than 1 in 10 m slope shall be provided; steps shall not be used.
4.12.5 Doors in horizontal exits shall be openable at all times from both sides.
4.15Fire Lifts
4.15.1 Where applicable, fire lifts shall be provided with a minimum capacity for 8 passengers and fully automated with emergency switch on ground level. In general, buildings 15 m in height or above shall be provided with fire lifts.
4.15.2 In case of fire, only fireman shall operate the fire lift. In normal course, it may be used by other persons.
4.15.3 Each fire lift shall be equipped with suitable inter-communication equipment for communicating with the control room on the ground floor of the building.
4.15.4 The number and location of fire lifts in a building shall be decided after taking into consideration various factors like building population, floor area, compartmentation, etc.
4.13Fire Tower
Fire towers are the preferred type of escape route for storeyed buildings and these shall be considered as the safest route for escape. Their number, location and size shall depend on the building concerned, and its associated escape routes.
4.13.1 In high rise buildings with over 8 storeys or 24 m in height, at least one required means of egress shall preferably be a fire tower.
4.13.2 The fire towers shall be constructed of walls with a 2 h fire resistance rating without openings other than the exit doorways, with platforms, landings and balconies having the same fire-resistance rating.
4.14 Ramps
4.14.1 Ramps shall comply with all the applicable requirements for stairways regarding enclosure,
capacity and limiting dimensions except where specified in 6.1 to 6.9 for special uses and occupancies.
4.14.2 The slope of a ramp shall not exceed 1 in 10. In certain cases steeper slopes may be permitted but in no case greater than 1 in 8.
4.14.3 For all slopes exceeding 1 in 10 and wherever the use is such as to involve danger of slipping, the ramp shall be surfaced with approved non-slipping material.
4.16Emergency and Escape Lighting
4.16.1 Emergency lighting shall be powered from a source independent of that supplying the normal lighting [see good practice [4 (17)].
Escape lighting shall be capable of:
a) Indicating clearly and unambiguously the escape routes,
b) Providing adequate illumination along such routes to allow safe movement of persons towards and through the exits,
c) Ensuring that fire alarm call points and firefighting equipments provided along the escape routes can be readily located.
4.16.2 The horizontal luminance at floor level on the centreline of an escape route shall be not less than 10 lux. In addition, for escape routes up to 2 m wide, 50 percent of the route width shall be lit to a minimum of 5 lux.
4.16.3 The emergency lighting shall be provided to be put on within 1 s of the failure of the normal lighting supply.
4.16.4 Escape lighting luminaries should be sited to cover the following locations:
a) Near each intersection of corridors,
b) at each exit door,
c) Near each change of direction in the escape route,
d) Near each staircase so that each flight of stairs receives direct light,
e) Near any other change of floor level,
f) Outside each final exit and close to it,
g) Near each fire alarm call point,
h) Near fire-fighting equipment, and
j) To illuminate exit and safety signs as required by the enforcing authority.
NOTE — For the purposes of this clause ‘near’ is normally considered to be within 2 m measured horizontally.
4.16.5 Emergency lighting systems shall be designed to ensure that a fault or failure in any one luminaire does not further reduce the effectiveness of the system.
4.16.6 The luminairies shall be mounted as low as possible, but at least 2 m above the floor level.
4.16.7 Signs are required at all exits, emergency exits and escape routes, which should comply with the graphic requirements of the relevant Indian Standards.
4.16.8 Emergency lighting luminaires and their fittings shall be of non-flammable type.
4.16.9 It is essential that the wiring and installation of the emergency lighting systems are of high quality so as to ensure their perfect serviceability at all times.
4.16.10 The emergency lighting system shall be capable of continuous operation for a minimum duration of 1 h and 30 m even for the smallest premises.
4.17Illumination of Means of Exit
Staircase and corridor lights shall conform to the following:
a) The staircase and corridor lighting shall be on separate circuits and shall be independently connected so that it could be operated by one switch installation on the ground floor easily accessible to fire fighting staff at any time irrespective of the position of the individual control of the light points, if any. It should be of miniature circuit breaker type of switch so as to avoid replacement of fuse in case of crisis;
b) Staircase and corridor lighting shall also be connected to alternative supply. The alternative source of supply may be provided by battery continuously trickle charged from the electric mains; and
c) Suitable arrangements shall be made by installing double throw switches to ensure that the lighting installed in the staircase and the corridor does not get connected to two sources of supply simultaneously. Double throw switch shall be installed in the service room for terminating the stand-by supply.
4.18Fire Detection and Warning
In buildings of such size, arrangement or occupancy where a fire may not itself provide adequate warning to occupants, automatic fire detection and alarm facilities shall be provided, where necessary, to warn occupants early of the existence of fire, so that they may escape, and to facilitate the orderly conduct of fire exit drills.
4.18.1 The fire detection system shall be in accordance with accepted standards [4(18)]. Guidelines for selection of various types of fire detectors for different occupancies and their installation and maintenance shall be in accordance with [4(19)].
4.18.2 The requirements of fire detection and alarm systems are covered for each occupancy in Table 23 and under 6.1 to 6.9; attention is also drawn to such requirements in case of high rise buildings (15 m or more in height) as given in Annex C.
5.2Fire Detection/Extinguishing System
In buildings of such size, arrangement or occupancy that a fire may not itself provide adequate warning to occupants, automatic fire detection and alarm facilities shall be provided, where necessary, to warn occupants early of the existence of fire, so that they may escape, or to facilitate the orderly conduct of fire exit drills.
5.2.1 The fire detection and extinguishing system shall be in accordance with accepted standards [4(18)]. Guidelines for selection of various types of fire detectors for different occupancies shall be in accordance with good practice [4 (19)]. Addressable analog fire detection system shall be preferred.
5.2.2 The requirements of fire detection and alarm systems are also covered for each occupancy in 6.1 to 6.9; and for high rise buildings (15 m or more in height) in Annex C.
5.3 Fire Extinguisher/Extinguishing System Using Halon Alternatives
Provisions for certain fire extinguishers and extinguishing systems for fire protection which may be used as halon alternatives, shall be in accordance in [4(25)].
5Fire Protection
5.1 Fire Extinguishers/Fixed Fire Fighting Installations
5.1.1 All buildings depending upon the occupancy use and height shall be protected by fire extinguishers, wet riser, down-comer, automatic sprinkler installation, high/medium velocity water spray, foam, gaseous or dry powder system in accordance with the provisions of 5.1.2 to 5.1.9.
5.1.2 These fire extinguishers/fixed installations shall be in accordance with accepted standards [4(20)]. The typical requirements of fire extinguishers/wet riser/ down-comer installation and capacity of water storage tanks and fire pumps, etc shall be as specified in Table 23. The requirements regarding size of mains/ risers shall be as given in Table 24. The typical arrangements of down-comer and wet riser installations are shown in Fig. 2 and Fig. 3. The wet riser shall be designed for zonal distribution ensuring that unduly high pressures are not developed in risers and hosepipes.
FIG. 2 TYPICAL ARRANGEMENT OF DOWN-COMER FOR BUILDING ABOVE 15 m BUT NOT EXCEEDING 30 m IN HEIGHT
FIG. 3 TYPICAL ARRANGEMENT OF WET RISER AND TOTAL SPRINKLER SYSTEM OF BUILDING OTHER THAN APPARTMENT EXCEEDING 30 m IN HEIGHT
(Clauses 4.18.2, 6.1.2, 6.2.3, 6.3.2, 6.4.3, 6.5.2, 6.5.2.1, 6.5.2.2, 6.5.2.3, 6.5.2.4, 6.5.2.5, 6.6.2, 6.7.2, 6.8.2 and 6.9.2) Minimum Requirements for Fire Fighting In
SI
Type of Building
Occupancy
Type of Installation
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
d) watchman’s booth, pumphouse, garbage shaft, electric cabin or sub-stations, and such other utility structures meant for the services of the building under consideration.
NOTE — For the purpose of this Part, covered area equals the plot area minus the area due for open spaces in the plot.
2.7 Down-comer — An arrangement of fire fighting within the building by means of down-comer pipe connected to terrace tank through terrace pump, gate valve and non-return valve and having mains not less than 100 mm internal diameter with landing valves on each floor/landing. It is also fitted with inlet connections at ground level for charging with water by pumping from fire service appliances and air release valve at roof level to release trapped air inside.
2.8 Dry Riser — An arrangement of fire fighting within the building by means of vertical rising mains not less than 100 mm internal diameter with landing valves on each floor/landing which is normally dry but is capable of being charged with water usually by pumping from fire service appliances.
2.9 Emergency Lighting — Lighting provided for use when the supply to the normal lighting fails.
2.10 Emergency Lighting System — A complete but discrete emergency lighting installation from the standby power source to the emergency lighting lamp(s), for example, self-contained emergency luminaire or a circuit from central battery generator connected through wiring to several escape luminaries.
2.11 Escape Lighting — That part of emergency lighting which is provided to ensure that the escape route is illuminated at all material times, for example, at all times when persons are on the premises, or at times the main lighting is not available, either for the whole building or for the escape routes.
2.12 Fire Door — A fire-resistive door approved for openings in fire separation.
2.13 Fire Exit — A way out leading to an escape route having panic bar hardware provided on the door.
2.14 Fire Lift — The lift installed to enable fire services personnel to reach different floors with minimum delay, having such features as required in accordance with this Part.
2.15 Fire Load — Calorific energy, of the whole contents contained in a space, including the facings of the walls, partitions, floors and ceilings.
2.16 Fire Load Density — Fire load divided by floor area.
2.17 Fire Resistance Rating — The time that a material or construction will withstand the standard fire exposure as determined by fire test done in accordance with the standard methods of fire tests of materials/structures.
2.18 Fire Resistance — Fire resistance is a property of an element of building construction and is the measure of its ability to satisfy for a stated period some or all of the following criteria:
a) resistance to collapse,
b) resistance to penetration of flame and hot gases, and
c) resistance to temperature rise on the unexposed face up to a maximum of 180°C and/or average temperature of 150°C.
2.19 Fire Separation — The distance in metres measured from the external wall of the building concerned to the external wall of any other building on the site, or from other site, or from the opposite side of street or other public space for the purpose of preventing the spread of fire.
2.20 Fire Separating Wall — The wall provides complete separation of one building from another or part of a building from another or part of a building from another part of the same building to prevent any communication of fire or heat transmission to wall itself which may cause or assist in the combustion of materials on the side opposite to that portion which may be on fire.
2.21 Fire Stop — A fire resistant material, or construction, having a fire resistance rating of not lesss than the fire separating elements, installed in concealed spaces or between structural elements of a building to prevent the spread/propagation of fire and smoke through walls, ceilings and like as per the laid down criteria.
2.22 Fire Tower — An enclosed staircase which can only be approached from the various floors through landings or lobbies separated from both the floor areas
and the staircase by fire-resisting doors, and open to the outer air.
2.23 Fire Resisting Wall — A fire resistance rated wall, having protected openings, which restricts the spread of fire and extends continuously from the foundation to at least 1 m above the roof.
2.24 Floor Area Ratio (FAR) — The quotient obtained by dividing the total covered area (plinth area) on all floors by the area of the plot:
FAR=Plot areaTotal covered area of all floors
2.25 High Rise Building — For the purpose of this Part, all buildings 15 m or above in height shall be considered as high rise buildings.
2.26 Horizontal Exit — An arrangement which allows alternative egress from a floor area to another floor at or near the same level in an adjoining building or an adjoining part of the same building with adequate fire separation.
2.27 Means of Egress — A continuous and unobstructed way of travel from any point in a building or structure to a place of comparative safety.
2.28 Occupancy or Use Group — The principal occupancy for which a building or a part of a building is used or intended to be used; for the purpose of classification of a building according to the occupancy, an occupancy shall be deemed to include subsidiary occupancies which are contingent upon it.
2.29 Plinth Area — The built-up covered area measured at the floor level of the basement or of any storey.
2.30 Pressurization — The establishment of a pressure difference across a barrier to protect a stairway, lobby, escape route or room of a building from smoke penetration.
2.31 Pressurization Level — The pressure difference between the pressurized space and the area served by the pressurized escape route, expressed in pascals (Pa).
2.32 Roof Exits — A means of escape on to the roof of a building, where the roof has access to it from the ground. The exit shall have adequate cut-off within the building from staircase below.
2.33 Site Plot — A parcel (piece) of land enclosed by definite boundaries.
2.34 Stack Pressure — Pressure difference caused by a temperature difference creating an air movement within a duct, chimney or enclosure.
2.35 Travel Distance — The distance to be travelled from any point in a building to a protected escape route, external escape route or final exit.
e)
2.36 Ventilation — Supply of outside air into, or the removal of inside air from an enclosed space.
2.37 Venting Fire — The process of inducing heat and smoke to leave a building as quickly as possible by such paths that lateral spread of fire and heat is checked, fire fighting operations are facilitated and minimum fire damage is caused.
2.38 Volume to Plot Area Ratio (VPR) — The ratio of volume of building measured in cubic metres to the area of the plot measured in square metres and expressed in metres.
2.39 Wet Riser — An arrangement for fire fighting within the building by means of vertical rising mains not less than 100 mm nominal diameter with landing valves on each floor/landing for fire fighting purposes and permanently charged with water from a pressurized supply.
NOTE — For definitions of other terms, reference shall be made to good practice [4(2)].
c) Sub-division A-3 Dormitories — These shall include any building in which group sleeping accommodation is provided, with or without dining facilities for persons who are not members of the same family, in one room or a series of closely associated rooms under joint occupancy and single management, for example, school and college dormitories, students, and other hostels and military barracks.
These shall include any building or structure in which living quarters are provided for three or more families, living independently of each other and with independent cooking facilities, for example, apartment houses, mansions and chawls.
Sub-division A-5 Hotels — These shall include any building or group of buildings under single management, in which sleeping accommodation is provided, with or without dining facilities for hotels classified up to 4 Star Category.
f) Sub-division A-6 Hotels (starred) — These shall include the hotels duly approved by the concerned authorities as Five Star and above Hotels.
3.1.3 Group B Educational Buildings
These shall include any building used for school, college, other training institutions for day-care purposes involving assembly for instruction, education or recreation for not less than 20 students.
Buildings and structures under Group B shall be further sub-divided as follows:
Sub-division B-1 Schools up to senior secondary level
Sub-division B-2 All others/training institutions
a) Sub-division B-1 Schools up to senior secondary level — This sub-division shall include any building or a group of buildings under single management which is used for students not less than 20 in number.
b) Sub-division B-2 All others/training institutions — This sub-division shall include any building or a group of buildings under single management which is used for students not less than 100 in number.
In the case of temporary buildings/structures which are utilized for educational purposes, the provisions of 3.2.5.3 shall apply.
If residential accommodation is provided in the schools/institutions, that portion of occupancy shall be classified as a building in sub-division A-3.
3.1.4 Group C Institutional Buildings
These shall include any building or part thereof, which is used for purposes, such as medical or other treatment or care of persons suffering from physical or mental illness, disease or infirmity; care of infants, convalescents or aged persons and for penal or correctional detention in which the liberty of the inmates is restricted. Institutional buildings ordinarily provide sleeping accommodation for the occupants.
Buildings and structures under Group C shall be further sub-divided as follows:
Sub-division C-1 Hospitals and sanatoria
Sub-division C-2 Custodial institutions
Sub-division C-3 Penal and mental institutions
a) Sub-division C-1 Hospitals and sanatoria — This sub-division shall include any building or a group of buildings under single management, which is used for housing persons suffering from physical limitations because of health or age, for example, hospitals, infirmaries, sanatoria and nursing homes.
b) Sub-division C-2 Custodial institutions — This sub-division shall include any building or a group of buildings under single management, which is used for the custody and care of persons, such as children, convalescents and the aged, for example, homes for the aged and infirm, convalescent homes and orphanages.
c) Sub-division C-3 Penal and mental institutions — This sub-division shall include any building or a group of buildings under single management, which is used for housing persons under restraint, or who are detained for penal or corrective purposes, in which the liberty of the inmates is restricted, for example, jails, prisons, mental hospitals, mental sanatoria and reformatories.
3.1.5 Group D Assembly Buildings
These shall include any building or part of a building, where number of persons not less than 50 congregate or gather for amusement, recreation, social, religious, patriotic, civil, travel and similar purposes, for example, theatres, motion picture houses, assembly halls, auditoria, exhibition halls, museums, skating rinks, gymnasiums, restaurants, places of worship, dance halls, club rooms, passenger stations and terminals of air, surface and marine public transportation services, recreation piers and stadia, etc.
Buildings under Group D shall be further sub-divided as follows:
Sub-division D-1 Buildings having a theatrical or motion picture or any other stage and fixed seats for over 1 000 persons
Sub-division D-2 Buildings having a theatrical or motion picture or any other stage and fixed seats upto 1 000 persons
Sub-division D-3 Buildings without a permanent stage having accommodation for 300 or more persons but no permanent seating arrangement.
Sub-division D-4 Buildings without a permanent stage having accommodation for less than 300 persons with no permanent seating arrangement.
Sub-division D-5 All other structures including temporary structures designed for assembly of people not covered by sub-divisions D-1 to D-4, at ground level.
Sub-division D-6 Buildings having mixed occupancies providing facilities such as shopping, cinema theatres, and restaurants.
Sub-division D-7 All other structures, elevated or underground, for assembly of people not covered by sub-divisions D-1 to D-6.
a) Sub-division D-1 — This sub-division shall
include any building primarily meant for theatrical or operatic performances and exhibitions and which has a raised stage, proscenium curtain, fixed or portable scenery or scenery loft, lights, motion picture houses, mechanical appliances or other theatrical accessories and equipment and which is provided with fixed seats for over 1 000 persons.
Sub-division D-2 — This sub-division shall include any building primarily meant for use as described for sub-division D-1, but with fixed seats up to 1 000 persons.
c) Sub-division D-3 — This sub-division shall include any building, its lobbies, rooms and other spaces connected thereto, primarily intended for assembly of people, but which has no theatrical stage or permanent theatrical and/or cinematographic accessories and has accommodation for 300 persons or more, for example, dance halls, night clubs, halls for incidental picture shows, dramatic, theatrical or educational presentation, lectures or other similar purposes having no theatrical stage except a raised platform and used without permanent seating arrangement; art galleries exhibition halls, community halls, marriage halls, places of worship, museums, lecture halls, passenger terminals and Heritage and Archeological Monuments.
d) Sub-division D-4 — This sub-division shall include any building primarily intended for use as described in sub-division D-3, but with accommodation for less than 300 persons with no permanent seating arrangements.
e) Sub-division D-5 — This sub-division shall include any building or structure permanent or temporary meant for assembly of people not covered by sub-divisions D-1 to D-4, for example, grandstands, stadia, amusement park structures, reviewing stands and circus tents.
f) Sub-division D-6 — This sub-division shall include any building for assembly of people provided with multiple services/facilities like shopping, cinema theatres and restaurants, for example, multiplexes.
g) Sub-division D-7 — This sub-division shall include any building or structure permanent or temporary meant for assembly of people not covered by D-1 to D-6, for example, underground or elevated railways.
3.1.6 Group E Business Buildings
These shall include any building or part of a building which is used for transaction of business (other than that covered by Group F and part of buildings covered
by 3.1.1.1); for keeping of accounts and records and similar purposes, professional establishments, service facilities, etc. City halls, town halls, court houses and libraries shall be classified in this group so far as the principal function of these is transaction of public business and keeping of books and records.
Business buildings shall be further sub-divided as follows:
Sub-division E-1 Offices, banks, professional establishments, like offices of architects, engineers, doctors, lawyers and police stations.
Sub-division E-2 Laboratories, research establishments, libraries and test houses.
Sub-division E-3 Computer installations.
Sub-division E-4 Telephone exchanges.
Sub-division E-5 Broadcasting stations and T.V. stations.
3.1.7 Group F Mercantile Buildings
These shall include any building or part of a building, which is used as shops, stores, market, for display and sale of merchandise, either wholesale or retail.
Mercantile buildings shall be further sub-divided as follows:
Sub-division F-1 Shops, stores, departmental stores markets with area up to 500 m2.
Sub-division F-2 Shops, stores, departmental stores markets with area more than 500 m2.
Sub-division F-3 Underground shopping centres. Storage and service facilities incidental to the sale of merchandise and located in the same building shall be included under this group.
3.1.8 Group G Industrial Buildings
These shall include any building or part of a building or structure, in which products or materials of all kinds and properties are fabricated, assembled, manufactured or processed, for example, assembly plants, industrial laboratories, dry cleaning plants, power plants, generating units, pumping stations, fumigation chambers, laundries, buildings or structures in gas plants, refineries, dairies and saw-mills, etc.
Buildings under Group G shall be further sub-divided as follows:
Sub-division G-1 Buildings used for low hazard industries.
Sub-division G-2 Buildings used for moderate hazard industries.
Sub-division G-3 Buildings used for high hazard industries.
The hazard of occupancy, for the purpose of the Code, shall be the relative danger of the start and spread of
fire, the danger of smoke or gases generated, the danger of explosion or other occurrences potentially endangering the lives and safety of the occupants of the buildings.
Hazard of occupancy shall be determined by the Authority on the basis of the fire loads of the contents, and the processes or operations conducted in the building, provided, however, that where the combustibility of the material, the flame spread rating of the interior finish or other features of the building or structure are such as to involve a hazard greater than the occupancy hazard, the greater degree of hazard shall govern the classification.
For determination of fire loads and fire load density for arriving at the classification of occupancy hazard, guidance including the calorific values of some common materials, is given at Annex A.
A broad classification of industrial and non-industrial occupancies into low, moderate and high hazard classes is given at Annex B, for guidance. Any occupancy not covered in Annex B, shall be classified in the most appropriate class depending on the degree of hazard.
Where different degrees of hazard of occupancy exist in different parts of a building, the most hazardous of those shall govern the classification for the purpose of this Code, except in cases where hazardous areas are segregated or protected as specified in the Code.
a) Sub-division G-1 — This sub-division shall include any building in which the contents are of such comparative low combustibility and the industrial processes or operations conducted therein are of such a nature that there are hardly any possibilities for any self propagating fire to occur and the only consequent danger to life and property may arise from panic, fumes or smoke, or fire from some external source.
b) Sub-division G-2 — This sub-division shall include any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with moderate rapidity or result in other hazardous situation and may give off a considerable volume of smoke, but from which neither toxic fumes nor explosions are to be feared in the event of fire.
c) Sub-division G-3 — This sub-division shall include any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with extreme rapidity or result in other hazardous situation or from which poisonous fumes or explosions are to be feared in the event of a fire. For fire safety in petroleum and fertilizer plant, good practice [4(3)] may be referred.
3.1.9 Group H Storage Buildings
These shall include any building or part of a building used primarily for the storage or sheltering (including servicing, processing or repairs incidental to storage) of goods, ware or merchandise (except those that involve highly combustible or explosive products or materials) vehicles or animals, for example, warehouses, cold storage, freight depots, transit sheds, storehouses, truck and marine terminals, garages, hangers, grain elevators, barns and stables. Storage properties are characterized by the presence of relatively small number of persons in proportion to the area. Any new use which increase the number of occupants to a figure comparable with other classes of occupancy shall change the classification of the building to that of the new use, for example, hangars used for assembly purposes, warehouses used for office purposes, garage buildings used for manufacturing.
3.1.10 Group J Hazardous Buildings
These shall include any building or part of a building which is used for the storage, handling, manufacture or processing of highly combustible or explosive materials or products which are liable to burn with extreme rapidity and or which may produce poisonous fumes or explosions for storage, handling, manufacturing or processing which involve highly corrosive, toxic or noxious alkalis, acids or other liquids or chemicals producing flame, fumes and explosive, poisonous, irritant or corrosive gases; and for the storage, handling or processing of any material producing explosive mixtures of dust which result in the division of matter into fine particles subject to spontaneous ignition. Examples of buildings in this class are those buildings which are used for:
a) Storage, under pressure of more than 0.1 N/mm2 and in quantities exceeding 70 m3, of acetylene, hydrogen, illuminating and natural gases, ammonia, chlorine, phosgene, sulphur dioxide, carbon dioxide, methyloxide and all gases subject to explosion, fume or toxic hazard, cryogenic gases, etc;
b) Storage and handling of hazardous and highly flammable liquids, liquefiable gases like LPG, rocket propellants, etc;
c) Storage and handling of hazardous and highly flammable or explosive materials (other than liquids); and
d) Manufacture of artificial flowers, synthetic leather, ammunition, explosives and fireworks. NOTE — A list of hazardous substances giving quantities, for which or exceeding which owners handling such substances are required to be covered under the Public Liability Insurance Act, has been notified under Government of India, Ministry of Environment and Forests Notification No. G.S.R. 347(E) dated 1 August 1996.
3.1.11 Any building not covered by Annex B or 3.1.8 shall be classified in the group which most nearly resembles its existing or proposed use.
3.1.12 Where change in the occupancy of any building places it in a different group or in a different subdivision of the same group, such building shall be made to comply with the requirements of the Code for the new group or its sub-division.
3.1.13 Where the new occupancy of a building is less hazardous, based on life and fire risk, than its existing occupancy, it shall not be necessary to conform to the requirements of the Code for the new group or its subdivision.
3.1.14 A certificate of occupancy shall be necessary, as required under Part 2 ‘Administration’, before any change is effected in the character of occupancy of any building.
3.2.5.1 Temporary buildings and structures shall be permitted only in Fire Zones No. 1 and 2 as the case may be, according to the purpose for which these are to be used, by special permit from the Authority for a limited period and subject to such conditions as may be imposed in the permit.
3.2.5.2 Such buildings and temporary structures shall be completely removed on the expiry of the period specified in the permit.
3.2.5.3 Adequate fire precautionary measures in the construction of temporary structures and PANDALS shall be taken in accordance with good practice [4(4)].
3.2.6 Restrictions on the Type of Construction for New Buildings
3.2.6.1 Buildings erected in Fire Zone No. 1 shall conform to construction of Type 1, 2, 3 or 4.
3.2.6.2 Buildings erected in Fire Zone No. 2 shall conform to construction of Type 1, 2 or 3.
3.2.6.3 Buildings erected in Fire Zone No. 3 shall conform to construction of Type 1 or 2.
3.2.7 Restrictions on Existing Buildings
The existing buildings in any fire zone shall not be required to comply with the requirement of the Code unless these are altered, or in the opinion of the Authority, such building constitutes a hazard to the safety of the adjacent property or the occupants of the building itself or is an unsafe building. In the event of alteration, it shall be necessary to obtain permission of the Authority for such alteration consistent with fire hazard (see Part 2 ‘Administration’).
Alterations/modifications/renovations shall be accomplished so as to ensure conformity with all the
safety requirements of the new buildings. Such alterations shall not in anyway bring down level of fire and life safety below that which existed earlier. Any addition or alterations or construction of cubicles or partitioning for floor area exceeding 500 m2 for all high rise buildings shall be with approval of local fire authority.
i) Exterior walls:
a) Fire separation less than 3.7 m
a) Bearing
4
2
2
1
b) Non-bearing
2
1(1)/(2)
1
1
b) Fire separation of 3.7 m or more but less than 9 m
a) Bearing
4
2
2
1
b) Non-bearing
1(1)/(2)
1
1
1
c) Fire separation of 9 m or more
a) Bearing
4
2
2
1
b) Non-bearing
1
1
1
1
ii) Fire resisting walls
4
2
2
2
iii) Fire separation assemblies (like fire check doors)
4
2
2
2
iv) Fire enclosures of exitways, hallways and stairways
2
2
2
2
v) Shaft other than exitways, elevator and hoistways
2
2
2
2
vi) Exitway access corridors
1
1
1
1
vii) Vertical separation of tenant spaces
1
1
1
1
viii) Dwelling unit separation
1
1
1
1
Non-load bearing partitions
— At least half an hour —
ix) Interior bearing walls, bearing partitions, columns, girders, trusses (other than roof trusses) and framing
a) Supporting more than one floor
4
2
2
2
b) Supporting one floor only
3
1(1)/(2)
1
1
c) Supporting a roof only
3
1(1)/(2)
1
1
x) Structural members support walls
3
1(1)/(2)
1
1
xi) Floor construction including walls
3
1(1)/(2)
1
1
xii) Roof construction
a) 5 m or less in height to lowest member
2
1(1)/(2)
1
1
b) More than 5 m but less than 6.7 m in height to lowest member
1
1
1
1
c) 6.7 m or more in height to lowest member
0
0
0
0
Table 2Masonry Walls: Solid (Required to Resist Fire from One Side at a Time) (Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm), Excluding any Finish for a Fire Resistance (Hours) of
Load Bearing
Non-load Bearing
1(3)
1(1)/(2) (4)
2(5)
3(6)
4(7)
1(8)
1(1)/(2) (9)
2(10)
3(11)
4(12)
i)
Reinforced ¹⁾ cement concrete
120 (25)²⁾
140 (25)²⁾
160 (25)²⁾
200 (25)²⁾
240 (25)²⁾
ii)
Unreinforced cement concrete
150
175
—
—
—
iii)
No-fines concrete with :
a) 13 mm cement/sand or gypsum/sand
—
—
—
—
—
150
150
150
150
150
b) 13 mm light weight aggregate gypsum plaster
—
—
—
—
—
150
150
150
150
150
iv)
Bricks of clay:
a) Without finish
90
100
100
170
170
75
90
100
170
170
b) With 13 mm lightweight aggregate gypsum plaster
90
90
90
100
100
75
90
90
90
100
v)
Bricks of sand lime:
a) Without finish
90
100
100
190
190
75
90
100
170
170
b) With 13 mm lightweight aggregate gypsum plaster
90
90
90
100
100
75
90
90
90
100
vi)
Blocks of concrete:
a) Without finish
90
100
100
—
—
75
90
100
140
150
b) With 13 mm lightweight aggregate gypsum plaster
90
90
90
100
100
75
75
75
90
100
c) With 13 mm cement/sand or gypsum/ sand
75
90
90
100
140
vii)
Blocks of lightweight concrete:
a) Without finish
90
100
100
140
150
75
75
75
125
140
b) With 13 mm lightweight aggregate gypsum plaster
90
90
90
100
100
50
63
75
75
75
c) With 13 mm cement/sand or gypsum/ sand
—
—
—
—
—
75
75
75
90
100
viii)
Blocks of aerated concrete:
a) Without finish
90
100
100
140
180
50
63
63
75
100
b) With 13 mm lightweight aggregate gypsum plaster
90
90
100
100
150
Walls containing at least 1 percent of vertical reinforcement.
Minimum thickness of actual cover to reinforcement.
Table 3Masonry Walls: Hollow (Required to Resist Fire from One Side at a Time) (Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Thickness (mm), Excluding any Finish for a Fire Resistance (Hours) of
Load Bearing
Non-load Bearing
1
1(1)/(2)
2
3
4
(1)/(2)
1
1(1)/(2)
2
3
4
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
i)
Bricks of clay:
a) Without finish
170
170
170
200
200
75
75
90
100
170
170
b) With 13 mm lightweight aggregate gypsum plaster
100
100
170
170
170
75
75
90
90
90
100
ii)
Blocks of concrete:
a) Without finish
90
125
125
140
140
150
b) With 13 mm cement/sand or gypsum/sand
190
200
200
—
—
90
125
125
140
140
140
c) With 13 mm lightweight aggregate gypsum plaster
75
90
90
100
125
125
iii)
Blocks of lightweight concrete:
a) Without finish
100
100
100
—
—
75
90
90
100
140
150
b) With 13 mm cement/sand or gypsum/sand
—
—
—
—
—
75
75
75
100
140
140
c) With 13 mm lightweight aggregate gypsum plaster
—
—
—
—
—
63
63
63
75
90
100
Table 4Framed Construction, Load Bearing (Required to Resist Fire from One Side at a Time) (Clause 3.3.2)
Sl Nature of Construction and Materials/Timber Studs at Centres not Minimum Thickness (mm) of Protection No. Exceeding 600 mm, Faced on Each Side with for a Fire Resistance of 1h(1) (2) (3)
i) Plasterboard layers with joints staggered, joints in outer layer taped and filled - Total 25 thickness for each face ii) One layer of 12.7 mm plasterboard with a finish of lightweight aggregate gypsum 13 plaster iii) Metal lath and plaster, thickness of plaster: a) Sanded gypsum plaster (metal lathing grade) 22 b) Lightweight aggregate gypsum plaster 13
Table 5 Framed Construction, Non-Load Bearing (Required to Resist Fire from One Side at a Time)
(Clause 3.3.2)
Nature of Construction and Materials/Steel or Timber Frame at Centres not Exceeding 600 mm, Facings on Both Sides of
Stud Construction
Minimum Thickness (mm) of Protection for a Fire Resistance
(1)/(2)h
1 h
1(1)/(2)h
2 h
(1)
(2)
(3)
(4)
(5)
(6)
A) Dry lining with materials fixed direct to studs (without plaster finish)
1. One layer of plasterboard with taped and filled joints
Timber or steel
12.7
2. Two layers of plasterboard with joints staggered, joints in outer layer taped and filled — Total thickness for each face
Timber or steel
19
25
3. One layer of asbestos insulating board with transverse joints backed by fillers of asbestos insulating board not less than 9 mm thick, or by timber
Timber or steel
9
12
4. One layer of wood wool slabs
Timber
25
5. One layer of chipboard or of plywood
Timber or steel
18
B) Lining with materials fixed direct to suds, with plaster finish:
Plasterboard of thickness:
Timber or steel
a) With not less than 5 mm gypsum plaster finish
9.5
b) With not less than 13 mm gypsum plaster finish
12.7
C) Wet finish:
Metal lath and plaster, thickness of plaster:
a) Sanded gypsum plaster
Timber or steel
13
b) Lightweight aggregate gypsum plaster
Timber
13
19
25
Steel
13
Table 6Framed External Walls Load Bearing (Required to Resist Fire from One Side at a Time)
Sl Nature of Construction and Materials Minimum Thickness (mm) of Protection No. for a Fire Resistance of 1 h(1) (2) (3)
Timber studs at centers not exceeding 600 mm with internal linings of : i) Plasterboard layers with joints in outer layer taped and filled, total thickness of 25 plasterboard
Table 7Framed External Walls Non-Load Bearing Required to Resist Fire only from Inside the Building (A) (Clause 3.3.2)
Nature of Construction and Materials
Mini ½ h
mum Th 1 h
ickness (Fire Re 1½ h
mm) of Pr sistance 2 h
otection 3 h
for a 4 h
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Steel frame with an external cladding of non-combustible sheets (excluding
sheet steel), with a steel supporting framework and internal lining of:
1. Metal lath and plaster, thickness of plaster:
a) Sanded gypsum plaster (metal lathing grade)
13
13
b) Lightweight aggregate gypsum plaster
10
13
15
15
15
19
2. Two layer of plasterboard with joints staggered joints in outer layer
21
32
taped and filled - Total thickness
3. Plasterboard of thickness:
a) With not less than 5 mm gypsum plaster finish
12.7
b) With not less than 13 mm gypsum plaster finish
9.5
c) With not less than 10 mm lightweight aggregate gypsum plaster
9.5
4. One layer of asbestos insulating board with transverse joints backed by
9
9
12
12
12
12
fillers of asbestos insulating board not less than 9 mm thick, or by timber
5. One layer of wood/wool slabs without finish
50
6. One layer of compressed straw building slabs:
a) Without finish
50
b) With not less than 5 mm gypsum plaster finish
50
7. Aerated concrete blocks
50
50
63
63
75
100
8. Bricks of clay:
a) Without finish
75
75
90
90
100
100
b) With not less than 13 mm lightweight aggregate gypsum plaster
75
75
90
90
Table 8Framed External Walls Non-Load Bearing Required to Resist Fire only from Inside the Building (B) (Clause 3.3.2)
N Naattuurree o off C Coonnssttrruuccttiioonn a anndd M Maatteerriiaallss
M Miinniimmuumm T Thhiicckknneessss ( (mmmm)) o off P Prrootteeccttiioonn t too P Prroovviiddee S Suuffffiicciieenntt I Innssuullaattiioonn t too A Acchhiieevvee a a M Mooddiiffiieedd F Fiirree R Reessiissttaannccee o off U Upp t too 4 4 h h
( (11))
( (22))
S Stteeeell f frraammee w wiitthh a ann e exxtteerrnnaall c cllaaddddiinngg o off s shheeeett s stteeeell f fuullllyy l laappppeedd,, s stteeeell b boolltteedd a anndd
f fiixxeedd t too s stteeeell s shheeeettiinngg r raaiillss,, w wiitthh t tiimmbbeerr o orr s stteeeell s suuppppoorrttiinngg f frraammeewwoorrkk a anndd i inntteerrnnaall
l liinniinngg o off::
1 1.. M Meettaall l laatthh a anndd p pllaasstteerr,, t thhiicckknneessss o off p pllaasstteerr::
a a)) S Saannddeedd g gyyppssuumm p pllaasstteerr ( (mmeettaall l laatthhiinngg g grraaddee))
1 133
b b)) L Liigghhttwweeiigghhtt a aggggrreeggaattee g gyyppssuumm p pllaasstteerr
1 100
2 2.. O Onnee l laayyeerr o off p pllaasstteerrbbooaarrdd w wiitthh j jooiinnttss t taappeedd a anndd f fiilllleedd
1 122..77
3 3.. P Pllaasstteerrbbooaarrdd o off t thhiicckknneessss w wiitthh n noott l leessss t thhaann 5 5 m mmm g gyyppssuumm p pllaasstteerr f fiinniisshh
9 9..55
4 4.. O Onnee l laayyeerr o off a assbbeessttooss i innssuullaattiinngg b booaarrdd w wiitthh t trraannssvveerrssee j jooiinnttss b baacckkeedd b byy
9 9
f fiilllleerrss o off a assbbeessttooss i innssuullaattiinngg b booaarrdd n noott l leessss t thhaann 9 9 m mmm t thhiicckk,, o orr b byy t tiimmbbeerr
5 5.. O Onnee l laayyeerr o off w woooodd//wwooooll s sllaabbss
2 255
6 6.. O Onnee l laayyeerr o off c coommpprreesssseedd s sttrraaww b buuiillddiinngg s sllaabbss
5 500
7 7.. O Onnee l laayyeerr o off c chhiippbbooaarrdd o orr o off p pllyywwoooodd
1 188
8 8.. A Aeerraatteedd c coonnccrreettee b blloocckkss
5 500
9 9.. B Brriicckkss o off c cllaayy
7 755
1 100.. A Annyy i inntteerrnnaall d deeccoorraattiivvee l liinniinngg w wiitthh a a c caavviittyy f fiillll i innddeeppeennddeennttllyy s suuppppoorrtteedd
5500
a anndd r reettaaiinneedd i inn p poossiittiioonn o off m miinneerraall f fiibbrree i innssuullaattiinngg m maatteerriiaall ( (eexxcclluuddiinngg
g <sub>g</sub>l<sub>l</sub>a<sub>a</sub>s<sub>s</sub>s<sub>s</sub>)) a att a a d deennssiittyy o off 4 488 k kgg//mm<sup>33</sup>
Table 9Framed Walls Non-Load Bearing Required to Resist Fire only from Inside the Building (C) (Clause 3.3.2)
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of 1½ h
(1)
(2)
Timber frame with external cladding of weather boarding or external plywood,
9.5 mm with an internal lining of:
1. Plasterboard not less than 9.5 mm thick, finished with:
a) Gypsum plaster
13
b) Lightweight aggregate gypsum plaster
10
2. Plasterboard not less than 12.7 mm thick, finished with:
a) Gypsum plaster
10
b) Lightweight aggregate gypsum plaster
10
3. One layer of asbestos insulating board with transverse joints backed by fillers
9
of asbestos insulating board not less than 9 mm thick, or by timber
12
Table 10 Reinforced Concrete Columns
(Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
(1)/(2)h
1 h
1(1)/(2)h
2 h
3 h
4 h
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Fully exposed
Width
150
200
250
300
400
450
Cover
40
40
40
40
40
40
ii)
50 percent exposed
Width
125
160
200
200
300
350
Cover
40
40
40
40
40
40
iii)
One face exposed
Thickness
100
120
140
160
200
240
Cover
40
40
40
40
40
40
Table 11 Concrete Beams
(Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
(1)/(2)h
1 h
1(1)/(2)h
2 h
3 h
4 h
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Reinforced concrete (simply supported)
Width
200
200
200
200
240
280
Cover
20
20
20
40
60¹⁾
70¹⁾
ii)
Reinforced concrete (continuous)
Width
200
200
200
200
240
280
Cover
20
20
20
30
40
50¹⁾
iii)
Prestressed concrete (simply supported)
Width
100
120
150
200
240
280
Cover
25
40
55
70
80
90
iv)
Prestressed concrete (continuous)
Width
80
100
120
150
200
240
Cover
20
30
40
55
70
80
Require attention to the additional measures necessary to reduce the risk of spalling.
Table 12 Concrete Floors(Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
(1)/(2)h (3)
1 h(4)
1(1)/(2)h (5)
2 h(6)
3 h(7)
4 h(8)
i)
Reinforced concrete (simply supported)
Thickness
75
95
110
125
150
170
Cover
20
20
25
35
45¹⁾
55¹⁾
ii)
Reinforced concrete (continuous)
Thickness
75
95
110
125
150
170
Cover
20
20
20
25
35
45¹⁾
Require attention to the additional measures necessary to reduce the risk of spalling.
Table 13Concrete Floors: Ribbed Open Soffit (Clause 3.3.2)
Sl No.
Nature of Construction and Materials
Minimum Dimensions (mm) Excluding any Finish, for a Fire Resistance of
(1)/(2)h
1 h
1(1)/(2)h
2 h
3 h
4 h
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i)
Reinforced concrete (simply supported)
Thickness of floor
75
95
110
125
150
170
Rib width
125
125
125
125
150
175
Cover
20
20
35
45
55
65
ii)
Reinforced concrete (continuous)
Thickness
75
95
110
125
150
170
Width
125
125
125
125
150
175
Cover
20
20
20
35
45
55
Table 14Encased Steel Columns, 203 mm × 203 mm (Protection Applied on Four Sides) (Clause 3.3.2)
Nature of Construction and Materials
Minimu 1 h
m Dimensio for a F 1½ h
ns (mm) E ire Resista 2 h
xcluding an nce of 3 h
y Finish, 4 h
(1)
(2)
(3)
(4)
(5)
(6)
A) Hollow protection (without an air cavity over the flanges):
1. <sup>1</sup>) Metal lathing with trowelled lightweight aggregate gypsum plaster
13
15
20
32
2. Plasterboard with 1.6 mm wire binding at 100 mm pitch, finished with
lightweight aggregate gypsum plaster not less than the thickness
specified:
a) 9.5 mm plaster board
10
15
b) 19 mm plaster board
10
13
20
3. Asbestos insulating boards, thickness of board:
a) Single thickness of board, with 6 mm cover fillets at transverse
19
25
joints
b) Two layers, of total thickness
38
50
4. Solid bricks of clay, composition or sand lime, reinforced in every
50
50
50
75
100
horizontal joint, unplastered
5. Aerated concrete blocks
60
60
60
6. Solid blocks of lightweight concrete hollow protection (with an air
50
50
50
60
75
cavity over the flanges)
B) Asbestos insulating board screwed to 25 mm asbestos battens
12
19
C) Solid protections
1. Concrete, not leaner than 1:2:4 mix (unplastered):
a) Concrete not assumed to be load bearing, reinforced <sup>2</sup>)
25
25
25
50
75
b) Concrete assumed to be load bearing
50
50
50
75
75
2. Lightweight concrete, not leaner than 1:2:4 mix (unplastered): concrete
25
25
25
40
60
not assumed to be load bearing, reinforced <sup>2</sup>)
So fixed or designed, as to allow full penetration for mechanical bond.
Reinforcement shall consist of steel binding wire not less than 2.3 mm in thickness, or a steel mesh weighing not less than 0.5 kg/m2. In concrete protection, the spacing of that reinforcement shall not exceed 200 mm in any direction.
Table 15Encased Steel Beams, 406 mm × 176 mm (Protection Applied on Three Sides) (Clause 3.3.2)
Nature of Construction and Materials(1)
Minimum Thickness (mm) of Protection for a Fire Resistance of
(1)/(2) h(2)
1h(3)
1(1)/(2) h(4)
2h(5)
3h(6)
4h(7)
A) Hollow protection (without an air cavity beneath the lower flange):
1. ¹ Metal lathing with trowelled lightweight aggregate gypsum plaster
13
13
15
20
25
2. Plasterboard with 1.6 mm wire binding ²⁾ at 100 mm pitch, finished with lightweight aggregate gypsum plaster not less than the thickness specified:
a) 9.5 mm plaster board
10
10
15
b) 19 mm plaster board
10
10
13
20
3. Asbestos insulating boards, thickness of board:
a) Single thickness of board, with 6 mm cover fillets at transverse joints
19
25
b) Two layers, of total thickness
38
50
B) Hollow protection (with an air cavity below the lower flange):
1. Asbestos insulating board screwed to 25 mm asbestos battens
9
12
C) Solid protection:
1. Concrete, not leaner than 1:2:4 mix (unplastered):
a) Concrete not assumed to be load bearing, reinforced ³
25
25
25
25
50
75
b) Concrete assumed to be load bearing
50
50
50
50
75
75
2. Lightweight concrete ⁴ , not leaner than 1:2:4 (mix) unplastered
25
25
25
25
40
60
Table 16Timber Floors — Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 21 mm Finished Thickness (Clause 3.3.2)
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
(1)/(2) h(2)
1h(3)
2h(4)
37 mm (minimum) timber joists with a ceiling of:
1. Timber lathing and plaster, plaster of thickness
15
2. Metal lathing and plaster, thickness of plaster:a) Sanded gypsum plaster (metal lathing grade)
15
b) Lightweight aggregate gypsum plaster
13
13
25
3. One layer of plasterboard with taped and filled joints
12.7
4. Two layers of plasterboard with joints staggered, joints in outer layertaped and filled total thickness
19
31
5. One layer of plasterboard not less than 9.5 mm thick, finished with:a) Gypsum plaster
5
b) Sanded gypsum plaster
13
c) Lightweight aggregate gypsum plaster
13
6. One layer of plasterboard not less than 12.7 mm thick, finished with:a) Gypsum plaster
5
b) Lightweight aggregate gypsum plaster
10
7. One layer of asbestos insulating board with any transverse jointsbacked by fillets of asbestos insulating board not less than 9 mmthick, or by timber
9
12
Table 17Timber Floors — Tongued and Grooved Boarding, or Sheets of Tongued and Grooved Plywood or Wood Chipboard, of not Less than 15 mm Finished Thickness (Clause 3.3.2)
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
11⁄2 h(2)
1 h(3)
2 h(4)
37 mm (minimum) timber joists with a ceiling of:
1. Timber lathing and plaster, plaster of thickness
15
2. Metal lathing and plaster, thickness of plaster for:
a) Sanded gypsum plaster (metal lathing grade)
15
b) Lightweight aggregate gypsum plaster
13
13
25
3. One layer of plasterboard with taped and filled joints
12.7
4. Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness
22
31
5. One layer of plasterboard not less than 9.5 mm thick, finish with:
a) Gypsum plaster
5
b) Sanded gypsum plaster
15
c) Lightweight aggregate gypsum plaster
13
6. One layer of plasterboard not less than 12.7 mm thick, finished with:
a) Gypsum plaster
5
b) Lightweight aggregate gypsum plaster
10
7. One layer of asbestos insulating board, with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber
9
12¹⁾
Finished on top with 25 mm minimum thick glass fibre or mineral wool laid between joints.
Table 18Timber Floors — Any Structurally Suitable Flooring of Timber or Lignocelluloses Boards (Clause 3.3.2)
Nature of Construction and Materials
Minimum Thickness (mm) of Protection for a Fire Resistance of
(1)
(1)/(2) h(2)
1h(3)
37 mm (minimum) timber joists with a ceiling of:
1. Timber lathing and plaster, plaster of thickness
15
2. Metal lathing and plaster, thickness of plaster for:
a) Sanded gypsum plaster (metal lathing grade)
15
b) Lightweight aggregate gypsum plaster
13
19
3. One layer of plasterboard with joints taped and filled and backed by timber
12.7
4. Two layers of plasterboard with joints staggered, joints in outer layer taped and filled total thickness
25
5. Two layers of plasterboard, each not less than 9.5 mm thick, joints between boards staggered and outer layer finished with gypsum plaster
5
6. One layer of plasterboard not less than 9.5 mm thick, finish with:
a) Sanded gypsum plaster
13
b) Lightweight aggregate gypsum plaster
15
7. One layer of plasterboard not less than 12.7 mm thick, finished with:
a) Sanded gypsum plaster
15
b) Lightweight aggregate gypsum plaster
13
8. One layer of asbestos insulating board with any transverse joints backed by fillets of asbestos insulating board not less than 9 mm thick, or by timber
12
3.3.3 Steel Construction
Load bearing steel beams and columns of buildings having total covered area of 500 m2 and above shall be protected against failure/collapse of structure in case
of fire. This could be achieved by use of appropriate methodology using suitable fire resistance rated materials alongwith suppression system {see Table 14, Table 15 and also accepted standard [4(5)]}.
The comparative floor area ratios for different occupancies and types of construction are given in
Table 19 (see also Part 3 ‘Development Control Rules and General Building Requirements’).
Table 19Comparative Floor Area Ratios for Occupancies Facing One Public Street Atleast 9 m Wide (Clauses 2.6 and 3.4.5)
Occupancy Classification(1)
Type of Construction
Type 1(2)
Type 2(3)
Type 3(4)
Type 4(5)
Residential
UL
2.0
1.4
1.0
Educational
UL
2.0
1.4
1.0
Institutional
UL
1.5
1.0
0.8
Assembly
UL
1.0
0.7
0.5
Business
UL
2.9
2.3
1.6
Mercantile
8.0
1.8
1.4
1.0
Industrial
7.5
1.9
1.6
1.3
Storage (see Note 5)
6.0
1.5
1.3
1.0
Hazardous (see Note 5)
2.8
1.1
0.9
NP
UL — Unlimited.
NP — Not permitted.
NOTES
1 The FAR values given in this table are subject to overall restrictions on the heights of buildings in the case of educational, institutional, assembly, storage and hazardous occupancies as specified in col 2 of Table 23.
2 This table has been prepared, taking into account the combustible content in the different occupancies as well as the fire resistance offered by the type of construction.
3 This table should be modified by the Authority, taking into account the other aspects as given below:
a) Density in terms of dwelling units per hectare;
b) Traffic considerations;
c) Parking spaces;
d) Local fire fighting facilities; and
e) Water supply, drainage and sanitation requirements.
4 The FAR values specified in this table may be increased by 20 percent for the following services:
a) A basement or cellar space under a building constructed on stilts and used as a parking space and airconditioning plant room used as accessory to the principal use;
b) Watchman’s booth, pumphouse, garbage shaft, electric cabin or sub-station and other utility structures meant for the services of the building under considerations;
c) Projections and accessory buildings as specifically exempted under the Code; and
d) Staircase room and lift rooms above the topmost storey; architectural feature; and chimneys and elevated tanks of dimensions as permissible under the Code; the area of the lift shaft shall be taken only on one floor.
5 In so far as single storey storage and hazardous occupancies are concerned, they would be further governed by volume to plot area ratio (VPR) to be decided by the Authority.
3.4.5.1 Each portion of a building, which is separated by one or more continuous fire resisting walls, having a fire resistance of not less than 2 h, extending from the foundation to 1 m above the roof at all points, may
be considered to be a separate building for the calculation of maximum permissible height and floor area, provided openings, if any, in the separating wall are also protected by fire assemblies of not less than 2 h.
3.4.6 Open Spaces
The open spaces around or inside a building shall conform to the requirements of Part 3 ‘Development Control Rules and General Building Requirements’.
3.4.6.1 For high rise buildings, the following additional provisions of means of access to the building shall be ensured (see Part 3 ‘Development Control Rules and General Building Requirements’):
a) The width of the main street on which the building abuts shall not be less than 12 m and one end of this street shall join another street not less than 12 m in width;
b) The road shall not terminate in a dead end; except in the case of residential building, up to a height of 30 m.
c) The compulsory open spaces around the building shall not be used for parking; and
d) Adequate passageway and clearances required for fire fighting vehicles to enter the premises shall be provided at the main entrance; the width of such entrance shall be not less than 4.5 m. If an arch or covered gate is constructed, it shall have a clear head-room of not less than 5 m.
3.4.7 Mixed Occupancy
When any building is used for more than one type of occupancy, then in so far as fire safety is concerned, it shall conform to the requirements for the occupancies of higher hazard. Unless the high hazard area is separated by separating walls of 4 h rating, the occupancies shall not be treated individually.
3.4.8 Openings in Separating Walls and Floors
At the time of designing openings in separating walls and floors, particular attention shall be paid to all such factors as will limit fire spread through these openings and maintain fire rating of the structural member.
3.4.8.1 For Types 1 to 3 construction, a doorway or opening in a separating wall on any floor shall be limited to 5.6 m2 in area with a maximum height/width of 2.75 m. Every wall opening shall be protected with fire-resisting doors having the fire rating of not less than 2 h in accordance with accepted standard [4 (7)]. All openings in the floors shall be protected by vertical enclosures extending above and below such openings, the walls of such enclosures having a fire resistance of not less than 2 h and all openings therein being
protected with a fire-resisting assembly as specified in 3.4.9.
3.4.8.2 For Type 4 construction, openings in the separating walls or floors shall be fitted with 2 h fireresisting assemblies.
3.4.8.3 Openings in walls or floors which are necessary to be provided to allow passages of all building services like cables, electrical wirings, telephone cables, plumbing pipes, etc, shall be protected by enclosure in the form of ducts/shafts having a fire resistance not less than 2 h. The inspection door for electrical shafts/ducts shall be not less than 2 h and for other services shafts/ducts, the same shall have fire resistance not less than 1 h. Medium and low voltage wiring running in shafts/ducts, shall either be armoured type or run through metal conduits. Further, the space between the conduits pipes and the walls/ slabs shall be filled in by a filler material having fire resistance rating of not less than 1 h.
NOTE — In the case of buildings where it is necessary to lower or lift heavy machinery or goods from one floor to the other, it may be necessary to provide larger openings in the floor. Such openings shall be provided with removable covers which shall have the same strength and fire resistance as the floor.
3.4.8.4 Vertical opening
Every vertical opening between the floors of a building shall be suitably enclosed or protected, as necessary, to provide the following:
a) Reasonable safety to the occupants while using the means of egress by preventing spread of fire, smoke, or fumes through vertical openings from floor to floor to allow occupants to complete their use of the means of egress. Further it shall be ensured to provide a clear height of 2 100 mm in the passage/escape path of the occupants.
b) Limitation of damage to the building and its contents.
3.4.9 Fire Stop or Enclosure of Openings
Where openings are permitted, they shall not exceed three-fourths the area of the wall in the case of an external wall and they shall be protected with fire resisting assemblies or enclosures having a fire resistance equal to that of the wall or floor in which these are situated. Such assemblies and enclosures shall also be capable of preventing the spread of smoke or fumes through the openings so as to facilitate the safe evacuation of building in case of a fire {see also accepted standard [4 (8)]}.
3.4.10 Electrical Installations
For requirements regarding electrical installations from the point of view of fire safety, reference may be made
to good practice [4(9)] (see also Part 8 ‘Building Services, Section 2 Electrical and Allied Installations’).
3.4.11 Air-conditioning and Ventilation
Air-conditioning and ventilation requirements of different rooms or areas in any occupancy shall be as given in Part 8 ‘Building Services, Section 1 Lighting and Ventilation and Section 3 Air-conditioning, Heating and Mechanical Ventilation’.
3.4.11.1 Air-conditioning and ventilating systems shall be so installed and maintained as to minimize the danger of spread of fire, smoke or fumes from one floor to other or from outside to any occupied building or structure (see C-1.17).
3.4.11.2 Air-conditioning and ventilating systems circulating air to more than one floor or fire area shall be provided with dampers designed to close automatically in case of fire and thereby preventing spread of fire or smoke and shall be in accordance with the accepted standard [4(10)]. Such a system shall also be provided with automatic controls to stop fans in case of fire, unless arranged to remove smoke from a fire, in which case these shall be designed to remain in operation.
3.4.11.3 Air-conditioning system serving large places of assembly (over 1 000 persons), large departmental stores or hotels with over 100 rooms in a single block shall be provided with effective means for preventing circulation of smoke through the system in the case of a fire in air filters or from other sources drawn into the system, and shall have smoke sensitive devices for actuation in accordance with the accepted standards [4(11)].
3.4.11.4 From fire safety point of view, separate air handling units for the various floors shall be provided so as to avoid the hazards arising from spread of fire and smoke through the air-conditioning ducts. The requirements of air-conditioning ducts shall be in accordance with good practice [4(12)].
3.4.11.5 For normal operation, air changes schedule shall be as given in Part 8 ‘Building Services, Section 3 Air-conditioning, Heating and Mechanical Ventilation’.
3.4.12 Smoke Venting
3.4.12.1 Smoke venting facilities for safe use of exits in windowless buildings, underground structures, large area factories, hotels and assembly buildings (including cinema halls) shall be automatic in action with manual controls in addition.
3.4.12.2 Natural draft smoke venting shall utilize roof vents or vents in walls at or near the ceiling level; such vents shall be normally open, or, if closed, shall be designed for automatic opening in case of fire, by release of smoke sensitive devices.
3.4.12.3 Where smoke venting facilities are installed for purposes of exit safety, these shall be adequate to prevent dangerous accumulation of smoke during the period of time necessary to evacuate the area served, using available exit facilities with a margin of safety to allow for unforeseen contingencies. It is recommended that smoke exhaust equipment should have a minimum capacity of 12 air changes per hour. Where mechanical venting is employed, it shall be firesafe.
3.4.12.4 The discharge apertures of all natural draft smoke vents shall be so arranged as to be readily accessible for opening by fire service personnel.
3.4.12.5 Power operated smoke exhausting systems shall be substituted for natural draft vents only by specific permission of the Authority.
3.4.13 Heating
Installation of chimney and heating apparatus shall be in accordance with good practice [4 (13)].
3.4.14 Additional Precautions
In addition to the factors covered by 3.4.2 to 3.4.12 there are certain aspects, applicable to particular occupancies only, which may effect the spread of fumes and thus the safe evacuation of the building in case of fire. Some such aspects are:
a) interior finish and decoration;
b) seating, aisles, railings, turnstiles and revolving doors in places of assembly;
c) service equipment and storage facilities in buildings other than storage buildings; and
d) hazards on stage, in waiting spaces, projection booths, etc, in theatres and cinemas.
3.4.15 Surface Interior Finishes
3.4.15.1 The use of combustible surface finishes on walls (including facade of the building) and ceilings affects the safety of the occupants of a building. Such finishes tend to spread the fire and even though the structural elements may be adequately fire resistant, serious danger to life may result. It is, therefore, essential to have adequate precautions to minimize spread of flame on wall, facade of building and ceiling surfaces.
The finishing materials used for various surfaces and décor shall be such that it shall not generate toxic smoke/fumes.
3.4.15.2 The susceptibility to fire of various types of wall surfaces is determined in terms of the rate of spread of flame. Based on the rate of spread of flame, surfacing material shall be considered as divided into four classes as follows {see also good practice [4(14)]}.
Class 1 Surfaces of very low flame spread.
Class 2 Surfaces of low flame spread.
Class 3 Surfaces of medium flame spread.
Class 4 Surfaces of rapid flame spread.
3.4.15.3 The uses for which surface materials falling into various classes shall be adopted in building construction are given below:
Class 1
Class 2
Class 3
May be used in any situation
May be used in any situation, except on walls, facade of the building, staircase and corridors
May be used only in living rooms and bed rooms (but not in rooms on the roof) and only as a lining to solid walls and partitions; not on staircases or corridors or facade of the building.
NOTE — Panelling (lining) shall be permitted in a limited area. It shall not be permitted in a vestibule.
3.4.15.4 Materials of Class 4 which include untreated wood fibreboards may be used with due fire retardant treatment as ceiling lining, provided the ceiling is at least, 2.4 m from the top surface of the floor below, and the wall surfaces conform to requirements of class [see Note under 3.4.15.3] Class 4 materials shall not be used in kitchens, corridors and staircases. Some materials contain bitumen and, in addition to risk from spread of fire, emit dense smoke on burning; such materials shall be excluded from use under these conditions and shall also not be used for construction of ceiling where the plenum is used for return air in air-conditioned buildings [see also 5.1.7(m)].
3.4.15.5 When frames, walls, partitions or floors are lined with combustible materials, the surfaces on both sides of the materials shall conform to the appropriate class, because there is considerable danger from fire starting and rapidly spreading within the concealed cavity unknown to the occupants whose escape may be hampered there by. For detailed information on materials and details of construction with their fireresistance rating, reference may be made to good practice [4(15)].
3.4.16 Glazing
3.4.16.1 Building of Types 1 to 4 construction shall employ one of the two types of glazing described in 3.4.16.2 and 3.4.16.3 except that Type 4 construction may have the alternative of hardwood sashes or frames or both.
3.4.16.2 Wired glass shall comply with the following requirements:
a) Wired glass — The wired glass shall be of minimum half hour fire resistance rating.
b) Sashes and frames — The sashes or frames or both shall be entirely of iron or other suitable metal such as stainless steel, securely bolted or keyed into the wall, except in the case of panels in internal doors.
c) Setting of glass — The panels of glass shall be set in rebates or grooves not less than 6.0 mm in width or depth, with due allowance for expansion, and shall be secured by hard metal fastenings to the sashes or frames independently of any cement or putty used for weather-proofing purposes.
3.4.16.3 Electro-copper glazing shall comply with the following requirements:
a) Electro-copper glazing — The electro-copper glazing shall be of minimum half hour fire resistance rating.
b) Sashes and frames — The sashes or frames or both shall be entirely of iron or other hard metal, securely bolted or keyed into the wall, except when in panels in internal doors.
c) Fixing of sectional lights — The sectional lights shall be set in rebate or grooves not less than 6.5 mm in width or depth, with due allowance for expansion and shall be secured by hard metal fastenings to the sashes or frames independently of any lead, cement or putty used for weather-proofing purposes.
3.4.16.4 Maximum permissible area shall be 5 m2 for protection by wired glass or electro-copper glazing.
3.4.16.5 Casement
Hard metal casements, not exceeding 0.8 m2 fitted with wired glass or electro-copper glazing in accordance with 3.4.16.2 and 3.4.16.3, secured to the frames by hard metal hinges not more than 600 mm apart and by fastening at top, centre and bottom shall be permissible.
3.4.17 Skylights
3.4.17.1 Wired glass for skylights or monitor lights shall comply with the following requirements:
a) Wired glass for skylights or monitor lights — The wired glass for skylights or monitor lights shall be of minimum half hour fire resistance rating.
b) Frames and glazing — The frame shall be continuous and divided by bars spaced at not more than 700 mm centres. The frame and bars shall be of iron or other hard metal, and supported on a curb either of metal or of wood covered with sheet metal. The toughened glass
shall be secured by hard metal fastenings to the frame and bars independently of any lead, cement or putty used for weather-proofing purposes.
3.4.18 Louvers
Louvers wherever provided shall be of minimum half hour fire resistance rating.
3.4.19 Glass of facade for high rise buildings, etc shall be of minimum 1 h fire resistance rating.
4.3.1 Mezzanine
The occupant load of a mezzanine floor discharging to a floor below shall be added to that floor occupancy and the capacity of the exits shall be designed for the total occupancy load thus established.
e) The main and external staircases shall be continuous from ground floor to the terrace level.
f) No electrical shafts/AC ducts or gas pipes, etc, shall pass through or open in the staircases. Lifts shall not open in staircase.
g) No combustible material shall be used for decoration/wall paneling in the staircase.
h) Beams/columns and other building features shall not reduce the head room/width of the staircase.
FIG. 1 TYPICAL DETAIL FOR HANDRAIL/BLUSTERS OF A STAIRCASE
j) The exit sign with arrow indicating the way to the escape route shall be provided at a suitable height from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs should be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipments. Further, all landings of floor shall have floor indicating boards prominently indicating the number of floor as per bye-laws.
The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5 m × 0.5 m.
k) Individual floors shall be prominently indicated on the wall facing the staircases.
m) In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. The second staircase may lead to basement levels provided the same is separate at ground level by ventilated lobby with discharge points to two different ends through enclosures.
4.10 Pressurization of Staircases (Protected Escape Routes)
4.10.1 Though in normal building design, compartmentation plays a vital part in limiting the spread of fire, smoke will readily spread to adjacent spaces through the various leakage openings in the compartment enclosure, such as cracks, openings around pipes ducts, airflow grills and doors, as perfect sealing of all these openings is not possible. It is smoke and toxic gases, rather than flame, that will initially obstruct the free movement of occupants of the building through the means of escape (escape routes). Hence the exclusion of smoke and toxic gases from the protected routes is of great importance.
4.10.2 Pressurization is a method adopted for protected escape routes against ingress of smoke, especially in high-rise buildings. In pressurization, air is injected into the staircases, lobbies or corridors, to raise their pressure slightly above the pressure in adjacent parts of the building. As a result, ingress of smoke or toxic gases into the escape routes will be prevented. The pressurization of staircases shall be adopted for high rise buildings and building having mixed occupancy/ multiplexes having covered area more than 500 m2.
4.10.3 The pressure difference for staircases shall be as under:
Building Height
Pressure Difference
Reduced Operation (Stage 1 of a 2-Stage System)
Emergency Operation (Stage 2 of a 2-Stage System or Single Stage System)
(Pa)
(Pa)
Less than 15 m
8
50
15 m or above
15
50
If possible, the same levels shall be used for lobbies and corridors, but levels slightly lower may be used for these spaces if desired. The difference in pressurization levels between staircase and lobbies (or corridors) shall not be greater than 5 Pa.
4.10.4 Pressurization system may be of two types:
a) Single-stage, designed for operation only in the event of an emergency, and
b) Two-stage, where normally a level of pressurization is maintained in the protected escape routes and an increased level of pressurization can be brought into operation in an emergency.
4.10.5 The normal air-conditioning system and the pressurization system shall be treated as an integral one, especially for a two-stage system. When the emergency pressurization is brought into action, the following changes in the normal air-conditioning system shall be effected:
a) Any re-circulation of air shall be stopped and all exhaust air vented to atmosphere;
b) Any air supply to the spaces/areas other than escape routes shall be stopped;
c) The exhaust system may be continued provided:
the positions of the extraction grills permit a general air flow away from the protected escape route entry;
the construction of the ductwork and fans is such that, it will not be rendered inoperable by hot gases and smoke; and
there is no danger of spread of smoke to other floors by the path of the extraction system which can be ensured by keeping the extraction fans running.
4.10.6 The pressurization system can be interconnected with the automatic/manual fire alarm system for actuation.
4.10.7 It will be desirable to have all the staircases in a building pressurized, if pressurization system is to
be resorted to. The use of pressurized and naturally ventilated staircases in the same building may introduce difficulties and hence shall be avoided. Under no circumstances shall a pressurized staircase be connected by a corridor or lobby to an un-pressurized staircase. Wherever pressurized staircase is to be connected to un-pressurized area, the two areas shall be segregated.
4.16.11 The emergency lighting system shall be well maintained by periodical inspections and tests so as to ensure their perfect serviceability at all times.
(14)
(15)
c) Dormitorises (A-3) Apartment Houses (A-4)
1) Less than 15 m in height
R
R
NR
NR
NR
NR
(see Note 2)
NR
NR
5 000 (5 000)(see Note 4)
NR
450 (450) (see Note 4)
2) 15 m and above but not exceeding 35 m in height
R
R
NR
NR
R
NR
(see Note 2)
NR
NR
25 000
NR
900
3) Above 35 m but not exceeding 45 m in height
R
R
NR
R
NR
NR
(see Notes 2 and 8)
NR
75 000 (5 000)(see Note 4)
5 000 (5 000)(see Note 19)
NR
4) Above 45 m in height but not exceeding 60 m in height
R
R
NR
R
NR
R
R
NR
75 000
10 000
(see Note 20)
NR
5) Above 60 m in height
R
R
NR
R
NR
R
R
R
100 000
25 000
(see Note 21)
NR
d) Hotels (A-5)
1) Less than 15 m in height
R
R
NR
NR
NR
NR
(see Note 2)
NR
NR
5 000 (see Note 2)
NR
450 (see Note 3)
ii) Covered area not exceeding 300 m2 on each floor but not more in each floor
R
R
NR
NR
NR
(see Note 2)
R
10 000 for every 500 m2 covered area subject to minimum of 50 000 (see Note 5)
10 000 (see Note 2)
NR (see Notes 5 and 19)
NR
iii) Covered area excepting 1 000 m2 on each floor
R
R
NR
(see Note 9)
10 000 (see Note 2)
(see Note 9)
100 000 (see Note 9)
NR
100 000 (see Note 2)
NR
450 (see Note 3)
Table 23Continued
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
2)
15 m and above but not exceeding 30 m
R
R
NR
R
NR
R
R(see Note 10)
R
R
150 000
20 000
(see Note 20)
NR
3)
Above 30 m in height
R
R
NR
R
NR
R
R(see Note 10)
R
R
200 000
20 000
(see Note 21)
NR
e)
Hotels (A-6)
R
R
NR
R
NR
R
R(see Note 10)
R
R
200 000
20 000
(see Note 22)
NR
EDUCATIONAL BUILDINGS (B) (see Note 12)
1)
Less than 15 m in height
i) Ground plus one storey
R
NR
NR
NR
NR
NR
R(see Note 2)
NR
NR
NR
5 000(see Note 3)
NR
450(see Note 3)
ii) Ground plus two or more storeys
R
R
NR
NR
NR
NR
R(see Note 2)
NR
NR
NR
10 000(5 000)(see Note 4)
NR
450(450)(see Note 4)
2)
15 m and above but not exceeding 30 m in height
R
R
NR
NR
R
NR
R(see Note 2)
R
NR
NR
25 000
NR
900
INSTITUTIONAL BUILDINGS (C) (see Note 12)
a)
Hospitals, Sanatoria and Nursing Homes (C-1)
1)
Less than 15 m in height with plot area up to 1000 m²
i) Up to ground plus one storey, with no beds
R
R
NR
NR
NR
NR
R(see Note 2)
R
NR
NR
2 500(2 500)(see Note 4)
NR
NR
ii) Up to ground plus one storey with beds
R
R
NR
NR
R
NR
R(see Note 2)
R
NR
NR
5 000(5 000)(see Note 4)
NR
450(450)(see Note 4)
iii) Ground plus two or more storeys, with no beds
R
R
NR
NR
R
NR
R(see Note 2)
R
R
NR
5 000(5 000)(see Note 4)
NR
450(450)(see Note 4)
iv) Ground plus two or more storeys, with beds
R
R
NR
R
NR
NR
R(see Note 2)
R
R
50 000
5 000(5 000)(see Note 4)
(see Note 19)
NR
Table 23Continued
1stole ZS — Continued
2) Less than 15 m in height with plot area more than 1 000 m²
R
R
NR
R
R
(see Note 2)
R
R
1 00 000
3) 15 m and above but not exceeding 24 m in height
R
R
NR
R
R
(see Note 11)
R
R
100 000
4) Above 24 m and not exceeding 30 m in height
R
R
NR
R
R
(see Note 11)
R
R
150 000
b) Custodial (C-2), and Renal and Pental (C-3)
I) Less than 10 m in height
(i) UP to 300 persons
R
R
NR
NR
NR
(see Note 2)
R
NR
10 000
(ii) More than 300 persons
R
R
NR
NR
R
(see Note 2)
R
NR
15 000
2) 10 m and above but not exceeding 15 m in height
R
R
NR
R
R
(see Note 2)
R
R
50 000
3) 15 m and above but not exceeding 24 m in height
R
R
NR
R
R
(see Note 11)
R
R
75 000
4) 24 m and above but not exceeding 30 m in height
R
R
NR
R
R
(see Note 11)
R
R
100 000
ASSEMBLY BUILDINGS (D) (see Note 12)
a) Buildings (D-1 to D-5)
I) Less than 10 m in height
(ii) UP to 300 persons
R
R
NR
R
R
(see Note 2)
R
NR
10 000
ASSEMBLY BUILDINGS (D) (see Note 12)
Table 23Continued
(in)
More than 300 persons
R
R
NR
NR
(RSE Note 2)
R
NR
NR
(RSE Note 2)
R
NR
NR
(RSE Note 4)
(see Note 4)
NR
450 (450)
Business Buildings (E)
Business Buildings (E)
(b)
Multiplex D-6
R
R
NR
R
NR
(RSE Note 10)
(RSE Note 10)
R
R
200 000
20 000
(see Note 22)
NR
Above 24 m but not exceeding 30 m in height
R
R
NR
R
NR
(RSE Note 10)
(RSE Note 10)
R
R
100 000
20 000
(see Note 21)
NR
Above 24 m but not exceeding 24 m in height
R
R
NR
R
NR
(RSE Note 11)
(RSE Note 11)
R
R
50 000
(see Note 20)
(see Note 4)
450 (450)
Above 15 m but not exceeding 15 m in height
R
R
NR
R
NR
(RSE Note 2)
(RSE Note 2)
R
R
10 000
(see Note 4)
(see Note 4)
450 (450)
Less than 10 m in height
R
R
NR
R
NR
(RSE Note 2)
(RSE Note 2)
R
NR
(see Note 4)
(see Note 4)
Above 15 m and up to above 15 m in height
R
R
NR
R
NR
(RSE Note 11)
(RSE Note 11)
R
R
75 000
10 000
(see Note 20)
NR
Above 24 m and up to above 24 m in height
R
R
NR
R
NR
(RSE Note 10)
(RSE Note 10)
R
R
200 000
20 000
(see Note 22)
NR
Above 30 m in height
R
R
NR
R
NR
(RSE Note 2)
(RSE Note 10)
R
R
200 000
20 000
(see Note 22)
NR
MERCANTIL E BUILININGS (E)
MERCAINTIL E BUILINGS (E)
a) F-1 & F-2 (see Note 12)
i) Ground plus one story, with total covered area not covering 500 m2
R
R
NR
NR
NR
(RSE Note 2)
(RSE Note 2)
NR
NR
5 000
(see Note 4)
NR
450 (450)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(ii) Ground plus one storey and covered area exceeding 500 m2
R
R
NR
NR
R
NR
(see Note 2)
R
NR
NR
25 000
NR
(iii) More than ground plus one storey
R
R
R
NR
R
NR
(see Note 2)
R
NR
5 000
(see Note 4)
900
2) Above 15 m but not exceeding 24 m in height
R
R
NR
R
NR
NR
(see Note 11)
R
R
100 000
10 000
(see Note 20)
3) Above 24 m but not exceeding 30 m in height
R
R
NR
R
NR
R
(see Note 10)
R
R
150 000
10 000
(see Note 21)
b) Underground shopping complex (F-3) (see Note 13)
R
R
NR
R
NR
R
(see Note 10)
R
R
150 000
10 000
(see Note 21)
a) Low Hazard (G-1) (see Note 15)
R
NR
NR
NR
NR
NR
(see Note 2)
NR
NR
5 000
(see Note 3)
450
(i) Built up area more than 100 m2 and up to 500 m2
R
R
NR
NR
NR
NR
(see Note 2)
NR
NR
5 000
(see Note 4)
450
(ii) Built up area more than 100 m2 and up to 500 m2
R
R
NR
NR
NR
NR
(see Note 7)
NR
NR
10 000
10 000
(see Note 20)
b) Moderate Hazard (G-2) (see Note 14)
(i) Built up area more than 100 m2 and up to 100 m2
R
R
NR
NR
NR
NR
(see Note 7)
NR
NR
10 000
NR
450
Table 23Continued
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
iii) Built up area more than 500 m² and up to 1 000 m²
Built up area more than 500 m² and up to 1 000 m²
R
R
NR
R
(see Note 7)
R
R
R
R
75 000
20 000
20 000
(see Note 20)
iv) Built up area more than 1 000 m²
Built up area more than 1 000 m²
R
R
NR
R
(see Note 7)
R
R
R
R
100 000
20 000
20 000
(see Note 20)
c) High Hazard (G-3) (see Note 16)
i) Built up area unp to 50 m²
Built up area unp to 50 m²
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
5 000
NR
NR
450
ii) Built up area more than 50 m² and up to 150 m²
Built up area more than 50 m² and up to 150 m²
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
5 000
NR
NR
450
iii) Built up area more than 150 m² and up to 300 m²
Built up area more than 150 m² and up to 300 m²
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
25 000
10 000
10 000
(see Note 19)
iv) Built up area more than 300 m² and up to 500 m²
Built up area more than 300 m² and up to 500 m²
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
50 000
20 000
20 000
(see Note 19)
v) Built up area more than 500 m²
Built up area more than 500 m²
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
100 000
20 000
20 000
(see Note 20)
I) Below 15 m in height and covered area less than 250 m²
Below 15 m in height and covered area less than 250 m²
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
25 000
5 000
5 000
(see Note 19)
2) Below 15 m in height and covered area more than 250 m²
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
50 000
10 000
10 000
(see Note 20)
i) Ground floor only
Ground floor only
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
75 000
10 000
10 000
(see Note 20)
ii) Ground plus one floor
R
R
NR
NR
(see Note 7)
NR
NR
NR
NR
50 000
10 000
10 000
(see Note 20)
4 1
Table 23Concluded
HAZARDOUS BUILDINGS (J) (see Note 17)
(i)
More than ground plus one floor
R
R
NR
R
R
NR
(10)
(9)
1) Up to 15 m in heightUp to 15 m in height
Single Story Building
R
R
NR
NR
R
NR
(8)
(7)
R
NR
NR
NR
R
NR
(6)
(5)
R
NR
NR
NR
R
NR
(4)
(3)
NOTES
1 Buildings above 15 m in height not to be permitted for occupancies A-1 and A-2.2 Required to be installed in basement if area of basement exceeds 200 m² .2 Required to be installed in basement if area of basement exceeds 200 m² .3 Required to be provided if basement area exceeds 200 m² .4 Additional value given in paranthesis shall be added if basement area exceeds 200 m² .5 Required to be provided for buildings with more than two storeys (Ground + One).6 As per the requirement of local authority Dry Riser may be used in hilly areas, industrial areas or as required.7 Required to be provided for buildings with height above 15 m.8 To be installed in basement. If basement provided is used for car parking and area thereof exceeds 750 m² then the sprinklers shall be fed water from both underground static water storage tank and terrace tank.9 Required to be provided for buildings with more than one storey.10 To be installed in entire building.11 To be installed in all floors at appropriate places and in consultation with local fire authorities.12 Buildings above 30 m in height not to be permitted for Group B, Group C, Group D and Group F occupancies.13 All underground shopping areas should be fully air-conditioned.14 The requirements given in this table for Group G Industrial Buildings are for small scale industry units. For other industries the requirements will have to be worked out on the basis of relevant IndianStandards and also in consultation with the local fire authorities.15 Buildings above 18 m in height not to be permitted for G-1 and G-2 occupancies.16 Buildings above 15 m in height not to be permitted for G-3 occupancies.17 Buildings above 15 m in height not to be permitted for Group H and Group J occupancies.
FIG. 4 TYPICAL SYSTEM OF PUMPING WITH ONE ELECTRIC AND ONE DIESEL FIRE PUMP
FIG. 5 TYPICAL SYSTEM OF PUMPING WITH TWO ELECTRIC, ONE DIESEL FIRE PUMP
5.1.3 In situations where one occupancy is provided with all the required fire protection arrangements but due to proximity of unprotected buildings around, causing exposure hazard to the protected building, the protected building walls facing the unprotected building shall be made of the requisite fire resistance rated materials or alternatively provided with water curtain/drencher system which can be actuated, when necessary.
5.1.4 First-aid fire fighting appliances shall be provided and installed in accordance with good practice [4(21)]. The fire fighting equipment and accessories to be installed in buildings for use in fire fighting shall be in accordance with the accepted standards contained in [4 (20)] and shall be maintained periodically so as to ensure their perfect serviceability at all times.
5.1.5 In addition to wet riser or down-comer, first-aid hose reels shall be installed on all the floors of buildings of 15 m in height or more and shall be in accordance with accepted standards [4(22)]. The first-aid hose reel shall be connected directly to the riser/down-comer main and diameter of the hose reel shall not be less than 19 mm.
5.1.6 Static Water Storage Tanks
A satisfactory supply of water for the purpose of fire fighting shall always be available in the form of underground/terrace level static storage tank with capacity specified for each building with arrangements or replenishment by mains of alternative source of supply at the rate of 1 000 l/min for underground static tank. When this is not practicable, the capacity of static storage tank(s) shall be increased proportionately in consultation with the local fire brigade.
The static storage water supply required for the above mentioned purpose shall entirely be accessible to the fire engines of the local fire service. Provision of suitable number of manholes shall be made available for inspection, repairs, insertion of suction hose, etc. The covering slab shall be able to withstand the total vehicular load of 45 T equally divided as a four point load when the slab forms a part of pathway/ driveway.
The domestic suction tank connected to the static water storage tank shall have an overflow capable of discharging 2 250 l/min to a visible drain point from which by a separate conduit, the overflow shall be conveyed to a storm water drain.
a) To prevent stagnation of water in the static water storage tank, the suction tank of the domestic water supply shall be fed only through an overflow arrangement to maintain the level therein at the minimum specified capacity (see Fig. 6).
b) The static water storage tank shall be provided with a fire brigade collecting head with 4 number 63 mm diameter (2 number 63 mm diameter for pump with capacity 1 400 l/min) instantaneous male inlets arranged in a valve box at a suitable point at street level and connected to the static tank by a suitable fixed pipe not less than 150 mm in diameter to discharge water into the tank when required at the rate of 2 250 l/min, if tank is in the basement or not approachable for the fire engines.
5.1.7 Automatic Sprinklers
Automatic sprinklers shall be installed in:
a) basements used as car parks or storage occupancy, if the area exceeds 200 m2;
b) multi-level basements, covered upper floors used as car parks, and for housing essential services ancillary to a particular occupancy or for storage occupancy, excluding any area to be used for sub-station, A.C. plant and DG set;
c) any room or other compartment of a building exceeding 1 125 m2 in area except as in (g) (see Note 1), if so advised by local authority;
d) departmental stores or shops, if the aggregate covered area exceeds 500 m2;
e) all non-domestic floors of mixed occupancy which constitute a hazard and are not provided with staircases independent of the remainder of the buildings;
f) godowns and warehouses, as considered necessary;
g) on all floors of the buildings other than residential and educational buildings, if the height of the building exceeds 15 m (45 m in case of group housing and apartments) (see Note 1);
h) dressing room, scenery docks, stages and stage basements of theatres;
j) in hotels, hospitals, industries low and moderate hazard mercantile buildings of height 15 m or above;
k) in hotels below 15 m, if covered area at each floor is more than 1 000 m2;
m) false ceiling voids exceeding 800 mm in height (see Note 2); and
n) canteen provided in upper floors of D-1 and D-2 occupancies shall be sprinklered.
1 It is desirable that all high rise buildings should be fully sprinklered irrespective of their height and occupancy. If
FIG. 6 TYPICAL ARRANGEMENT FOR PROVIDING COMBIND FIRE FIGHTING AND DOMESTIC WATER STORAGE TANK
Table 24Size of Rising Mains/Risers (Clause 5.1.2)
Size of the Mains(1)
Type of Building(2)
Height of Building(3)
100 mm as single outlet landing valves
1. Residential buildings (A)i) 1)Lodging or rooming housesii) Dormitoriesiii) One or two family private dwellingsiv) Apartment houses (flats)v) With shopping area not exceeding 500 m²vi) Hotels
15 m or above and not exceeding 45 mLess than 15 m15 m or above in height but not exceeding 30 m and area not exceeding 600 m² per floor
-do-
2. Educational buildings (B)
15 m or above but not exceeding 30 m
-do-
3. Institutional buildings (C)i) For hospitals and sanitoriumii) For custodial institutions and mental institutions
15 m or above but not exceeding 30 m15 m or above but not exceeding 30 m
-do-
4. Assembly buildings (D)
15 m or above but not exceeding 30 m and total floor area not exceeding 500 m²/floor (above 30 m, not to be permitted)
-do-
5. Business buildings (E)
15 m or above but not exceeding 30 m
-do-
6. Mercantile buildings (F)
15 m or above but not exceeding 30 m (above 30 m, not to be permitted)
-do-
7. Industrial buildings (G)
15 m or above but not exceeding 18 m
-do-
8. All buildings classified under 1 (i) to (iv)
Above 45 m
-do-
9. All buildings classified under 5 above with shopping area exceeding 500 m²
Above 15 m
-do-
10. All buildings classified under 1 (v) above
Above 30 m and area exceeding 500 m²
150 mm with twin outlet landing valves
11. Hotels
Above 30 m
-do-
12. All buildings classified under 2 and 3 above
Above 30 m
-do-
13. All buildings classified under 5 above
Above 30 m
-do-
14. All storage buildings (H)
Above 10 m but not exceeding 15 m
-do-
15. All Hazardous buildings (J)
Above 10 m but not exceeding 15 m
Buildings above 15 m in height not permitted in case of high hazard industrial buildings.
selective sprinklering is adopted, there is a real danger of a fire starting on one of the lower unsprinklered floors gathering momentum, spreading upwards from floor to floor through the unsprinklered floor and reaching the first sprinklered floor as a fully developed fire. In such an event, the sprinklers can be rendered useless or ineffective.
2 Use of false ceiling voids for storage or as return air plenums should be discouraged.
3 For areas having very high ceiling height and other special function areas, where automatic sprinklers cannot be provided, appropriate sprinklers/provisions shall be provided in consultation with local fire authorities.
5.1.8 Automatic High Velocity Water Spray or Emulsifying System
Automatic high velocity water spray or emulsifying system shall be provided for protection of indoor oil-
cooled transformers as applicable in accordance with C-1.16 and good practice [4(23)].
5.1.9 Fixed Foam Installation
Fixed foam generating system shall be provided for protection of oil storage area for boilers with its ancillary storage of furnace oils in basement. Fixed foam installations can be low, medium or high expansion types, which can cover fire risks in oil storage areas generally. High expansion foams are used for cable tunnels and other confined areas.
5.1.10 Carbon Dioxide Fire Extinguishing System
Fixed carbon dioxide fire extinguishing installation shall be provided in accordance with good practice
[4(24)] on premises where water or foam cannot be used for fire extinguishing because of the special nature of the contents of the buildings/areas to be protected. For some special fire risk/essential applications, carbon dioxide may not be suitable and it may be necessary to provide BCF (Bromochlorodifluoromethane) — Halon 1211 or BTM (Bromochlorotrifluoromethane) — Halon 1301 or some other identified substitutes.
However, the use of halons shall be discouraged, as halons are ozone depleting substances (ODS) and their use is being phased out throughout the world.
5.1.11 Fire fighting equipment shall be suitably located and clearly marked by luminous signs.
NOTE — This provision shall not apply to occupancies A-2 and A-4 less than 15 m in height.
6Additional Occupancy-wise Requirements
6.1 Requirements of Residential Buildings (Group A)
6.1.1 In addition to the general requirements for the type of construction and occupancy group specified in 3.4 and the exit requirements given in 4, the requirements 6.1.2 to 6.1.4.10 shall be complied with. The capacity of any open mezzanine or balcony shall be added to the capacity of the floor below for the purpose of determining exit capacity.
6.1.2 Fire Detection/Extinguishing System
The requirements for occupancy sub-divisions A-1 to
A-5 as specified in Table 23 and Annex C (for High Rise Buildings) shall apply.
6.1.3 Exit Facilities
The capacity of any open mezzanine or balcony shall be added to the capacity of the floor for the purpose of determining the exit capacity.
6.1.3.1 In addition to requirements specified for occupancy sub-division A-2, the following shall be provided for occupancy sub-division A-1:
Every sleeping room above the street floor shall have access to two separate means of exits, at least one of which shall consist of an enclosed interior stairway, or a fire escape or horizontal exit all so arranged as to provide a safe path of travel to the outside of the building without traversing any corridor or space exposed to an unprotected vertical opening.
6.1.3.2 For occupancy sub-division A-2 of more than two rooms, every occupied room, excluding areas used solely for storage shall have at least two means of exits, at least one of which shall be a door or a stairway providing a means of un-obstructed travel to the outside of the building or street or grade level. No room or space shall be occupied which is accessible only by a ladder, folding stairs or through a trap door.
Further the following provisions shall be made:
All locking devices, which would impede or prohibit exit, such as chain type bolts, limited opening sliding type locks and burglar locks, which are not dis-engaged easily by quickreleasing catches, shall be prohibited. All closet door latches shall be such that even children can open the doors from inside. All bathroom door locks or fasteners shall be designed to permit the opening of the locked or closed door from the outside in an emergency without the use of a special key.
6.1.3.3 For occupancy sub-division A-3, the following provisions shall apply:
All dormitories shall have exits so arranged that from any sleeping room or open dormitory sleeping area, there shall be access to two separate and distinct exits in different directions with no common path of travel unless the room or space is subject to occupancy by not more than 10 persons and has a door opening directly to the outside of the building at street or grade level, or to an outside stairway in which case one means of exit may be accepted.
6.1.3.4 For occupancy sub-division A-4, the following provisions shall apply:
a) Every individual living unit covered by occupancy sub-division A-4 shall comply with the requirement for occupancy subdivision A-2 in respect of exits.
b) Every living unit shall have access to at least two separate exits, which are remote from each other and are reached by travel in different directions, except that a common path of travel may be permitted for the first 6 m (that is a dead end corridor up to 6 m long may be permitted) provided that single exit may be permitted under any of the conditions given under (c).
c) Any part of building lower than the grade level shall have direct accessibility from outside.
d) At least half of required exits shall discharge direct to the outside of the buildings; any other exit shall be the same as required for hotels.
6.1.3.5 For occupancy sub-divisions A-5 and A-6, the following provisions shall apply:
a) Not less than two exits, as remote from each other as practicable, shall be accessible from every floor, including basements occupied for hotel purpose, except as a single exit as permitted in (b) below. Exits and ways of access thereto shall be so arranged that they are accessible in at least two different directions from every point in any open area, or from any room door.
b) Any room or section with an outside door at street or grade level may have such outside door as a single exit, provided no part of the room or area is more than 15 m from the door measured along the natural path of travel.
c) Provision of panic bars shall be provided in the exits.
6.1.3.5.1 Where stairways or other exits serve two or more upper floors, the same stairway or other exit required to serve any one upper floor may also serve other upper floors, except that no inside open stairway or ramp may serve as a required egress facility from more than one floor [see good practice 4(26)].
6.1.3.6 Basement Exits
a) Basements occupied for hotel purposes shall have exits arranged in accordance with 6.1.3.5.
b) Basement exits shall be sufficient to provide for the capacity of the basement as determined in accordance with 6.1.1. In no case shall there be less than two independent basement exits.
c) Basement or sub-basements not open to the public and used only for heating equipment,
storage and service operations (other than kitchens, which are considered part of the hotel occupancy) shall have exits appropriate to the actual occupancy, in accordance with other applicable provisions of the Code, or in case of mixed occupancy where there may be doubt as to which other section is applicable, such basements shall have exits determined on the basis of lesser exit capacity.
6.1.4 Additional Precautions
6.1.4.1 Flammable liquids for household purposes shall be kept in tightly stoppered or sealed containers. For the limits of quantities of flammable liquids to be allowed in various occupancies, reference may be made to appropriate regulations.
6.1.4.2 No stove or combustion heater shall be located directly under or immediately at the foot of stairs or otherwise so located as to block escape in case of malfunctioning of the stove or heater.
6.1.4.3 All kitchen exhaust fans, where provided, shall be fixed to an outside wall or to a duct of non-combustible material, which leads directly to the outside. The ducts must not pass through areas having combustible materials.
6.1.4.4 All wiring shall be done in accordance with Part 8 ‘Building Services, Section 2 Electrical Installations’, good practice [4(10)] and National Electric Code.
6.1.4.5 Where television is installed, all outdoor antennae shall be properly grounded and protected from lightning (see Part 8 ‘Building Services, Section 2 Electrical Installations’).
6.1.4.6 Doors leading to rooms in which flammable liquids are stored or used shall be as in 4.7. Such assembly shall be self-closing and shall be posted with a sign on each side of the door in 25 mm high block letters stating — ‘FIREDOOR — KEEP CLOSED’.
6.1.4.7 Where a boiler room is provided or a central heating plant is installed, which uses solid or liquid fuel, it shall be separated from rest of the building by a separation wall with all openings protected as in 3.4.7 and 3.4.8.
6.1.4.8 Rooms containing high pressure boilers, refrigerating machinery, transformers or other service equipment subject to possible explosion shall not be located directly under or adjacent to exits. All such rooms shall be effectively cut off from other parts of the building and shall be provided with adequate vents to the outside air.
6.1.4.9 All rooms or areas of high hazard in additions to those herein before mentioned, shall be segregated
or shall be protected as may be directed by the enforcing Authority where, in the opinion of the enforcing Authority, fire, explosion or smoke there from is likely to interfere with safe egress from the building.
6.1.4.10 For detailed information regarding fire safety requirements for hazardous petroleum products, reference may be made to the Petroleum Act, 1934 and the Rules thereof.
6.2Requirements of Educational Buildings (Group B)
6.2.1 In addition to the general requirements specified in 3.4 for the type of construction and occupancy group and the exit requirements given in 4, the requirements given in 6.2.2 to 6.2.6.3 shall be complied with.
6.2.2 Buildings intended for educational occupancy shall not be used for any hazardous occupancy.
6.2.3 Fire Detection/Extinguishing System
The requirements for occupancy sub-divisions B-1 and B-2 as specified in Table 23 and Annex C (for High Rise Buildings) shall apply.
6.2.4 Exit Facilities
The capacity of any open mezzanine or balcony shall be added to the capacity of the floor for the purpose of determining the exit capacity.
In addition to the provisions in 4, the following shall be provided:
6.2.4.1 Exits, in accordance with 4 shall be so arranged that at least two separate exits are available in every floor area. Exits shall be as remote from each other as practicable and so arranged that there are no pockets or dead ends of appreciable size in which occupants may be trapped.
6.2.4.2 Every room with a capacity of over 45 persons in area shall have at least two doorways.
6.2.4.3 Exterior doors shall be operated by panic bars or some other panic hardware device, except that doors leading from classrooms directly to the outside may be equipped with the same type of lock as is used on classroom doors leading to corridor, with no provision whatsoever for locking against egress from the classroom.
6.2.5 Additional Precautions
6.2.5.1 Storage of volatile flammable liquids shall be prohibited and the handling of such liquids shall be restricted to science laboratories only.
6.2.5.2 Each building shall be provided with an approved outside gas shut-off valve conspicuously
marked. The detailed requirements regarding safe use of gas shall be as specified in Part 9 ‘Plumbing Services, Section 3 Gas Supply’.
6.2.5.3 All exterior openings in a boiler room or rooms containing central heating equipment, if located below opening in another storey or if less than 3 m from other doors or windows of the same building, shall be protected by a fire assembly as in 3.4.8. Such assemblies shall be fixed, automatic or self-closing. Provisions of 6.1.4.7 shall also apply to this group of occupancy.
6.2.6 Exception and Deviation
6.2.6.1 Gymnasiums, indoor stadiums and similar occupancies may have floors/running tracks of wood, cinder, synthetic or unprotected steel or iron.
6.2.6.2 In gymnasiums and in multi-purpose school rooms having an area not greater than 300 m2, 25 mm nominal tight tongue-and-grooved or 20 mm plywood wall covering may be used in the inner side in lieu of fire-resistant plaster.
6.2.6.3 A building, which will have only the first floor and is accessible to not more than 20 pupils at any time, may be used for school purposes with the following exceptions:
a) Exterior walls or parts of walls which are less than 900 mm from adjacent property lines shall have no openings therein.
b) Classrooms may have only one exit not less than 900 mm wide.
6.3Requirements of Institutional Buildings (Group C)
6.3.1 In addition to the general requirements specified in 3.4 for the type of construction and occupancy group and the exit requirements given in 4, the requirements given in 6.3.2 to 6.3.5 shall be complied with.
6.3.2 Fire Detection/Extinguishing System
The requirements for occupancy sub-divisions as specified in Table 23 and Annex C (for High Rise Buildings) shall apply.
6.3.3 Exit Facilities
In addition to the provisions of 4, the following requirements shall be complied with.
6.3.3.1 In buildings or sections occupied by bedridden patients where the floor area is over 280 m2, facilities shall be provided to move patients in hospital beds to the other side of a smoke barrier from any part of such building or section not directly served by approved horizontal exits or exits from the first floor (floor 2) of a building to the outside.
6.3.3.2 Not less than two exits of one or more of the following types shall be provided for every floor, including basement, of every building or section:
a) Doors leading directly outside the building;
b) Stairways;
c) Ramps;
d) Horizontal exits; and
e) Fire tower.
6.3.3.3 All required exits that serve as egress from hospital or infirmary sections shall be not less than 2 m in clear width including patient bedroom doors to permit transportation of patients on beds, litters, or mattresses. The minimum width of corridors serving patients bedrooms in buildings shall be 2 400 mm. For detailed information on recommendations for buildings and facilities for the physically handicapped, reference may be made to good practice [4(27)].
6.3.3.4 Elevators constitute a desirable supplementary facility, but are not counted as required exits. Patient lifts shall also be provided with enough room for transporting a stretcher trolley.
6.3.3.5 Any area exceeding 500 m2 shall be divided into compartments by fire resistant walls.
6.3.3.6 Doors in fire resistant walls shall be so installed that these may normally be kept in open position, but will close automatically. Corridor door openings in smoke barriers shall be not less than 2 000 mm in width. Provision shall also be made for double swing single/ double leaf type door.
6.3.3.7 Exits and other features for penal and mental institutions, and custodial institutions shall be the same as specified for hospitals, in so far as applicable. Reliable means shall be provided to permit the prompt release of inmates from any locked section in case of fire or other emergency.
6.3.3.8 Wherever any inmates are confined in any locked rooms or spaces, adequate guards or other personnel shall be continuously on duty or immediately available to provide for release of inmates or for such other action as may be indicated in case of fire or other emergency.
6.3.3.9 No building constructed in whole or in part of combustible materials shall be used to confine inmates in cells or sleeping quarters, unless automatic sprinkler protection is provided.
6.3.3.10 All buildings or sections of buildings in penal and mental institutions used for manufacturing, storage or office purposes shall have exits in accordance with the provisions of the Code for those occupancies.
6.3.4 Additional Precautions
6.3.4.1 No combustible material of any kind shall be
stored or used in any building or section thereof used for institutional occupancy, except as necessary to normal occupancy and use of the building.
6.3.4.2 Bare minimum quantities of flammable material such as chloroform, ethyl alcohol, spirit, etc shall be allowed to be stored and handled. The handling of such liquids shall not be permitted by un-authorized persons. Bulk storage of these items, will be governed by relevant rules and safe practices.
6.3.5 Exceptions and Deviations
It is recognized that in institutions or part of buildings housing various types of psychiatric patients, or used as penal and mental institutions, it is necessary to maintain locked doors and barred windows; and to such extent the necessary provision in other sections of the Code requiring the keeping of exits unlocked may be waived. It is also recognized that certain type of psychiatric patients are not capable of seeking safety without adequate guidance. In buildings where this situation prevails, reliable means for the rapid release of occupants shall be provided, such as remote control of locks, or by keying all locks to keys commonly used by attendants.
6.7Requirements of Industrial Buildings (Group G)
6.7.1 In addition to the general requirements specified in 3.4 for the type of construction and occupancy group and the exit requirements given in 4, the requirements given in 6.7.2 to 6.7.5 shall be complied with.
6.7.2 Fire Detection/Extinguishing System
The requirements for occupancy sub-divisions G-1 to G-3 as specified in Table 23 and Annex C (for High Rise Buildings) shall apply.
6.7.3 Exit Facilities
In addition to the provisions of 4, the following requirements shall be complied with.
6.7.3.1 Not less than two exits shall be provided for every floor or section, including basements used for industrial purposes or uses incidental thereto.
6.7.3.2 In buildings used for aircraft assembly or other occupancy requiring undivided floor areas so large that the distances from points within the area to the nearest outside walls where exit doors could be provided are in excess of 45 m, requirements for distance to exits may be satisfied by providing stairs leading to exit tunnels or to overhead passageways. In cases where such arrangements are not practicable, the Authority may, by special ruling, permit other exit arrangements for one storey buildings with distances in excess of the maximum distances specified in 4, if completely automatic sprinkler protection is provided and if the heights of ceiling curtain boards and roof ventilation are such as to minimize the possibility that employees will be overtaken by the spread of fire or smoke within 1 800 mm of the floor level before they have time to reach exits, provided, however, that in no case may the distance of travel to reach the nearest exit exceed 45 m where smoke venting is required as a condition for permitting distances of travel to exits in excess of the maximum otherwise allowed.
6.7.3.3 Additional precautions
a) In any room in which volatile flammable substances are used or stored, no device generating a glow or flame capable of igniting flammable vapour shall be installed or used. Such a room shall be provided with a suitably designed exhaust ventilation system (see Annex D). To ensure safety from fire due to short circuit, faulty electrical connection or some similar cause, proper care shall be taken in designing electrical installations in such room (see Part 8 ‘Building Services, Section 2 Electrical Installations’).
b) The storage, use and handling of gasoline, fuel oil and other flammable liquids shall not be permitted in any Group G occupancy unless it complies with regulations pertaining to Petroleum Act, 1934 and Rules thereunder.
c) Every boiler room or room below the first floor containing a heating plant shall be adequately separated from the rest of the buildings.
d) For requirements regarding electrical generating and distribution stations, reference may be made to good practice [4(23)].
6.7.3.4 Exception and deviation
a) Basements used only for storage, heating or other service equipment, and not subject to industrial occupancy, shall have exits in accordance with the requirements of Group H occupancies.
b) The following exceptions shall apply to special purpose industrial occupancies:
Exits need be provided only for the persons actually employed; spaces not subject to human occupancy because of the presence of machinery or equipment may be excluded from consideration.
Where unprotected vertical openings are necessary to manufacturing operations, these may be permitted beyond the limits specified for industrial occupancy, provided every floor level has direct access to one or more enclosed stairways or other exits protected against obstruction by any fire in the open areas connected by the unprotected vertical openings or smoke therefrom.
Industrial buildings of low and moderate hazard are permitted only up to 18 m height.
c) The following exceptions shall apply to high hazard industrial occupancies:
Exits shall be so located that it will not be necessary to travel more than 22.5 m from any point to reach the nearest exit.
From every point in every floor area, there shall be at least two exits accessible in different directions; where floor areas are divided into rooms, there shall be at least two ways of escape from every room, however small, except toilet rooms, so located that the points of access thereto are out of or suitably shielded from areas of high hazard.
In addition to types of exits for upper floors specified for Group G occupancies, slide escapes may be used as required exits for both new and existing buildings.
All high hazard industrial occupancies shall have automatic sprinkler protection or such other protection as may be appropriate to the particular hazard, including explosion venting for any area subject to explosion hazard, designed to minimize danger to occupants in case of fire or other emergency before they have time to utilize exits to escape.
Industrial buildings of high hazard are permitted only up to 15 m height.
6.7.4 For detailed information on fire safety of certain individual (specific) industrial occupancies reference may be made to good practice [4(39)].
6.7.5 Fire protection considerations for venting industrial occupancies shall be as given in Annex D.
6.4Requirements of Assembly Buildings (Group D)
6.4.1 In addition to the general requirements specified in 3.4 for type of construction and occupancy group and the exit requirements given in 4, the requirements given in 6.4.2 to 6.4.8.9 shall be complied with.
6.4.2 Mixed Occupancy
Places of assembly in buildings of other occupancy, such as ballrooms in hotels, restaurants in stores and assembly rooms in schools, shall be so located, separated or protected as to avoid any undue danger to the occupants of the place of assembly from a fire originating in the other occupancy or smoke therefrom.
6.4.3 Fire Detection/Extinguishing System
The requirements for occupancy sub-divisions D-1 to D-5 as specified in Table 23 and Annex C (for High Rise Buildings) shall apply.
NOTE — Canteens shall not be provided in basements. If provided in the upper floors, it shall be sprinklered.
6.4.4 Exit Facilities
6.4.4.1 Every place of assembly, every tier or balcony, and every individual room used as a place of assembly shall have exits sufficient to provide for the total capacity thereof as determined in accordance with 4. Door width for assembly buildings shall not be less than 2 000 mm.
a) Every place of assembly of sub-division D-1
shall have at least four separate exits as remote from each other as practicable.
b) Every place of assembly of sub-division D-2, shall have at least two separate exits as remote from each other as practicable and if of capacity over 600 at least three exits shall be provided with each exit not less than of 2 000 mm width.
6.4.4.2 Clear aisles not less than 1.2 m in width shall be formed at right angles to the line of seating in such number and manner that no seat shall be more than seven seats away from an aisle. Rows of seats opening on to an aisle at one end only shall have not more than seven seats. Under the conditions, where all these aisles do not directly meet the exit doors, cross-aisles shall be provided parallel to the line of seating so as to provide direct access to the exit, provided that not less than one cross aisle for every 10 rows shall be required. The width of cross-aisles shall be minimum of 1 m. Steps shall not be placed in aisles to overcome differences in levels, unless the gradient exceeds 1 in 10.
6.4.4.3 The fascia of boxes, balconies and galleries shall have substantial railings not less than 1 000 mm high above the floor. The railings at the end of aisles extending to the fascia shall be not less than 1 100 mm high for the width of the aisle or 1 200 mm high at the foot of steps.
6.4.4.4 Cross-aisles except where the backs of seats on the front of the aisle project 600 mm or more above the floor of the aisle shall be provided with railings not less than 900 mm high.
6.4.4.5 No turnstiles or other devices to restrict the movement of persons shall be installed in any place of assembly in such a manner as to interfere in any way with the required exit facilities.
6.4.4.6 In theatres and similar places of public assembly where persons are admitted to the building at a time when seats are not available for them and are allowed to wait in a lobby or similar space until seats are available, such use of lobby or similar space shall not encroach upon the required clear width of exits. Such waiting shall be restricted to areas separated from the required exit ways by substantial permanent partitions or fixed rigid railing not less than 105 cm high. Exits shall be provided for such waiting spaces on the basis of one person for each 0.3 m2 of waiting space area. Such exits shall be in addition to the exits specified for the main auditorium area and shall conform in construction and arrangement to the general rules of exits given above.
6.4.4.7 No display or exhibit shall be so installed or operated as to interfere in any way with access to any required exit, or with any required exit sign.
All displays or exhibits of combustible material or construction and all booths and temporary construction in connection therewith shall be so limited in combustibility or protected as to avoid any undue hazard of fire which might endanger occupants before they have opportunity to use the available exits, as determined by the authority.
6.4.4.8 Places of assembly in buildings of other occupancy may use exits common to the place of assembly and the other occupancy, provided the assembly area and the other occupancy are considered separately, and each has exits sufficient to meet the requirements of the Code.
6.4.4.9 Exits shall be sufficient for simultaneous occupancy of both the places of assembly and other parts of the building, unless the Authority determines that the conditions are such that simultaneous occupancy will not occur.
6.4.4.10 For any place of assembly under sub-division D-1, at least half the required means of exits shall lead directly outdoors or through exit ways completely separated from exits serving other parts of the building.
6.4.4.11 For detailed information regarding cinema buildings, reference may be made to good practice [4 (28)].
6.4.5 Lighting
No open flame lighting devices shall be used in any place of assembly, except in the following cases:
a) Where necessary for ceremonial purposes, the enforcing Authority may permit open flame lighting under such restrictions as are necessary to avoid danger of ignition of combustible materials or injury to occupants.
b) Candles may be used on restaurant tables if securely supported on non-combustible bases and so located as to avoid danger of ignition of combustible materials.
c) Open flame devices may be used on stages where they are a necessary part of theatrical performance, provided adequate precautions, satisfactory to the Authority are taken to prevent ignition of combustible materials.
6.4.6 Additional Precautions
6.4.6.1 The decorations of places of assembly shall be of non-flammable materials. Fabrics and papers used for such purpose shall be treated with an effective flame-retardant material. Stage settings made of combustible materials shall likewise be treated with fire retardant materials of Class 1 flame spread.
6.4.6.2 Seats in places of public assembly, accommodating more than 300 persons, shall be
securely fastened to the floor, except as permitted in 6.4.6.3. All seats in balconies and galleries shall be securely fastened to the floor, except that in nailed-in enclosures, boxes with level floors and having not more than 14 seats, the seats need not be fastened.
6.4.6.3 Chairs not secured to the floor may be permitted in restaurants, night clubs and other occupancies where the fastening of seats to the floor may not be practicable, provided that in the area used for seating, excluding dance floor, stage, etc, there shall be not more than one seat for each 1.4 m2 of floor area and adequate aisles to reach exits shall be maintained at all times.
6.4.6.3.1 Rows of seats between aisles shall have not more than 14 seats.
6.4.6.3.2 Rows of seats opening on to an aisle at one end only shall have not more than 7 seats.
6.4.6.3.3 Seats without dividing arms shall have their capacity determined by allowing 450 mm per person.
6.4.6.4 The spacing of rows of seats from back-to-back shall be neither less than 850 mm nor less than 700 mm plus the sum of the thickness of the back and inclination of the back. There shall be a space of not less than 350 mm between the back of one seat and the front of the seat immediately behind it as measured between plumb lines.
6.4.6.5 Rooms containing high pressure boilers, refrigerating machinery other than domestic refrigerator type, large transformers or other service equipments subject to possible explosion shall not be located directly under or adjacent to the required exits. All such rooms shall be effectively cut off from other parts of the building and provided with adequate vents to the outer air.
6.4.6.6 All rooms or areas used for storage of any combustible materials or equipment, or for painting, refinishing, repair or similar purposes shall be effectively cut off from assembly areas or protected with a standard system of automatic sprinklers. They shall be located away from staircases.
6.4.6.7 Every stage equipped with fly galleries, grid irons and rigging for movable theatre type scenery, shall have a system of automatic sprinklers over and under such stage areas or spaces and auxiliary spaces, such as dressing rooms, store rooms and workshops, and the proscenium opening shall be provided with a fire- resisting curtain, capable of withstanding a lateral pressure of 4 kN/m2 over the entire area. The curtain shall have an emergency closing device capable of causing the curtain to close without the use of power and when so closed, it shall be reasonably tight against the passage of smoke.
6.4.7 Exception and Deviation
6.4.7.1 Where boilers or central heating plants using liquid or solid fuel are located at grade level, these shall be separated from the remainder of the building by a separating wall with openings protected as in 3.4.7 and 3.4.8.
6.4.7.2 Gymnasiums, indoor stadiums and similar occupancies may have floors/running tracks of wood, cinder, synthetic or un-protected steel or iron.
6.4.7.3 The underside of continuous steel deck grand stands when erected outdoors need not be fire-protected when occupied for public toilets.
6.4.8 Fire Protection and Fire Fighting System for Metro Stations
6.4.8.1 Wet riser system
Main and diesel fire pump of 1 800 l/min capacity to be provided to support 3 to 4 hydrants at a time. Jockey pump capacity shall be 180 l/min. Where it is possible to extend reliable DG supply to the fire pump room without routing through the station building, the provision of diesel pump can be dispensed with and instead, two electric pumps may be provided out of which at least one should have DG back-up. The jockey pump should also have DG back-up.
6.4.8.2 Internal hydrant
The internal hydrant is proposed to be provided with 2 number RRL hose pipes of 38 mm dia with 63 mm standard instantaneous coupling along with associated branch pipes and cabinet and a first aid hose reel of 25 mm dia, length 45 m and fitted with 6.5 mm nozzle.
Two internal hydrants are proposed to be provided on each platform in such a way so that most of the platform is covered by hose. However, in case of necessity, the hose pipes from other hose cabinets can be utilized for extending the length of fire hose pipe for fire fighting, if need be. At the concourse level minimum two hydrants will be provided. In station where the concourse is split into two halves at least one hydrant is to be provided in each half of the concourse. Further, in case the area is more than 2 000 m2, an additional first aid hose-reel point shall be provided for every additional 1 000 m2.
In addition, hydrants shall be provided in commercial areas also.
One hydrant shall be provided at entry of each station at ground floor for providing the coverage to the parking area.
6.4.8.3 Sprinklers
Sprinklers are required to be provided only in the commercial areas, if any, in the station. The commercial areas will be segregated from the station area through 2 h fire rated walls and doors. Additional sprinkler pumps are not required, as two pumps already provided for hydrant system will take care of the sprinkler flow requirements.
However, if such commercial areas in the premises of stations are in isolated building separate from the station building then the provision of sprinkler pump and water tank capacities shall be as per this Code. The water storage and pumps may however be common.
6.6Requirements of Mercantile Buildings (Group F)
6.6.1 In addition to the general requirements specified in 3.4 for type of construction and occupancy and the exit requirements given in 4, the requirements given in 6.6.1.1 to 6.6.5 shall be complied with.
6.6.1.1 Mixed occupancy
No dwelling unit shall have its sole means of exit through any mercantile occupancy in the same building except in the case of a single family unit where the family operates the store.
6.6.2Fire Detection/Extinguishing System
The requirements for occupancy sub-divisions F-1 to F-3 as specified in Table 23 and Annex C (for High Rise Buildings) shall apply.
6.6.3Exit Facilities
In addition to the provisions of 4, the following requirements shall be complied with.
6.6.3.1 In the case of mezzanines or balconies open to the floor below, or other un-protected vertical openings between floors, the population or area of the
mezzanine or other subsidiary floor level shall be added to that of the main floor for the purpose of determining the required exits, provided, however, that in no case shall the total number of exit units be less than that required if all vertical openings were enclosed.
6.6.3.2 At least two separate exits shall be accessible from every part of every floor, including basements; such exits shall be as remote from each other as practicable and so arranged as to be reached by different paths of travel in different directions, except that a common path of travel may be permitted for the first 15 m from any point.
6.6.4 Additional Precautions
6.6.4.1 Requirements specified in 6.5.4.1 shall be applicable to all Group F occupancies also.
6.6.4.2 Hazardous areas of mercantile occupancies shall be segregated or protected suitably.
6.6.4.3 In self-service stores, no check-out stand or associated railings or barriers shall obstruct exits or required aisles or approaches thereto.
6.6.4.4 Open-air mercantile operations, such as open-air markets, gasoline filling stations, roadside stands for the sale of a farm produce and other outdoor mercantile operations shall be so arranged and conducted as to maintain free and unobstructed ways of travel at all times to permit prompt escape from any point of danger in case of fire or other emergency, but no dead-ends in which persons might be trapped due to display stands, adjoining buildings, fences, vehicles or other obstructions.
6.6.4.5 If mercantile operations are conducted in roofed-over areas, these shall be treated as mercantile buildings, provided canopies over individual small stands to protect merchandise from the weather shall not be constructed to constitute buildings for the purpose of the Code.
6.6.5 Exception and Deviation
Any mercantile occupancy, where goods of a highly hazardous nature are pre-dominant, shall be considered under Group J occupancy for the purpose of the Code.
6.8Requirements of Storage Buildings (Group H)
6.8.1 In addition to the general requirements specified in 3.4 for type of construction and occupancy group and the exit requirements given in 4, the requirements given in 6.8.2 to 6.8.5 shall be complied with.
6.8.2 Fire Detection/Extinguishing System
The requirements for occupancy group H, as specified in Table 23 and Annex C (for High Rise Building) shall apply.
NOTE — Automatic sprinklers are prohibited where water reactive materials are kept. Instead automatic fire alarm system coupled with suitable fire extinguishing systems shall be installed.
6.8.3 Exit Facilities
In addition to the provisions of 4, the following requirements shall also be complied with.
6.8.3.1 Every building or structure used for storage and every section thereof considered separately, shall have access to at least one exit so arranged and located as to provide a suitable means of escape for any person employed therein and in any room or space exceeding 1 400 m2 gross area, or where more than 10 persons may be normally present, at least two separate means of exit shall be available, as remote from each other as practicable.
6.8.3.2 Every storage area shall have access to at least two means of exit, which can be readily opened. This shall not be subject to locking so long as any persons are inside and shall not depend on power operation.
6.8.3.3 The following special provisions shall apply to parking garages of closed or open type, above or below ground, but not to mechanical parking facilities where automobiles are moved into and out of storage mechanically which are not normally occupied by persons and thus require no exit facilities. Where repair operations are conducted, the exits shall comply with the requirements of Group G occupancies in addition to compliance with the following:
a) Where both parking and repair operations are conducted in the same building, the entire building shall comply with the requirements for Group G occupancies, unless the parking
and repair sections are effectively separated by separation walls.
Every floor of every closed parking garage shall have access to at least two separate means of exit, so arranged that from any point in the garage the paths of travel to the two means of exit shall be in different directions, except that a common path of travel may be permitted for the first 15 m, from any point.
c) On the street floor, at least two separate exit doors shall be provided, except that any opening for the passage of automobiles may serve as a means of exit, provided no door or shutter is installed thereon. Street floor exits in closed garages shall be so arranged that no point in the area is more than 30 m from the nearest exit, or 45 m in the case of garages protected by automatic sprinklers, distance being measured along the natural path of travel.
d) On floors above the street, at least two means of exit shall be provided, one of which shall be an enclosed stairway. The other means of egress may be a second exit of any of the types, or in a ramp type garage with open ramps not subject to closure, the ramp may serve as the second means of exit.
e) Upper floor exits in closed garages shall be so arranged that no point in the area shall be more than 30 m from the nearest exit other than a ramp on the same floor level or 45 m in the case of garages protected by automatic sprinklers.
f) On floors below the street (either basement or outside underground garages) at least two exits shall be provided, not counting any automobile ramps, except that for garages extending only one floor level below the street, a ramp leading direct to the outside may constitute one required means of exit. In garages below street level, exits shall be so arranged that no part of the area shall be more than 30 m from the nearest stair exit.
g) If any gasoline pumps are located within any closed parking garage, exits shall be so located that travel away from the gasoline pump in any direction shall lead to an exit; with no dead-end in which occupants might be trapped by fire or explosion at any gasoline pump. Such exit shall lead to the outside on the building on the same level, or downstairs; no upward travel shall be permitted unless direct outside exits are available from that floor and any floor below (as in the case of a basement garage where
the grade is one storey or more lower at the rear than at the street).
6.8.3.4 Exits from aircraft hangers (storage or servicing areas) shall be provided at intervals of not more than 45 m on all exterior walls of aircraft hangers. There shall be a minimum of two exits serving each aircraft storage or servicing areas. Horizontal exits through interior fire walls shall be provided at intervals of not more than 30 m. ‘Dwarf or ‘smash’ doors accommodating aircraft may be used to comply with these requirements. All doors designated as exits shall be kept unlocked in the direction of exit travel while the area is occupied.
6.8.3.5 Exits from mezzanine floors in aircraft storage or servicing areas shall be so arranged that the maximum travel to reach the nearest exits from any point on the mezzanine shall not exceed 22.5 m. Such exits shall lead directly to a properly enclosed stairwell discharging directly to the exterior or to a suitably cutoff area or to outside fire escape stairs.
6.8.3.6 The following special provisions shall apply to grain elevators:
a) There shall be at least one stair tower from basement to first floor and from the first floor to the top floor of workhouse which is enclosed in a dust-tight non-combustible shaft.
b) Non-combustible doors of self-closing type shall be provided at each floor landing.
c) An exterior fire escape of the stair or basket ladder type shall be provided from the roof of the workshop to ground level or the roof of an adjoining annexe with access from all floors above the first.
d) An exterior fire escape of either the stair or basket ladder type shall be provided from the roof of each storage annexe to ground level.
6.8.4 Additional Precautions
Requirements specified in 6.7.3.3 shall apply to Group H occupancies also.
6.8.5 Exceptions and Deviations
Every area used for the storage of hazardous commodities shall have an exit within 22.5 m of any point in the area where persons may be present or 35 m where automatic sprinkler protection is provided.
6.5Business Buildings (Group E)
6.5.1 In addition to the general requirements specified in 3.4 for type of construction and occupancy group and the exit requirements given in 4, the requirements given in 6.5.2 to 6.5.5 shall be complied with.
6.5.2 Fire Detection/Extinguishing System
The requirements for occupancy sub-divisions as specified in Table 23 and Annex C (for High Rise Buildings) shall apply.
6.5.2.1 Occ buildings)
upancy sub-division E-1 (except office
Details of
Fire Detection/Extinguishing
Occupancy
System
E-1
Automatic fire alarm system {good practice [4(17)] and [4(18)], and Table 23}.
6.5.2.2Occupancy sub-division E-2
Details of Occupancy
Fire Detection/Extinguishing System
a) Laboratory with delicate instruments
Fixed automatic CO2 fire extinguishing system or automatic fire alarm system {good practice [4(18)] and [4(19)], and Table 23}
b) Solvent storage and/or flammable liquid
Automatic foam installation or automatic CO2 fire extinguishing system
6.5.2.3Occupancy sub-division E-3
Details of Occupancy
Fire Detection/Extinguishing System
a) Area of computer installations
Automatic fire alarm system{good practice [4(18)] and [4(19)], and Table 23} any suitable halon alternative fire extinguishing system (see 5.3) or any other suitable fire extinguishing installation{see also [4(29)]}.
b) Space under false ceiling (floor)
Automatic fire alarm system{good practice [4(18)] and [4(19)], and Table 23}
c) Space above false ceiling and below false floor
Automatic fire alarm system{good practice [4(18)] and [4(19)], and Table 23}
d) Electrical switch board
Automatic fire alarm system{good practice [4(18)] and [4(19)], and Table 23} and CO2 fire extinguishing installation
6.5.2.4 Occupancy sub-division E-4
Details of Occupancy
Fire Detection/Extinguishing System
Telephone exchanges
Any suitable halon alternative fire extinguishing system (see 5.3) and/or automatic sprinkler system as per requirement (see also Table 23)
6.5.2.5 Occupancy sub-division E-5
Details of Occupancy
Fire Detection/ Extinguishing System
Broadcasting stations
Automatic fire alarm system based on smoke detectors and sprinkler system (see also Table 23)
6.5.3 Exit Facilities
6.5.3.1 In the case of mezzanines or balconies open to the floor below, or other unprotected vertical openings between floors, the population of the mezzanine or other subsidiary floor for level shall be added to that of the main floor for the purpose of determining the required exits, provided, however, that in no case shall the total number of exit units be less than that required if all vertical openings were enclosed.
6.5.3.2 Not less than two exits shall be provided for every floor, including basements occupied for office purposes or uses incidental thereto.
6.5.4Additional Requirements
6.5.4.1 The handling and use of gasoline, fuel oil and other flammable liquids shall not be permitted, unless such use and handling complies with the appropriate regulations.
6.5.4.2 Every boiler room or room containing a central heating plant using solid or liquid fuel shall be separated from the rest of the building by a separating wall. Every boiler room or room containing a central heating plant, which burns gas as a fuel shall be adequately separated from the rest of the building.
6.5.5Exception and Deviation
6.5.5.1 Basements used only for storage, heating, any other service equipment shall conform to exit requirements for Group H occupancies in all respects.
6.9Requirements of Buildings for Hazardous Uses (Group J)
6.9.1 In addition to the general requirements specified in 3.4 for type of construction and occupancy group and the exit requirements given in 4, the requirements given in 6.9.2 to 6.9.4 shall be complied with.
6.9.2 Fire Detection/Extinguishing System
The requirements for occupancy Group J, as specified in Table 23 and Annex C (for High Rise Building) shall apply.
NOTE — Hazardous buildings shall have vapour detectors/ explosion suppression systems/automatic sprinklers, besides hydrant system, wet risers and automatic fire alarm system depending on the type of fire hazard involved.
6.9.3 Exit Facilities
Requirements specified in 4 and 6.7.3.4 (c) shall apply to Group J occupancies also.
6.9.4 Additional Precautions
The following requirements shall apply to all Group J occupancies, as applicable:
a) Each building where gas is employed for any purpose shall be provided with an approved outside gas shut-off valve conspicuously marked. The detailed requirements regarding safe use of gas shall be as specified in Part 9 ‘Plumbing Services, Section 2 Gas Supply’.
b) Each boiler room or room containing a heating plant shall be separated from the rest of the building by a separating wall.
c) In any room in which volatile flammable substances are used or stored, no device generating a spark, or glow flame capable of igniting flammable vapour shall be installed
d)
e)
f)
g)
or permitted unless it is enclosed in a flameproof enclosure.
The use, handling, storage and sale of gasoline, fuel oil and other flammable liquids snail not be permitted in Group J occupancies unless such use, handling, storage and sale is in accordance with appropriate legislation in force.
All openings in exterior walls except wall vents shall be protected by a fire stop assembly as in 4 and they shall be fixed, automatic or self-closing. Wall vents having an area of not less than 100 cm2 each shall be placed in the exterior walls near the floor line, not more than 1 800 mm apart horizontally. Each building shall be provided with a power driven fan exhaust system of ventilation which shall be arranged and operated so as to produce a complete change of air in each room every 3 min.
Each machine in dry-cleaning establishments which uses flammable liquid shall have an adequate steam line or any other suitable extinguishing agent directly connected to it, so arranged as to have the agent automatically released to the inside of each machine should an explosion occur in the machine.
Equipment or machinery which generates or emits combustible or explosive dust or fibres shall be provided with an adequate dust collecting and exhaust system.
(Clause 3.1.8)
ANNEX A
Calorific Values of Common Materials and Typical Values of Fire Load Density
A-1 The calorific values of some common materials are given in Table 25 for guidance.
Table 25Calorific Values of Common Materials
Material
Calorific Value (103 kJ/kg-1)<sup>1</sup>)
Wood Equivalent(kg/kg)
(1)
(2)
(3)
Solid Fuels
Anthracite
28.6
1.66
Bituminous Coal
30.8
1.75
Charcoal
28.4
1.61
Coke (average)
27.5
1.56
Peats
20.9
1.19
Sub-bituminous Coal
22.0
1.25
Woods (hard or softwood)
17.6
1.00
Hydrocarbons
Benzene
39.6
2.25
Butane
47.1
2.68
Ethane
49.1
2.79
Ethylene
47.7
2.71
Fuel Oil
41.6
2.36
Gas Oil
42.9
2.44
Hexane
44.9
2.55
Methane (natural gas)
52.8
3.00
Octane
45.3
2.58
Paraffin
39.6-44.0
2.3-2.5
Pentane
46.0
2.61
Propane
47.3
2.69
Propylene
46.2
2.63
Alcohols
Ethyl Alcohol
28.4
1.61
Methyl Alcohol
21.1
1.20
Propyl Alcohol
31.9
1.81
Polymers
Casein
23.1
1.31
Cellulose
16.5
0.94
Cellulose Acetate
17.8
1.01
Polyethylene
48.4
2.75
Polypropylene
Annex BBroad Classification of Industrial and Non-industrial Occupancies Into Different Degree of Hazard
B-1 Low Hazard Occupancies
Abrasive manufacturing premises Aerated water factories Agarbatti manufacturing premises Analytical and/or Q.C. Laboratories Arecanut slicing and/or Betelnut factories Asbestos steam packing and lagging manufacturers Assembly buildings small (D-4 and D-5) Battery charging and service stations Battery manufacturing Breweries Brickworks Canning factories Cardamom factories Cement factories and/or asbestos or concrete products manufacturing premises Ceramic factories, crockery, stoneware pipe manufacturing Clay works Clock and watch manufacturing Clubs Coffee curing, roasting and grinding factories Condensed milk factories, milk pasturising plants and dairies Confectionary manufacturing Dwellings, lodges, dormitories, etc Educational and research institutions Electric lamps (incandescent and fluorescent) and T.V. tube manufacturing Electroplating works Engineering workshops Fruits and vegetables dehydrating and drying factories Fruits products and condiment factories Glass and glass fibre manufacturing Godowns and warehouses (non-combustible goods) Gold thread/gilding factories Gum and/or glue and gelatine manufacturing Ice candy and ice-cream and ice factories Ink (excluding printing ink) factories Mica products manufacturing
Office premises Places of worship Pottery works Poultry farms Residential buildings (A-1 to A-4) (except hotels A-5) Salt crushing factories/refineries stables Sugar candy manufacturing Sugar factories and refineries Tanneries Umbrella assembling factories Vermicelli factories Water treatment/filtration plants and water pump houses Zinc/copper factories
B-2 Moderate Hazard Occupancies
Airport and other transportation terminal buildings Aluminium factories Assembly buildings (D-1 to D-3) Atta and cereal grinding Bakeries and biscuit factories Beedi factories Bobbin factories Book-binders, envelopes and paper bag manufacturing Cable manufacturing Camphor boiling Candle works Carbon paper/typewriter ribbon makers Card board box manufacturing Carpenters, wood wool and furniture makers Carpet and durries factories Cashewnut factories Chemical manufacturers (using raw materials having F.P > 23°C) Cigar and cigarette factories Coir factories Cold storage premises Computer installations Cork products manufacturing (coir, carpets, rugs and tobacco) (hides and skin presses) Dry cleaning, dyeing and laundries Electric sub-stations/distribution stations
Electrical generating stations except under ground powerhouses Enamelware factories Filler and wax paper manufacturing Flour mills Garment makers Ghee factories (other than vegetable) Godowns and warehouses (other than non-combustible goods) Grains and seed disintegrating or crushing Grease manufacturing Hosiery, lace, embroidery and thread Hospitals including ‘X’-ray and other diagonastic clinics (institutional buildings) Incandescent gas mantle manufacturers Industrial gas manufacturing (only halogenated hydrocarbons/inert gases) Man-made yarn/fibre (except acrylic fibre/yarn) Manure and fertilizer works (blending, mixing and granulating only) Mercantile occupancies (departmental stores, shopping complex, etc) Mineral oil blending and processing Museums, archieves, record rooms Oil and leather cloth factories Open storage of flammable liquids (in drums, cans, etc) Oxygen plants Paper and cardboard mills (except raw material yard) Piers, wharves, dockyards Plastic goods manufacturing Plywood/wood veneering factories Printing press premises Pulverizing and crushing mills Residential apartments, hotels, cafes, restaurants Rice mills Rope works Rubber goods manufacturing Rubber tyres and tubes manufacturing Shellac factories Silk filiatures Soaps and glycerine factories Spray painting Starch factories Tea factories (including blending packing of tea) Telephone exchanges, garages Textile mills
Tobacco chewing and pan masala making Tobacco re-drying factories Woolen mills
A)
B-3 High Hazard Occupancies
Aircraft hangers Aluminium/magnesium powder plants Bitumanized paper/hessian cloth/tar felt manufacturing Bulk storage of flammable liquids (tank farm, etc) Celluloid goods making Chemical manufacturers (where raw materials have a F.P. < 23°C) Cigarette filter manufacturing Cinema films and T.V. production studios Coal, coke and charcoal ball and briquettes making Collieries, steel plants Cotton seeds cleaning and delinting factories Cotton waste factories Distilleries Duplicating/stencil paper making Fire works manufacture Foamed plastic and/or converting plants Godowns of warehouses (combustible/hazardous goods) (H) Grass, hay, fodder and BHOOSA (chaff) Hazardous occupancy buildings (J) Industrial gas manufacturing (except halogenated hydrocarbon gases/inert gases) Industrial units (G-3 occupancies) Jute mills and jute presses Linoleum factories Man-made fibres (only acrylic fibre/yarn making) Match factories Mattress and pillow makings (foam plastics) Metal or tin printers (if more than 50 percent is engineering, shift to ordinary hazard) Oil mills Oil extraction plants Oil terminals/depots Paints/Varnish factories Paper and cardboard mills (only raw material yard) Pressing factories Printing ink making Resin, lamp black and turpentine manufacture Saw mills
Surgical cotton manufacturing Tarpaulin and canvas proofing factories Turpentine and resin distilleries Tyre retreading and resolving factories Underground shopping complexes (F-3) B) Ammonia and urea synthesis plants
NOTE — In case of complexes having segregated plants with varying degrees of hazards, the competent authority having jurisdictions shall be consulted to decide the level of protections to be provided.
Fire Protection Requirements for High Rise Buildings — 15 M in Height or Above
C-0 General
In addition to the general provisions given in this Part, the Authority may insist on suitable protection measures (see C-1 to C-11) in a building 15 m in height or above.
C-1 Construction
C-1.1 All materials of constructions in load bearing elements, stairways and corridors and facades shall be non-combustible.
C-1.2 The interior finish materials shall not have a flame spreadability rating exceeding Class 1 (see 3.4.15.2).
C-1.3 The internal walls or staircase shall be of brick or reinforced concrete with a minimum of 2 h fire rating.
C-1.4 The staircase shall be ventilated to the atmosphere at each landing and a vent at the top; the vent openings shall be of 0.5 m2 in the external wall and the top. If the staircase cannot be ventilated, because of location or other reasons, a positive pressure 50 Pa shall be maintained inside. The mechanism for pressurizing the staircase shall operate automatically with the fire alarm. The roof of the shaft shall be 1 m above the surrounding roof. Glazing or glass bricks if used in staircase, shall have fire resistance rating of minimum 2 h.
C-1.5 Lifts
General requirements of lifts shall be as follows:
a) Walls of lift enclosures shall have a fire rating of 2 h; lifts shafts shall have a vent at the top of area not less than 0.2 m2.
b) Lift motor room shall be located preferably
on top of the shaft and separated from the shaft by the floor of the room.
c) Landing doors in lift enclosures shall have a fire resistance of not less than 1 h.
d) The number of lifts in one row for a lift bank shall not exceed 4 and the total number of lifts in the bank (of two rows) shall not exceed 8. A wall of 2 h fire rating shall separate individual shafts in a bank.
e) Lift car door shall have a fire resistance rating of half an hour.
f) Collapsible gates shall not be permitted for lifts and shall have solid doors with fire resistance of at least 1 h.
g) If the lift shaft and lobby is in the core of the building, a positive pressure between 25 and 30 Pa shall be maintained in the lobby and a positive pressure of 50 Pa shall be maintained in the lift shaft. The mechanism for pressurization shall act automatically with the fire alarm; it shall be possible to operate this mechanically also.
h) Exit from the lift lobby, if located in the core of the building, shall be through a self-closing smoke stop door of half an hour fire resistance.
j) Lifts shall not normally communicate with the basement; if, however, lifts are in communication, the lift lobby of the basements shall be pressurized as in (g), with self-closing door as in (h).
k) Grounding switch(es), at ground floor level, shall be provided on all the lifts to enable the fire service to ground the lifts.
m) Telephone or other communication facilities
shall be provided in lift cars for building of 30 m in height and above. Communication system for lifts shall be connected to fire control room for the building.
Suitable arrangements such as providing slope in the floor of lift lobby, shall be made to prevent water used during fire fighting, etc, at any landing from entering the lift shafts.
p) A sign shall be posted and maintained on every floor at or near the lift indicating that in case of fire, occupants shall use the stairs unless instructed otherwise. The sign shall also contain a plan for each floor showing the locations of the stairways.
Alternate source of power supply shall be provided for all the lifts through a manually operated changeover switch.
q) Fire Lifts — Following details shall apply for a fire lift:
To enable fire services personnel to reach the upper floors with the minimum delay, one fire lift per 1 200 m2 of floor area shall be provided and shall be available for the exclusive use of the firemen in an emergency.
The lift shall have a floor area of not less than 1.4 m2. It shall have loading capacity of not less than 545 kg (8 persons lift) with automatic closing doors of minimum 0.8 m width.
The electric supply shall be on a separate service from electric supply mains in a building and the cables run in a route safe from fire, that is, within the lift shaft. Lights and fans in the elevators having wooden paneling or sheet steel construction shall be operated on 24 V supply.
Fire fighting lift should be provided with a ceiling hatch for use in case of emergency, so that when the car gets stuck up, it shall be easily openable.
In case of failure of normal electric supply, it shall automatically trip over to alternate supply. For apartment houses, this changeover of supply could be done through manually operated changeover switch. Alternatively, the lift shall be so wired that in case of power failure, it comes down at the ground level and comes to stand-still with door open.
The operation of a fire lift is by a simple toggle or two-button switch situated in a glass-fronted box adjacent to the lift at
the entrance level. When the switch is on, landing call-points will become inoperative and the lift will be on car control only or on a priority control device. When the switch is off, the lift will return to normal working. This lift can be used by the occupants in normal times.
The words ‘Fire Lift’ shall be conspicuously displayed in fluorescent paint on the lift landing doors at each floor level.
The speed of the fire lift shall be such that it can reach the top floor from ground level within 1 min.
C-1.9 Service Ducts/Shafts
a) Service ducts and shafts shall be enclosed by walls of 2 h and doors of 1 h, fire rating. All such ducts/shafts shall be properly sealed and fire stopped at all floor levels.
b) A vent opening at the top of the service shaft shall be provided having between one-fourth and one-half of the area of the shaft.
C-1.10 Refuse chutes shall have opening at least 1 m above roof level or venting purpose and they shall have an enclosure wall of non-combustible material with fire resistance of not less than 2 h. They shall not be located within the staircase enclosure or service shafts, or air-conditioning shafts inspection panel and doors shall be tight fitting with 1 h fire resistance; the chutes should be as far away as possible from exits.
C-1.11 Refuge Area
Provisions contained in 4.12.3 shall apply for all buildings except multi-family dwellings, refuge area of not less than 15 m2 shall be provided on the external walls.
C-1.12 Electrical services shall conform to the following:
a) The electric distribution cables/wiring shall be laid in a separate duct. The duct shall be sealed at every floor with non-combustible materials having the same fire resistance as that of the duct. Low and medium voltage wiring running in shaft and in false ceiling shall run in separate conduits;
b) Water mains, telephone lines, intercom lines, gaspipes or any other service line shall not be laid in the duct for electrical cables; use of bus ducts/solid rising mains instead of cables is preferred;
c) Separate circuits for fire fighting pumps, lifts, staircases and corridor lighting and blowers for pressurizing system shall be provided directly from the main switch gear panel and these circuits shall be laid in separate conduit pipes, so that fire in one circuit will not affect the others. Such circuits shall be protected at origin by an automatic circuit breaker with its no-volt coil removed. Master switches controlling essential service circuits shall be clearly labelled;
d) The inspection panel doors and any other opening in the shaft shall be provided with air-tight fire doors having fire resistance of not less than 2 h;
e) Medium and low voltage wiring running in shafts, and within false ceiling shall run in metal conduit. Any 230 V wiring for lighting or other services, above false ceiling, shall have 660 V grade insulation. The false ceiling, including all fixtures used for its suspension, shall be of non-combustible material and shall provide adequate fire resistance to the ceiling in order to prevent spread of fire across ceiling reference may be made to good practice [4(29)];
f) An independent and well ventilated service room shall be provided on the ground level or first basement with direct access from outside or from the corridor for the purpose of termination of electric supply from the licensees’ service and alternative supply cables. The doors provided for the service room shall have fire resistance of not less than 2 h;
NOTE — If service room is located at the first basement, it should have automatic fire extinguishing system.
g) If the licensees agree to provide meters on upper floors, the licensees’ cables shall be segregated from consumers’ cables by providing a partition in the duct. Meter rooms on upper floors shall not open into stair case enclosures and shall be ventilated directly to open air outside; and
h) Suitable circuit breakers shall be provided at the appropriate points.
C-1.6 Basements
C-1.6.1 Each basement shall be separately ventilated. Vents with cross-sectional area (aggregate) not less than 2.5 percent of the floor area spread evenly round the perimeter of the basement shall be provided in the form of grills, or breakable stallboard lights or pavement lights or by way of shafts. Alternatively, a system of air inlets shall be provided at basement floor level and smoke outlets at basement ceiling level. Inlets and extracts may be terminated at ground level with stallboard or pavement lights as before, but ducts to convey fresh air to the basement floor level have to be laid. Stallboard and pavement lights should be in positions easily accessible to the fire brigade and clearly marked ‘SMOKE OUTLET’ or ‘AIR INLET with an indication of area served at or near the opening.
C-1.6.2 The staircase of basements shall be of enclosed type having fire resistance of not less than 2 h and shall be situated at the periphery of the basement to be entered at ground level only from the open air and in such positions that smoke from any fire in the basement shall not obstruct any exit serving the ground and upper stores of the building and shall communicate with basement through a lobby provided with fire resisting self closing doors of 1 h resistance. For travel distance see 4.5. If the travel distance exceeds as given in Table 21, additional staircases shall be provided at proper places.
C-1.6.3 In multi-storey basements, intake ducts may serve all basement levels, but each basement levels and basement compartment shall have separate smoke outlet duct or ducts. Ducts so provided shall have the same fire resistance rating as the compartment itself. Fire rating may be taken as the required smoke extraction time for smoke extraction ducts.
C-1.6.4 Mechanical extractors for smoke venting system from lower basement levels shall also be provided. The system shall be of such design as to
operate on actuation of heat/smoke sensitive detectors or sprinklers, if installed, and shall have a considerably superior performance compared to the standard units. It shall also have an arrangement to start it manually.
C-1.6.4.1 Mechanical extractors shall have an internal locking arrangement, so that extractors shall continue to operate and supply fans shall stop automatically with the actuation of fire detectors.
C-1.6.4.2 Mechanical extractors shall be designed to permit 30 air changes per hour in case of fire or distress call. However, for normal operation, air changes schedule shall be as given in 3.4.11.5.
C-1.6.4.3 Mechanical extractors shall have an alternative source of supply.
C-1.6.4.4 Ventilating ducts shall be integrated with the structure and made out of brick masonry or reinforced cement concrete as far as possible and when this duct crosses the transformer area or electrical switchboard, fire dampers shall be provided.
C-1.6.5 Use of basements for kitchens working on gas fuel shall not be permitted, unless air conditioned.
The basement shall not be permitted below the ward block of a hospital/nursing home unless it is fully sprinkled.
Building services such as electrical sub-stations, boiler rooms in basements shall comply with the provisions of the Indian Electricity Act/Rules.
C-1.6.6 If cut outs are provided from basements to the upper floors or to the atmospheres, all sides cut out openings in the basements shall be protected by sprinkler head at close spacing so as to form a water curtain in the event of a fire.
C-1.7 Openable windows on external walls shall be fitted with such locks that can be opened by a fireman’s axe.
C-1.8 All floors shall be compartmented with area not exceeding 750 m2 by a separation wall with 2 h fire rating, for floors with sprinklers the area may be increased by 50 percent. In long building, the fire separation walls shall be at distances not exceeding 40 m. For departmental stores, shopping centres and basements, the area may be reduced to 500 m2 for compartmentation. Where this is not possible, the spacings of the sprinklers shall be suitably reduced. When reducing the spacing of sprinklers, care should be taken to prevent spray from one sprinkler impeding the performance of an adjascent sprinkler head.
C-1.8.1 It is essential to make provisions for drainage of any such water on all floors to prevent or minimize water damage of the contents. The drain pipes should be provided on the external wall for drainage of water
from all floors. On large area floors several such pipes may be necessary which should be spaced 30 m apart. Care shall be taken to ensure that the construction of the drain pipe does not allow spread of fire/smoke from floor to floor.
C-1.13 Gas supply shall conform to the following:
a) Town Gas/L.P. Gas Supply Pipes — Where gas pipes are run in buildings, the same shall be run in separate shafts exclusively for this purpose and these shall be on external walls, away from the staircases. There shall no interconnection of this shaft with the rest of the floors. LPG distribution pipes shall always be below the false ceiling. The length of these pipes shall be as short as possible. In the case of kitchen cooking range area, apart from providing hood, covering the entire cooking range, the exhaust system should be designed to take care of 30 m3 per minute per m2 of hood protected area. It should have grease filters using metallic grill to trap oil vapours escaping into the fume hood.
NOTE — For detailed information on gas pipe installations, reference may be made to Part 9 ‘Plumbing Services, Section 3 Gas Supply’.
b) All wiring in fume hoods shall be of fibre glass insulation. Thermal detectors shall be installed into fume hoods of large kitchens for hotels, hospitals, and similar areas located in high rise buildings. Arrangements shall be made for automatic tripping of the exhaust fan in case of fire. If LPG is used, the same shall be shut off. The voltage shall be 24 V or 100 V dc operated with external rectifier. The valve shall be of the hand re-set type and shall be located in an area segregated from cooking ranges. Valves shall be easily accessible. The hood shall have manual facility for steam or carbon dioxide gas injection, depending on duty condition; and
c) Gas meters shall be housed in a suitably constructed metal cupboard located in a well ventilated space, keeping in view the fact that LPG is heavier than air and town gas is lighter than air.
C-1.16 Transformers shall conform to the following:
a) A sub-station or a switch-station with oil filled equipment shall not be located in the building. The sub-station structure shall have separate fire resisting walls/surroundings and shall necessarily be located at the periphery of the floor having separate access from fire escape stair case. The outside walls, ceiling, floor, openings including doors and windows to the sub-station area shall be provided with a fire resisting door of 2 h fire rating. Direct access to the transformer room shall be provided, preferably from outside fire escape staircase.
b) The sub-station area needs to be maintained at negative air pressures and area in sub-station shall not be used as storage/dump areas.
c) When housed inside the building, the transformer shall be of dry type and shall be cut off from the other portion of premises by walls/doors/cutout having fire resistance rating of 4 h.
C-1.14 Illumination of Means of Exit
Staircase and corridor lights shall conform to the following (see 4.16 and 4.17 for additional details):
a) The staircase and corridor lighting shall be on separate circuits and shall be independently connected so as it could be operated by one switch installation on the ground floor easily accessible to fire fighting staff at any time irrespective of the position of the individual control of the light points, if any. It should be of miniature circuit breaker type of switch so as to avoid replacement of fuse in case of crisis;
b) Staircase and corridor lighting shall also be connected to alternative supply. The alternative source of supply may be provided by battery continuously trickle charged from the electric mains;
c) Suitable arrangements shall be made by installing double throw switches to ensure that the lighting installed in the staircase and the corridor does not get connected to two sources of supply simultaneously. Double throw switch shall be installed in the service room for terminating the stand-by supply;
d) Emergency lights shall be provided in the staircase and corridor; and
e) All wires and other accessories used for emergency light shall have fire retardant property.
C-1.15 A stand-by electric generator shall be installed to supply power to staircase and corridor lighting circuits, fire lifts, the stand-by fire pump, pressurization
fans and blowers, smoke extraction and damper systems in case of failure of normal electric supply. The generator shall be capable of taking starting current of all the machines and circuits stated above simultaneously. If the stand-by pump is driven by diesel engine, the generator supply need not be connected to the stand-by pump. Where parallel HV/LV supply from a separate sub-station is provided with appropriate transformer for emergency, the provision of generator may be waived in consultation with the Authority.
C-1.17 Air-conditioning shall conform to the following:
a) Escape routes like staircases, common corridors, lift lobbies, etc, shall not be used as return air passage.
b) The ducting shall be constructed of substantial gauge metal in accordance with good practice [4(31].
c) Wherever the ducts pass through fire walls or floors, the opening around the ducts shall be sealed with materials having fire resistance rating of the compartment.
d) Where duct crosses a compartment which is fire rated, the ducts shall be fire rated for same fire rating. Further depending on services passing around the duct work, which may get affected in case of fire temperature rising, the ducts shall be insulated.
e) As far as possible, metallic ducts shall be used even for the return air instead of space above the false ceiling.
f) Where plenum is used for return air passage,
g)
ceiling and its fixtures shall be of non-combustible material.
The materials used for insulating the duct system (inside or outside) shall be of non-combustible materials. Glass wool shall not be wrapped or secured by any material of combustible nature.
h) Area more than 750 m2 on individual floor shall be segregated by a fire wall and automatic fire dampers for isolation shall be provided [see (j)].
j) Air ducts serving main floor areas, corridors, etc, shall not pass through the staircase enclosure.
k) The air-handling units shall be separate for each floor and air ducts for every floor shall be separated and in no way inter-connected with the ducting of any other floor.
m) If the air-handling unit serves more than one floor, the recommendations given above shall be complied with in addition to the conditions given below:
proper arrangements by way of automatic fire dampers working on smoke detector/ or fusible link for isolating all ducting at every floor from the main riser shall be made.
When the automatic fire alarm operates, the respective air-handling units of the airconditioning system shall automatically be switched off.
n) The vertical shaft for treated fresh air shall be of masonry construction.
p) The air filters of the air-handling units shall be of non-combustible materials.
q) The air-handling unit room shall not be used for storage of any combustible materials.
t) Fire Dampers
These shall be located in conditioned air ducts and return air ducts/passages at the following points:
i) At the fire separation wall.
ii) Where ducts/passages enter the central vertical shaft.
iii) Where the ducts pass through floors.
iv) At the inlet of supply air duct and the return air duct of each compartment on every floor.
The dampers shall operate automatically and shall simultaneously switch off the air-handling fans. Manual operation facilities shall also be provided.
NOTE — For blowers, where extraction system and duct accumulators are used, dampers shall be provided.
Fire/smoke dampers (for smoke extraction shafts) for buildings more than 24 m in height.
For apartment In non-ventilated houses lobbies/ corridors operated by fusible link/smoke detectors and with manual control.
For other On operation of smoke buildings detection system and with manual control.
Automatic fire dampers shall be so arranged as to close by gravity in the direction of air movement and to remain tightly closed on operation of a fusible link/smoke detector.
C-1.18 Provisions of boiler and boiler rooms shall conform to Indian Boiler Act. Further, the following additional aspects may be taken into account in the location of boiler room:
a) The boilers shall not be allowed in subbasement, but may be allowed in the basements away from the escape routes.
b) The boilers shall be installed in a fire resisting room of 4 h fire resistance rating, and this room shall be situated on the periphery of the basement. Catch-pits shall be provided at the low level.
c) Entry to this room shall be provided with a composite door of 2 h fire resistance.
d) The boiler room shall be provided with fresh air inlets and smoke exhausts directly to the atmosphere.
e) The furnace oil tank for the boiler, if located in the adjoining room shall be separated by fire resisting wall of 4 h rating. The entrance to this room shall be provided with double composite doors. A curb of suitable height shall be provided at the entrance in order to
prevent the flow of oil into the boiler room in case of tank rupture.
f) Foam inlets shall be provided on the external walls of the building near the ground level to enable the fire services to use foam in case of fire.
C-2 Provision of First-aid Fire Fighting Appliances
C-5 Fire Control Room
For all buildings 15 m in height or above and apartment buildings with a height of 30 m and above, there shall be a control room on the entrance floor of the building with communication system (suitable public address system) to all floors and facilities for receiving the message from different floors. Details of all floor plans along with the details of fire fighting equipment and installations shall be maintained in the fire control room. The fire control room shall also have facilities to detect the fire on any floor through indicator boards connection; fire detection and alarm systems on all floors. The fire staff incharge of the fire control room
shall be responsible for the maintenance of the various services and fire fighting equipment and installations in co-ordination with security, electrical and civil staff of the building.
C-6 Fire Officer for Hotels, Business and Mercantile Buildings with Height More Than 30 M
C-6.1 A qualified Fire Officer with experience of not less than 3 years shall be appointed who will be available on the premises.
C-6.2 The Fire Officer shall:
a) maintain the fire fighting equipment in good working condition at all times,
b) prepare fire orders and fire operational plans and get them promulgated,
c) impart regular training to the occupants of the buildings in the use of fire fighting equipments provided on the premises and keep them informed about the fire emergency evacuation plan,
d) keep proper liaison with city Fire Brigade, and
e) ensure that all fire precautionary measures are observed at the times.
NOTE — Competent authority having jurisdiction may insist on compliance of the above rules in case of buildings having very large areas even if the height is less than 30 m.
C-7 House Keeping
To eliminate fire hazards, good house keeping, both
inside and outside the building, shall be strictly maintained by the occupants and/or the owner of the building.
C-8 Fire Drills and Fire Orders
Fire notices/orders shall be prepared to fulfil the requirements of fire fighting and evacuation from the buildings in the event of fire and other emergency. The occupants shall be made thoroughly conversant with their actions in the event of emergency, by displaying fire notices at vantage points and also through regular training. Such notices should be displayed prominently in broad lettering.
For guidelines for fire drills and evacuation procedures for high rise buildings, see Annex E.
C-9 Compartmentation
The building shall be suitably compartmentalized so that fire/smoke remain confined to the area where fire incident has occurred and does not spread to the remaining part of the building.
C-10 Helipad
For high rise buildings above 60 m in height, provision for helipad should be made.
C-11 Materials for Interior Decoration/furnishing
The use of materials which are combustible in nature and may spread toxic fume/gases should not be used for interior decoration/furnishing, etc.
C-3 Fire Alarm System
C-3.1 All buildings with heights of 15 m or above shall be equipped with manually operated electrical fire alarm (MOEFA) system and automatic fire alarm system in accordance with good practice [4(18)] and [4(19)]. However, apartment buildings between 15 m and 30 m in height may be exempted from the installation of automatic fire alarm system provided the local fire brigade is suitably equipped for dealing with fire in a building of 15 m in height or above and in the opinion of the Authority, such building does not constitute a hazard to the safety of the adjacent property or occupants of the building itself.
C-3.1.1 Manually operated electrical fire alarm system shall be installed in a building with one or more call boxes located at each floor. The call boxes shall conform to good practice [4 (18)] and [4(19)].
C-3.1.2 The installation of call boxes in hostels and such other places where these are likely to be misused shall as far as possible be avoided. Location of call boxes in dwelling units shall preferably be inside the building.
C-4 Lightning Protection of Buildings
The lightning protection for buildings shall be provided as given in Part 8 ‘Building Services, Section 2 Electrical Installations’.
Annex D(Clauses 6.7.3.3 (a) and 6.7.5)
Fire Protection Considerations for Venting in Industrial Buildings
D-1 Application and Scope
D-1.1 The provisions given below are applicable only to single storey industrial buildings (factories and storage buildings) covering large floor areas without sub-dividing/separating walls which are usually designed to meet modern production methods.
D-1.2 The requirements of fire and explosion venting of industrial buildings, as dealt with in this section, fall under two categories:
a) Smoke and fire venting, and
b) Explosion relief vents.
D-2 Smoke and Fire Venting
D-2.1 The basic considerations for formulating the design and other requirements for smoke and fire vents are as given in D-2.1.1 to D-2.1.20.
D-2.1.1 The smoke and hot combustion products from a fire, being lighter than the surrounding air, tend to rise and on reaching the roof or ceiling spread out (mushroom) on all sides and form a layer which floats on top of the cold air beneath. In the absence of vents, this layer becomes progressively deeper until the whole building is filled with hot smoky gases. The time consumed for this to happen may be only a few
minutes, depending on variables like, type of materials on fire, process/storage conditions involved, etc.
D-2.1.2 The hot gases at the roof level moved by convection currents contribute to rapid lateral spread of fire.
D-2.1.3 The provision of properly designed and suitably located vents in adequate number helps the speedy removal of smoke and hot gases, thereby preventing spread of fire, besides reducing risks of explosion of unburnt gases and reducing damage to the contents and structure of the building by heat and smoke. In addition, they facilitate fire fighting operations, and minimize personal hazards to the firemen.
D-2.1.4 The time taken for accumulation of smoke and hot gases within a building on fire being very short, the venting devices installed shall be designed to operate in the early stage of the fire and must be automatic so as to ensure speed and efficiency in their operation.
D-2.1.5 The smoke and fire venting system shall be designed in such a manner as to keep the temperature of the combustion products from the fire as low as possible, preferably below approximately 150°C.
D-2.1.6 Automatic venting systems are complementary to the fire extinguishing systems, and automatic sprinklers, where provided, should operate before the operation of the vents; otherwise, venting may delay sprinkler operation.
D-2.1.7 It is easier to vent a building of smoke than clear it of smoke once it has been filled.
D-2.1.8 Venting is particularly desirable in large area industrial buildings or warehouses, windowless buildings, underground structures or in areas housing hazardous operations. Automatic fire vents shall be provided for all industrial occupancies (including storage buildings) classified as medium hazard or above having floor areas exceeding 750 m2, irrespective of whether they are compartmentalized or not.
D-2.1.9 These provisions do not cover other aspects, of ventilation (or lighting) designed for regulation of temperature within a building for personal comfort or meeting process needs.
D-2.4 Vent Operation
D-2.4.1 The vents shall be automatic in operation, unless where specified in these provisions that they shall be designed for both manual and automatic operation.
D-2.4.2 The release mechanism shall be simple for operation and independent of electrical power, since electrical services may be interrupted by fire.
D-2.4.3 The automatic operation of vents shall be achieved by actuation of fusible links or other types of heat and smoke detectors, or by interlocking with operation of sprinkler system or any other automatic fire extinguishing system covering the area. Following their release, the vents shall be designed to open by a system of counterweights and associated equipment utilizing the force of gravity or spring loaded levers.
D-2.4.4 Automatic fire alarm system, where installed, shall be coupled to the automatic vents to ensure simultaneous operation.
D-2.4.5 Automatic sprinklers, where installed, shall operate before the vents open in order to avoid any likely delay in sprinkler operation. However, heat actuated devices used for vent release shall be suitably shielded from sprinkler discharge so that water does not delay their action.
D-2.4.6 Premises where height of roof apex is 10 m or more or where the materials handled or stored have high smoke producing characteristics, in addition to fusible links, the vent release mechanism shall be interlinked to smoke actuated automatic fire detectors to ensure early operation of vents.
D-2.4.7 Non-corrosive materials shall be used for hinges, hatches and other related parts to ensure long fail-safe operation of the vents.
D-2.4.8 In case of any doubts regarding the types of vents required to be installed for any particular
occupancy, authorities having jurisdiction shall be consulted.
D-2.3 Types of Vents
D-2.3.1 Venting shall be accomplished by any of the types such as monitors continuous gravity vents, until type vents or sawtooth roof skylights.
D-2.3.2 Where monitor type vents are installed, wired glass or metal panels shall be used only if the sash is arranged to open automatically.
D-2.3.3 The use of plain thin glass for venting shall be avoided on account of its unpredictable behaviour during fire. However, if glass or other suitable plastic sheet materials with early disintegration characteristics are used, they should be designed for automatic operation.
D-2.3.4 Where monitors or unit type vents are used, the panels shall be hinged at the bottom and designed to open automatically. Both sides of the vents shall be designed to vent simultaneously to ensure that their effectiveness at the time of fire is not in any way impeded by wind direction.
D-2.3.5 Where movable shutters are provided for continuous gravity vents, these shall open automatically in the event of fire.
D-2.3.6 Unit type vents shall be of relatively small area, ranging between 1 m2 and 9 m2, having light weight metal frames and housing with hinged dampers
which shall be designed for both manual and automatic operation.
D-2.3.7 Sawtooth roof skylight shall be considered as satisfactory for venting purposes only when designed for automatic operation.
D-2.3.8 Likewise, exterior wall windows shall not be reckoned as satisfactory means for venting of fire gases and smoke in industrial buildings. However, they may be reckoned as additional means of venting when, they are located close to the eaves and are provided with ordinary glass or movable sash arranged for both manual and automatic operation.
D-2.3.9 Baffles shall not be installed inside vents, as they greatly reduce the effective area for venting.
D-2.5 Size, Spacing and Disposition of Vents
D-2.5.1 Vents shall be correctly sited to ensure their functional efficiency. Ideally, they shall be sited at the highest point in each area to be covered.
D-2.5.2 They shall, as far as possible, be located immediately above the risk to be protected so as to allow free and speedy removal of smoke and other combustion products in the event of fire.
D-2.5.3 The minimum dimension for an effective vent opening shall be not less than 1.25 m in any direction.
D-2.5.4 The spacing of the individual vents shall be based on the principle that more number of well distributed smaller vents are more effective than less number of badly located larger vents.
D-2.5.5 The maximum spacing between vents for the three occupancy classifications shall be as follows:
a) Low heat release content — 45 m between centres
b) Moderate heat release content — 36 to 37 m between centres
c) High heat release content — 22.5 to 30 m between centres, depending on the severity of fire potential.
D-2.5.6 Vents shall be placed in a sheltered situation where advantage can be taken of the prevailing wind. The design of the vent shall be such as to produce a suction effect. A wind blowing across a flat roof or one with a pitch be 40° produces a negative pressure, that is, it tends to draw gases out of the building and so aids venting of hot gases. Wind blowing across a roof of pitch greater than 40° will draw gases out on the leeward side, but oppose outward flow on the windward side of the roof.
D-2.5.7 Low level inlets, with total area not less than the total area of vents, shall be provided to permit outside air to be drawn in to aid automatic venting. These inlets, which may be in the form of doors, windows or such other openings, shall be designed for manual operation when desired.
D-2.2 Venting Area
D-2.2.1 The estimated requirements for ventilation are
largely based on the assumed build-up of the fire from the time of initial outbreak to the time of effective fire fighting action by fire brigade.
D-2.2.2 The vent area required to be provided shall be approximately proportional to the perimeter of the fire area, because the entrained air forms the bulk of the vented gases.
D-2.2.3 The effective area shall be the minimum cross-sectional area through which the hot gases must flow out to the atmosphere.
D-2.2.4 No consideration shall be given to the increased air movement obtained by power operated fans, since it must be assumed that in the event of fire, power will be interrupted, or fans damaged by heat.
D-2.2.5 The total vent areas to be provided shall be as per the following ratios of effective area of vent openings to floor area for various occupancy classifications indicated:
a) Low heat release content 1:150 (Sub-division G-1)
b) Moderate heat release content 1:100 (Sub-division G-2)
c) High heat release content 1:30 to 1:50 (Sub-division G-3)
D-2.6 Roof Screens or Curtain Boards
D-2.6.1 Industrial buildings with large areas and having no sub-division/separating walls limiting the area of individual compartments to 750 m2 or less, shall be provided with roof screens or curtain boards.
These screens which extend from the roof downwards at specific intervals not only prevent lateral spread of heat and smoke in the event of fire below, but
substantially assist in early operation of automatic sprinklers and vents.
D-2.6.2 They shall be of sheet metal or any other substantial non-combustible material strong enough to withstand damage by heat or impact.
D-2.6.3 They shall be reasonably gas-tight, although small openings for passage of pipes, conduits, etc, shall be permitted.
D-2.6.4 They shall extend down from the roof/ceiling for a minimum depth of 2.2 m. Around specific hazards, the depth shall be 4 m. Where roof/ceiling height exceeds 15 m they shall extend down to within 3 m of the floor. For pitched sawtoothed roofs, they shall extend down to truss level dividing the roof into compartments.
D-2.6.5 In moderate hazard occupancies, the distance between the screens/curtain boards shall not exceed 75 m and the curtained areas shall be limited to a maximum of 4 500 m2.
D-2.6.6 In high hazard occupancies, the distance between screens shall not exceed 30 m and the curtained area shall be limited to 750 m2.
D-2.6.7 The curtained roof area shall be so arranged that they effectively aid in the venting of smoke and hot gases through the automatic vents provided in each area.
D-2.6.8 In sprinklered buildings, the screens shall preferably be so located as to coincide with the individual sprinkler system areas.
D-3 Explosion Relief Vents
D-3.1 Industrial premises where combustible dusts can accumulate or where flammable gases, vapours or mists in explosive concentrations may be present are constantly exposed to explosion hazards. Pressures developed by such explosions may be of the order of 7 × 105 Pa and ordinary buildings will not be able to withstand the shock of such pressures. Hence, such buildings require explosion relief vents for preventing structural damage.
Annex EGuidelines for Fire Drill and Evacuation Procedures for High Rise Buildings (above 15 M in Height)
E-1 Introduction
In case of fire in a high rise building, safe evacuation of its occupants may present serious problems unless a plan for orderly and systematic evacuation is prepared in advance and all occupants are well drilled in the operation of such plan. These guidelines are intended to assist them in this task.
E-2 Alarms
Any person discovering fire, heat or smoke shall immediately report such condition to the fire brigade, unless he has personal knowledge that such a report has been made. No person shall make, issue, post or maintain any regulation or order, written or verbal, that would require any person to take any unnecessary delaying action prior to reporting such condition to the fire brigade.
D-3.2 Basic Principle/Considerations
D-3.2.1 Most ordinary building walls will not withstand a sustained internal pressure as great as 6.9 × 103 Pa. Hence, explosion relief vents for buildings must be designed to operate at pressures well below those at which the building walls will fail.
D-3.2.2 There is a rise in pressure during an explosion within an enclosure even with open, unobstructed vents, and any delay in opening the venting devices increases that pressure.
D-3.2.3 Structural damage can be minimized by locating hazardous operations or equipment outside buildings and cut off from other operations by a pressure resisting wall. Such isolated processes or equipment shall be housed in single-storey buildings properly vented and a device provided at the inlet of the collector which will prevent an explosion from blowing back through the duct work and into the building.
D-3.2.4 Where highly hazardous operations cannot be located outside of main buildings they shall be segregated by pressure resisting walls and each such unit shall be ventilated outdoors. External walls may be of heavy construction if equipped with suitable vents or high weight panels which blow out easily.
D-3.2.5 Operations or equipment involving explosion hazards shall not be permitted in basements or areas partially below grade.
D-3.2.6 Fire can be expected to follow an explosion in most occupancies, so that any fixed fire extinguishing equipment, like sprinklers, if installed, shall be such that only the minimum damage is caused to it.
D-3.2.7 For a given material, the finer the particle size of the dust, the more violent is the explosion. Some materials, such as aluminium powder, hydrogen, and acetylene, are difficult to vent effectively due to the rapid rate of pressure rise. Some slow burning materials, such as coal dust in a confined space, may do much damage because of the longer duration of their presence. Some dusts, such as magnesiusm, titanium and zirconium and several metal hydrides may react with water and ignite in some common inert gases, such as nitrogen and carbon dioxide.
D-3.2.8 The maximum explosion pressure in a vented structure decreases as the size of the vent increases, but is independent of the rupturing pressure of a diaphragm.
D-3.2.9 The most effective vent for the release of explosion pressures is an unobstructed vent opening.
D-3.2.10 Pressure required to rupture diaphragms of the same area and material directly varies with the thickness of the material.
D-3.2.11 The slower the rate of pressure rise, the more easily can the explosion be vented.
D-3.4 Design, Size and Disposition of Vents
D-3.4.1 The required area of explosion vents shall ordinarily depend on the expected maximum intensity of an explosion in the occupancy, the strength of the structure, the type of vent closure and other factors.
D-3.4.2 Venting shall be planned in such a manner as
to prevent injury to personnel and damage to explosures. In congested locations, substantial ducts or diverters shall be provided to direct the blast.
D-3.4.3 When ductwork is used, the ducts shall be of sufficient strength to withstand the maximum expected explosion pressure.
D-3.4.4 Where explosions are likely within duct and piping systems, they shall be vented by the use of suitable diaphragms designed to blow out at a predetermined pressure. There shall be no physical connection between ductwork system for more than one collector.
D-3.4.5 In large structures, the position of vents shall be relative to the point of origin of explosion, when it can be determined.
D-3.4.6 Where relatively slow explosions involving coal dust, chlorinated solvents, etc, are involved, light, hinged swinging panels may be preferred to diaphragm type of vents.
D-3.4.7 Obstructions of any kind blocking the vents from the risk covered shall be avoided, particularly where risks of rapid violent explosions are present.
D-3.4.8 Counter weights add to the inertia of the vents and so shall be avoided.
D-3.4.9 Various relieving devices, including devices actuated by detonators, shall start to open at as low a pressure as possible. They shall be of light construction, so that full opening can be quickly attained.
D-3.4.10 Vents shall be of such size and design as to prevent rupture of the protected device or apparatus.
D-3.4.11 Skylights or monitors with movable sash that will open outwards, or fixed sash containing panes of glass or plastic that will blow out readily under pressure from within, can be used to supplement wall vents or windows, provided resistance to their displacement or opening is kept as low as consistent with the requirements for structural strength.
D-3.4.12 Flexible plastic sheets when used for vent closures shall be installed in slotted frames in such a way that pressure from within bulges the sheets and releases them from the holding frame.
D-3.4.13 Fragile sheets made of plastic, when used for vent closures, shall be thin sheets that will crack or rupture under less pressure than single strength glass. For this reason use of transparent or translucent plastic sheets is more advantageous instead of glass in window sash.
D-3.3 Types of Explosion Relief Vents
D-3.3.1 The explosion relief vents shall be any one or more of the following types, depending on individual requirements as assessed by the Authority. Open or unobstructed vents, louvers, open roof vents, hanger type doors, building doors, windows, roof or wall panels or movable fixed sash.
D-3.3.2 The effect of external wind pressure or suction on these devices shall be taken into consideration while designing and selecting the type of vents, since wind pressures may reach over 2 × 105 Pa in severe wind storms.
D-3.3.3 The type of vent for explosion relief for any occupancy shall be selected with life safety as the primary aim followed by minimum damage to property.
D-3.3.4 Where large hanger type doors or metal curtain doors in side walls are used as vents care shall be taken to ensure that they are kept wide open during operations.
D-3.3.5 Where weather hoods are used to cover roof vents, they shall be as light as possible and lightly attached so as to enable them to be blown off quickly when an explosion occurs.
D-3.3.6 Doors and windows when used as explosion vents shall be installed to swing outwards. Doors shall have friction, spring or magnetic latches that will function automatically to permit the door to open under slight internal pressure.
D-3.3.7 Movable sash shall be of the top or bottom hinged or protected type. These shall be equipped with a latch or friction device to prevent accidental opening due to wind action or intrusion. Such latches or locks shall be well maintained.
D-3.3.8 Fixed sash shall be set in place with very light wall anchorages, or, if right, shall be securely fitted and glazed with plastic panes in plastic putty.
D-3.3.9 Where the process is such that the whole of a building or a room may be desirable to arrange for a lightly constructed wall or roof to collapse and thus avert the worst effects of an explosion.
6.4.6.8 The stage roof of every theatre using movable scenery or having a motion picture screen of highly combustible construction shall have a ventilator or ventilators in or above it, openable from the stage floor by hand and also opening by fusible links or some other approved automatic heat/smoke actuated device, to give a free opening equal to at least one-eighth the area of the floor of the stage.
6.4.6.9 The proscenium wall of every theatre using movable scenery of decorations shall have, exclusive of the proscenium opening, not more than two openings entering the stage, each not to exceed 2 m2 and fitted with self-closing fire resistant doors.
6.4.6.10 Every place of assembly in which projection of motion pictures by light is made shall have the projection apparatus enclosed in a fire-resisting fixed booth in accordance with good practice [4(27)], except that such booth shall not be required where no nitrocellulose motion picture film is used.
6.4.6.11 Automatic smoke vents actuated by smoke detectors shall be installed above the auditorium or theatres, including motion picture houses, with vent area equal to not less than 3 percent of the floor area of the auditorium, including the sum of the floor areas of all balconies, galleries, boxes and tiers. It may be desirable to provide a large number of small vents rather than a small number of large vents.
6.4.8.4 Detectors
Detectors are required to be provided only in areas where there are false ceiling and false floor and areas of equipment rooms. Wherever there are false ceiling, the detectors should be provided both above and below
false ceiling giving due consideration to depth of false ceiling/flooring. However, in concourse, the detectors below false ceiling may not be effective due to heights/ cross ventilation and therefore may not be provided. In other areas, because of high heights and cross-ventilations, detectors will not be effective and hence therefore can be dispensed. A conventional detection system will suffice at a normal station.
6.4.8.5 Manual call box
Manual call box should be provided at a central place on each platform (near emergency plunger) and at least two on the concourse, on each sidewall. When the concourse in two halves there should be one manual call box on each side.
6.4.8.6 Manual panel gas flooding
Electric panels should have provision of manual gas flooding. Alternatively panels can be provided with linear heat sensing tubes with CO cylinder. This required to be provided only in main power panels, that is HT panel, main LT panel, main LT distribution board and essential power panels and other such major panels.
6.4.8.7 External area of the station
A ‘two way/four way’ fire brigade inlet to be provided at ground level on each rising main for hydrants/ sprinkles.
The ‘Draw Off Connection’ shall be provided on the underground tank for fire brigade.
6.4.8.8 Water tank capacity
Capacity of fire tanks at stations without any commercial development (Beverage stall/ATM/Florist/ Book stalls up to total 250 m2 excluded) shall be 50 000 litres.
However, at stations having commercial development, the fire tank capacity shall be 100 000 litres.
6.4.8.9 Portable fire extinguishers
For the purpose of standardization, the following portable extinguishers are recommended:
a) Water CO2 type 9 litres
b) CO fire extinguishers 4.5 kg
They shall be provided in various areas as detailed hereunder:
SlNo.(1)
Item(2)
Numbers and Location(3)
PLATFORM
1.
Internal Hydrants
Two at each platform. The hydrants at two platforms may be staggered for maximum coverage.
2.
Manual call box
One on each platform preferably near emergency plunger.
3.
Portable Extinguishers
One set of Water CO2 and CO2 type on each platform at a central area.
CONCOURSE
1.
Internal Hydrants
Two at each concourse. When concourse is in two parts then each part should have at least one hydrant.
2.
Additional first-aid reel point
Additional first-aid reel point for every additional 1000 m2, if the area is more than 2000 m2. Similarly, if the concourse is in two parts then additional first aid reel point for every additional 1000 m2, if the area of the part is more than 1000 m2.
3.
Manual call box
Two at each concourse. When concourse is in two parts then each part should have at least one.
4.
Portable Extinguishers
Two sets at each concourse. When concourse is in two parts then each part should have at least one set.
5.
Detectors
Above false ceiling where depth of false ceiling is greater than 800 mm. Required in commercial areas also.
EQUIPMENT ROOM AREAS
1.
Internal Hydrants/first-aid reel point
The requirement shall get covered with platform/concourse. Additional first-aid reel point may be provided, if required.
2.
Manual call box
One at a central place. When the equipment rooms are in two/more parts then each part should have one.
3.
Portable Extinguishers
One set for each room.
4.
Detectors
Above and below false ceiling and below floor giving due consideration to depth of false ceiling/floor.
5.
Response Indicator
To be provided.
6.
Panel gas flooding
To be provided for HT panel, main LT panel, main LT distribution board and essential power panels and other such major panels.
EXTERNAL AREAS
1.
Hydrants
One at ground floor at each entry to station near staircase/DG room.
2.
Two/four way fire brigade inlet
To be provided for each riser/sprinkler riser.
3.
Fire brigade Draw-off connection
To be provided on water tank.
48.4
2.75
Polystyrene
41.8
2.38
Polyvinylchloride
20.9
1.19
Polymethylmethacrylate
24.6
1.40
Polyurethane
35.2
2.00
Polyamide (nylon)
22.0
1.25
Polyester
22.0
1.25
Common Solids
Asphalt
38.3
2.13
Bitumen
33.4
1.90
Carbon
32.1
1.83
Cotton (Dry)
15.8
0.90
Flax
14.3
0.81
Furs and Skins
18.7
1.06
Hair (animal)
20.9
1.19
Leather
17.6
1.00
Table 25 — Concluded
(1)
(2)
(3)
Ozokerite (wax)
43.3
2.46
Paper (average)
15.4
0.88
Paraffin wax
40.9
2.33
Pitch
33.0
1.88
Rubber
37.4
2.13
Straw
13.2
0.75
Tallows
37.6
2.14
Tan bark
20.9
1.19
Tar (bituminous)
35.2
2.00
Wool (raw)
21.6
1.23
Wool (scoured)
19.6
1.11
Foodstuffs
Barely
14.1
0.80
Bran
11.0
0.63
Bread
9.9
0.56
Butter
29.5
1.68
Cheese (Cheddar)
18.1
1.03
Cornmeal
14.1
0.80
Flour
14.1
0.80
Margarine
29.5
1.68
Oatmeal
15.8
0.90
Rice
13.9
0.79
Soyabean Flour
16.1
0.91
Sugar
15.4
0.88
Whole Wheat
14.3
0.81
Miscellaneous
Acetone
29.7
1.69
Acetaldehyde
25.1
1.43
Formaldehyde
17.6
1.00
Hydrogen
134.2
7.63
Magnesium
24.0
1.36
¹⁾ 1 kJ is approximately equal to 1 Btu so the figures in the tables are also equivalent to Btu/kg,
A-2 The typical values fire load density for arriving at the classification of occupancy hazard is given in Table 26 for guidance.
Table 26Typical Values of Fire Load Density
Sl Building Type Fire Load Density (Expressed No. as Wood Equivalent kg/m<sup>2</sup>(1) (2) (3)
i) Residential (A-1 and A-2) 25 ii) Residential (A-3 to A-5) 25 iii) Institutional and 25 Educational (B and C) iv) Assembly (D) 25-50 v) Business (E) 25-50 vi) Mercantile (F) Up to 250 vii) Industrial (G) Up to 150 viii) Storage and Hazardous Up to 500 (H and J)
(Clauses 3.1.8 and 3.1.11)
r) Inspection panels shall be provided in the main trunking to facilitate the cleaning of ducts of accumulated dust and to obtain access for maintenance of fire dampers.
s) No combustible material shall be fixed nearer than 150 mm to any duct unless such duct is properly enclosed and protected with non-combustible material (glass wool or spunglass with neoprene facing enclosed and wrapped with aluminimum sheeting) at least 3.2 mm thick and which would not readily conduct heat.
The first-aid fire fighting equipment shall be provided on all floors, including basements, lift rooms, etc, in accordance with good practice [4(21)] in consultation with the Authority.
D-2.1.10 Similarly, fire and smoke venting requirements as given here under are also not applicable to multi-storey buildings, as their requirements are different and more complex.
D-2.1.11 It is difficult to determine precise venting requirements on account of the many variables involved. For instance, the rate of combustion varies appreciably according to the nature, shape, size and
packaging of the combustible materials as well as the size, height and disposition of the stacks of materials.
D-2.1.12 In industrial buildings of floor area less than 750 m2 and used as low fire hazard occupancies, conventional ventilators fitted high up near the eaves of the external walls may serve as vents for smoke and hot gases, provided care is taken to ensure that they are kept open at all times or are designed to open automatically in case of fire.
D-2.1.13 Extinction of fires by closing the doors and windows is not likely in the case of industrial buildings because of their large size, where sufficient air to sustain the fire at least in the initial stages can be expected to be present.
D-2.1.14 Of the two types of building ventilation, namely, vertical and horizontal, vertical ventilation is the one commonly adopted in the case of single storey industrial buildings.
D-2.1.15 Since 70 to 80 percent of heat produced in a fire is convective heat, the ventilation system has to be suitably designed to ensure early outflow of the heat and thereby minimize fire spread.
D-2.1.16 Combustible roof linings shall be avoided, as they themselves will contribute to the spread of fire, thereby multiplying the venting problems.
D-2.1.17 A wind blowing across a flat roof or a roof with a pitch under 40° produces a negative pressure, that is, it tends to draw gases out of the building and so aids venting of hot gases. Wind blowing across a roof of pitch greater than 40° will draw gases out on the leeward side, but oppose outward flow on the windward side of the roof.
D-2.1.18 For vents to work at full efficiency, the area of the inlets for cold air entering the compartment must equal at least the total area of the vents. Ideally, the inlets shall be as close to the ground as possible.
D-2.1.19 Where roof vents are installed in a singlestorey building any neighbouring buildings, particularly those of more than one storey, will be subject to some degree of exposure hazard either from flying birds or radiation, or both, as a result.
D-2.1.20 If vents are to be installed, the size, design, number and disposition of the vents and the associated roof screens/curtain boards have to be assessed after careful analysis of the various factors stated under D-2.1.11 above, as well as other related factors like type of building construction, nature and height of roof, process hazards, exposure hazard, etc.
D-3.2.12 The degree of venting required is directly proportional to the degree of explosion hazard.
D-3.2.13 Experience has shown that most explosions of dusts, vapours and gases do not involve a large part of the total volume of the enclosure, and frequently occur near the upper or lower limits of the explosive range. Consequently, such explosions are relatively weak compared with the optimum.
D-3.2.14 Rectangular unrestricted vents are as effective as square vents of equal area.
D-3.4.14 If closed vents are used they shall be larger in area than unenclosed vents to provide equivalent explosion pressure relief.
D-3.4.15 Small enclosures, such as machines, shall be vented more generously than buildings, because if an explosion occurs in a machine, its entire volume may be involved.
D-3.4.16 Vents for the protection of buildings and equipment shall be installed on the following basis:
D-3.4.16.1 Small enclosures of less than 30 m3, machines and ovens of light construction: 1 000 cm2 for each 0.3 m3 to 0.9 m3.
D-3.4.16.2 For small enclosures of more substantial construction having reasonably high bursting strength: 1 000 cm2 for each 0.9 m3.
D-3.4.16.3 Fairly large enclosures of 30 to 700 m3, such as bins, silos, rooms, storage tanks, etc: 1 000 cm2 for each 0.9 m3 to 1.5 m3. In these cases, attempt shall be made to the extent possible to predict the likely point of origin of the explosion in relation to the vent.
D-3.4.16.4 Large rooms and buildings over 700 m3 containing hazardous equipment comprising a small fraction of the entire volume:
a) For heavy reinforced concrete, walls — 100 cm2 for each 2.25 m3.
b) For light reinforced concrete, brick or wood construction — 1 000 cm2 for each 1.65 m3 to 2.25 m3.
c) For lightweight construction such as prefabricated panels — 1 000 cm2 for each 1.5 m3 to 1.65 m3.
D-3.4.16.5 Large rooms or building over 700 m3 containing hazardous equipment comprising a large part of the entire volume of a room or building shall be vented as generously as possible 1 000 cm2 for each 0.3 m3 to 1.05 m3.
D-3.4.16.6 In order to obtain these ratios, the size of the building or room must be limited. For some hazardous materials, such as hydrogen, acetylene, carbon disulphide, etc, these limits are extremely low.
D-3.4.17 Emphasis shall always be placed on segregating hazardous areas by means of firewalls or separating walls to prevent spread of fire.
D-3.4.18 Interior walls of light construction, such as tile, shall be avoided in hazardous locations, since they can cause injuries to personnel in the event of an explosion.