This Part deals with the development control rules and general building requirements to ensure health and safety of the public.
this in view, many city development agencies have evolved innovative planning and development tools like transferable development rights (TDR) where the developer would receive a portion of the development rights in a new location, keeping in view the constraints in the existing land area and the development potential. Such development rights can be transferred into outskirts or new developed areas where land availability is assured. This would encourage the professionals and developers to participate in urban renewal and at the same time ensure that the developments in both the inner core areas and new areas take place in an orderly and efficient manner. The TDR concept should be increasingly encouraged by the authority dealing with urban renewal, redevelopment projects including housing and re-development projects for slum including dwellers.
Urbanization in India is taking place at a rapid pace. With 5 million population in cities at the time of independence, it has already crossed 28 million (2001 census). It is likely to be 50 million by 2021. The number of cities and towns have been expanding and there are 5 161 cities and towns of various sizes. In the Indian practice cities over 50 lakhs population have been identified as mega-cities (6 in number) and cities over 10 lakhs (29 in number) population as metro-cities. These 35 cities above 10 lakhs population is likely to be above 70 by 2021. The other cities are either small or medium towns or cities with different population limits. Urbanization in each of above cities and towns (mega-cities, metro-cities, small and medium towns and cities) will be different in nature and the development challenges are also different keeping in view the extent of urbanization, industrialization, commercialization and the nature of transportation needs. Therefore, the Code provisions should be appropriately utilized depending upon the need of hierarchy of cities for which the administrative and technical requirements have been covered in the Code for various facets of the activity.
The first version of this Part was prepared in 1970. As a result of incorporation of this Part in the revised development control rules and building byelaws of some municipal corporations and municipalities, some useful suggestions had emerged. First revision of this part was brought out in 1983, where these suggestions were incorporated to the extent possible. The major modifications incorporated in the first revision included:
a) Addition of development control rules giving guidance on means of access, community spaces and other aspects required for planning layouts.
b) Addition of provisions regarding plot sizes and frontage for different types of buildings, such as detached, semi-detached, row type and special housing schemes.
c) Requirements of open spaces for other occupancies, such as educational, institutional, assembly, industrial buildings, etc, were included.
d) Provisions relating to interior open space were elaborated, including requirements for ventilation shaft.
e) Requirements of open spaces for group housing development were covered.
f) Requirements of off-street parking spaces were covered.
g) Requirements for greenbelts and landscaping including norms for plantations of shrubs and trees were covered.
h) Requirements of certain parts of buildings, such as loft, store room, garage, basement, chimney, parapet, cabin, boundary wall, wells, septic tanks, office-cum-letter box room, meter room were included.
j) Special requirements of low income housing were covered.
The term Development Control Rules used in this Part encompasses the related aspects comprehensively with a view to promoting orderly development of an area.
This second revision is being brought out to incorporate the modifications found necessary in light of the experience gained with the use of this Part. Significant modifications incorporated in this revision include:
a) Terminology given in this Part has been made exhaustive by incorporating definitions of additional terms used, such as, access, chimney, to erect, etc, and number of terms pertaining to cluster planning for housing.
b) Detailed planning norms/open spaces for various amenities such as educational facilities, health care facilities, socio-cultural facilities, distribution services, police, civil defence and home guards, and fire services have been included.
c) Off-street parking requirements have now been also included for cities with population (i) between 1 000 000 and 5 000 000, and (ii) above 5 000 000 (see Annex B).
d) Special requirements for low income housing given in the earlier version have been modified and updated (see Annex C) based on IS 8888 (Part 1) : 1993 ‘Guide for requirements of low income housing:
Part 1 Urban area (first revision)’. In these revised provisions, single room dwelling has been discouraged, guidelines for water seal latrine have also been incorporated, and cluster planning approach has been recommended.
e) Requirements for cluster planning for housing have been added (see Annex E), which are based on the guidelines given in IS 13727 : 1993 ‘Guide for requirements of cluster planning for housing’.
f) Special requirements for low income housing for rural habitat planning has been added (see Annex F).
g) Special requirements for development planning in hilly areas has been added (see Annex G).
h) The requirements for buildings and facilities for the physically challenged have been revised, with listing of additional categories of physically challenged; modifications in requirements of ramps, stairs, doors, handrails and controls; and incorporation of additional requirements regarding windows.
j) Also, the opportunity has been utilized to update the reference to Indian Standards.
2.0 For the purpose of this part, the following definitions shall apply:
2.1 Access — A clear approach to a plot or a building.
2.2 Accessory Use — Any use of the premises subordinate to the principal use and customarily incidental to the principal use.
2.3 Alteration — A change from one occupancy to another, or a structural change, such as an addition to the area or height, or the removal of part of a building, or any change to the structure, such as the construction of, cutting into or removal of any wall, partition, column, beam, joist, floor or other support, or a change to or closing of any required means of ingress or egress or a change to the fixtures or equipment.
2.4 Approved — Approved by the Authority having jurisdiction.
2.5 Authority Having Jurisdiction — The Authority which has been created by a statute and which for the purpose of administering the Code/Part may authorize a committee or an official to act on its behalf; hereinafter called the ‘Authority’.
2.6 Back-to-Back Cluster — Clusters when joined back to back and/or on sides (see Fig. 1).

FIG. 1 BACK-TO-BACK CLUSTER
2.7 Balcony — A horizontal projection, with a handrail or balustrade or a parapet, to serve as passage or sitting out place.
2.8 Basement or Cellar — The lower storey of a building below or partly below ground level.
2.9 Building — Any structure for whatsoever purpose and of whatsoever materials constructed and every part thereof whether used as human habitation or not and includes foundation, plinth, walls, floors, roofs, chimneys, plumbing and building services, fixed platforms, VERANDAH, balcony, cornice or projection, part of a building or anything affixed thereto or any wall enclosing or intended to enclose any land or space and signs and outdoor display structures. Tents, SHAMIANAHS, tarpaulin shelters, etc, erected for temporary and ceremonial occasions with the permission of the Authority shall not be considered as building.
2.10 Building, Height of — The vertical distance measured in the case of flat roofs, from the average level of the ground around and contiguous to the building or as decided by the Authority to the terrace of last livable floor of the building adjacent to the external walls; and in the case of pitched roofs, up to the point where the external surface of the outer wall intersects the finished surface of the sloping roof; and in the case of gables facing the road, the mid-point between the eaves level and the ridge. Architectural features serving no other function except that of decoration shall be excluded for the purpose of measuring heights.
2.11 Building Envelope — The horizontal spatial limits up to which a building may be permitted to be constructed on a plot.
2.12 Building Line — The line up to which the plinth of a building adjoining a street or an extension of a street or on a future street may lawfully extend. It includes the lines prescribed, if any, in any scheme. The building line may change from time-to-time as decided by the Authority.
2.13 Cabin — A non-residential enclosure constructed of non-load bearing partition.
2.14 Canopy — A projection over any entrance.
2.15 Carpet Area — The covered area of the usable rooms at any floor level (excluding the area of the wall).
2.16 CHHAJJA — A sloping or horizontal structural overhang usually provided over openings on external walls to provide protection from sun and rain.
2.17 Chimney — An upright shaft containing one or more flues provided for the conveyance to the outer air of any product of combustion resulting from the operation of heat producing appliance or equipment employing solid, liquid or gaseous fuel.
2.18 Chowk or Courtyard — A space permanently
GROUP OPEN
open to the sky, enclosed fully or partially by building and may be at ground level or any other level within or adjacent to a building.
2.19 Chowk, Inner — A chowk enclosed on all sides.
2.20 Chowk, Outer — A chowk one of whose sides is not enclosed.
2.21 Closed Clusters — Clusters with only one common entry into cluster open space (see Fig. 2).
2.22 Cluster — Plots or dwelling units or housing grouped around an open space (see Fig. 3).
Ideally housing cluster should not be very large. In ground and one storeyed structures not more than 20 houses should be grouped in a cluster. Clusters with more dwelling units will create problems in identity, encroachments and of maintenance.
2.23 Cluster Court Town House — A dwelling in a cluster plot having 100 percent or nearly 100 percent ground coverage with vertical expansion, generally limited to one floor only and meant for self use.
2.24 Cluster Plot — Plot in a cluster.
2.25 Cooking Alcove — A cooking space having
direct access from the main room without any intercommunicating door.
2.26 Covered Area — Ground area covered by the building immediately above the plinth level. The area covered by the following in the open spaces is excluded from covered area (see Table 3):
a) Garden, rockery, well and well structures, plant nursery, waterpool, swimming pool (if uncovered), platform round a tree, tank, fountain, bench, CHABUTRA with open top and unenclosed on sides by walls and the like;
b) Drainage culvert, conduit, catch-pit, gully pit, chamber, gutter and the like;
c) Compound wall, gate, unstoreyed porch and portico, canopy, slide, swing, uncovered staircase, ramps areas covered by CHHAJJA and the like; and
d) Watchmen’s booth, pumphouse, garbage shaft, electric cabin or sub-stations, and such other utility structures meant for the services of the building under consideration.
NOTE — For the purpose of this Part, covered area equals the plot area minus the area due for open spaces.

FIG. 2 CLOSED CLUSTER

FIG. 3 CLUSTER
The land use classification may be as indicated below:
| Sl No. | Use Zone (Level 1) | Use Zone (Level 2) |
|---|---|---|
| (1) | (2) | (3) |
| i) | Residential (R) | Primary Residential Zone (R-1) Mixed Residential Zone (R-2) Unplanned/Informal Residential Zone (R-3) |
| ii) | Commercial (C) | Retail Shopping Zone (C-1) General Business and Commercial District/Centres (C-2) Wholesale, Godowns, Warehousing/Regulated Markets (C-3) |
| iii) | Manufacturing (M) | Service and Light Industry (M-1) Extensive and Heavy Industry (M-2) Special Industrial Zone Hazardous, Noxious and Chemical (M-3) |
| iv) | Public and Semi-Public (PS) | Government/Semi-Government/Public Offices (PS-1) Government Land (use determined) (PS-2) Educational and Research (PS-3) Medical and Health (PS-4) Social, Cultural and Religious (PS-5) Utilities and Services (PS-6) Cremation and Burial Grounds (PS-7) |
| v) | Recreational (P) | Playgrounds/Stadium/Sports Complex (P-1) Parks and Gardens - Public Open Spaces (P-2) Special Recreational Zone - Restricted Open Spaces (P-3) Multi-Open Space (Maidan) (P-4) |
| (1) | (2) | (3) |
| vi) | Transportation and Communication (T) | Roads (T-1)Railways (T-2)Airport (T-3)Seaports and Dockyards (T-4)Bus Depots/Truck Terminals and Freight Complexes (T-5)Transmission and Communication (T-6) |
| vii) | Agriculture and Water Bodies | Agriculture (A-1)Forest (A-2)Poultry and Dairy Farming (A-3)Rural Settlements (A-4)Brick Kiln and Extractive Areas (A-5)Water Bodies (A-6) |
| viii) | Special Area | Old Built-up (Core) Area (S-1)Heritage and Conservation Areas (S-2)Scenic Value Areas (S-3)Village Settlement (S-4)Other Uses (S-5) |
1 Areas of informal activities may be identified in the above land use categories at Level 2.
2 Mixed use zone may be identified at the development plan level, having more than one use zone with mixed activities of such use zones.
3 In all, there could be 35 use zones at the development plan level within eight land use categories at the perspective plan level as given in the above table.
4 Use premises for different activities could be provided at the project/action plan level or with the approval of the Authority as the case may be.
5 Use zone regulations for the use permissibility could be decided by the town planner depending upon the requirement/ feasibility.
3.2 The various building uses and occupancies (see 7) permitted on the various zones shall be as given in the Master Plan.
Where the use of buildings or premises is not specifically designated on the Development Plan or in the absence of Development Plan, shall be in conformity with the zone in which they fall.
Where the use of a site is specifically designated on the Development Plan, it shall be used only for the purpose so designated.
No plot shall be put to any use, occupancy or premises other than the uses identified in 3.1, except with the prior approval of the Authority.
Buildings shall be so planned, designed and constructed as to ensure fire safety and this shall be done as per Part 4 ‘Fire and Life Safety’.
Plots/dwelling units when located along a pedestrianised or vehicular ‘cul-de-sac’ road (see Fig. 4).

FIG. 4 CUL-DE-SAC CLUSTER
2.28 Density — The residential density expressed in terms of the number of dwelling units per hectare.
NOTE — Where such densities are expressed exclusive of community facilities and provision of open spaces and major roads (excluding incidental open spaces), these will be net residential densities. Where these densities are expressed taking into consideration the required open space provision and community facilities and major roads, these would be gross residential densities at neighbourhood level, sector level or town level, as the case may be. The provision of open spaces and community facilities will depend on the size of the residential community.
Incidental open spaces are mainly open spaces required to be left around and in between two buildings to provide lighting and ventilation.
2.29 Detached Building — A building detached on all sides.
2.30 Development — ‘Development’ with grammatical variations means the carrying out of building, engineering, mining or other operations, in, or over, or under land or water, on the making of any material change, in any building or land, or in the use of any building, land, and includes re-development and layout and subdivision of any land and ‘to develop’ shall be construed accordingly.
2.31 Drain — A conduit, channel or pipe for the carriage of storm water, sewage, waste water or other water borne wastes in a building drainage system.
2.32 Drainage — The removal of any liquid by a system constructed for the purpose.
2.33 Dwelling Unit/Tenement — An independent housing unit with separate facilities for living, cooking and sanitary requirements.
2.34 Escalator — A power driven, inclined, continuous stairway used for raising or lowering passengers.
2.35 Exit — A passage, channel or means of egress from any building, storey or floor area to a street or other open space of safety.
2.36 External Faces of Cluster — Building edges facing the cluster open spaces.
2.37 Fire Separation — The distance in metres measured from the external wall of the building concerned to the external wall of any other building on the site, or from other site, or from the opposite side of a street or other public space for the purpose of preventing the spread of fire.
2.38 Floor — The lower surface in a storey on which one normally walks in a building. The general term ‘floor’ unless specifically mentioned otherwise shall not refer to a ‘mezzanine floor’.
2.39 Floor Area Ratio (FAR) — The quotient obtained by dividing the total covered area (plinth area) on all floors by the area of the plot:
2.40 Gallery — An intermediate floor or platform projecting from a wall of an auditorium or a hall providing extra floor area, additional seating accommodation, etc. It shall also include the structures provided for seating in stadia.
2.41 Garage, Private — A building or a portion thereof designed and used for parking of private owned motor driven or other vehicles.
2.42 Garage, Public — A building or portion thereof, other than a private garage, designed or used for repairing, servicing, hiring, selling or storing or parking motor driven or other vehicles.
2.43 Group Housing — Housing for more than one dwelling unit, where land is owned jointly (as in the case of co-operative societies or the public agencies, such as local authorities or housing boards, etc) and the construction is undertaken by one Agency.
2.44 Group Open Space — Open space within a cluster.
Group open pace is neither public open space nor private open space. Each dwelling unit around the cluster open space have a share and right of use in it. The responsibility for maintenance of the same is to be collectively shared by all the dwelling units around.
2.45 Habitable Room — A room occupied or designed for occupancy by one or more persons for study, living, sleeping, eating, kitchen if it is used as a
living room, but not including bathrooms, water-closet compartments, laundries, serving and store pantries, corridors, cellars, attics, and spaces that are not used frequently or during extended periods.
2.46 Independent Cluster — Clusters surrounded from all sides by vehicular access roads and/or pedestrian paths (see Fig. 5).

FIG. 5 INDEPENDENT CLUSTER
2.47 Interlocking Cluster — Clusters when joined at back and on sides with at least one side of a cluster common and having some dwelling units opening onto or having access from the adjacent clusters.
Dwelling units in such clusters should have at least two sides open to external open space. Houses in an interlocking cluster can have access, ventilation and light from the adjacent cluster and should also cater for future growth (see Fig. 6).
2.48 Internal Faces of Cluster — Building edges facing the adjacent cluster open space (as in case of interlocking cluster) of the surrounding pedestrian paths or vehicular access roads.
2.49 Ledge or TAND — A shelf-like projection, supported in any manner whatsoever, except by means of vertical supports within a room itself but not having projection wider than 1 m.
2.50 Lift — An appliance designed to transport persons or materials between two or more levels in a vertical or substantially vertical direction by means of a guided car or platform. The word ‘elevator’ is also synonymously used for ‘lift’.
2.51 Loft — A structure providing intermediate storage space in between two floors with a maximum height of 1.5 m, without having a permanent access.
2.52 Mezzanine Floor — An intermediate floor between two floors of any storey forming an integral part of floor below.
2.53 Occupancy or Use Group — The principal occupancy for which a building or a part of a building is used or intended to be used; for the purposes of classification of a building according to occupancy; an occupancy shall be deemed to include subsidiary occupancies which are contingent upon it.
2.54 Occupancy, Mixed — The occupancy, where more than one occupancy are present in different portions of the building.
2.55 Open Clusters — Cluster where cluster open spaces are linked to form a continuous open space (see Fig. 7).
2.56 Open Space — An area, forming an integral part of the plot, left open to the sky.
NOTE — The open space shall be the minimum distance measured between the front, rear and side of the building and the respective plot boundaries.
2.57 Open Space, Front — An open space across the front of a plot between the building line and front boundary of the plot.
2.58 Open Space, Rear — An open space across the rear of a plot between the rear of the building and the rear boundary of the plot.
2.59 Open Space, Side — An open space across the side of the plot between the side of the building and the side boundary of the plot.

FIG. 6 INTERLOCKING CLUSTER

FIG. 7 OPEN CLUSTER
2.60 Owner — Person or body having a legal interest in land and/or building thereon. This includes free holders, leaseholders or those holding a sub-lease which both bestows a legal right to occupation and gives rise to liabilities in respect of safety or building condition.
In case of lease or sub-lease holders, as far as ownership with respect to the structure is concerned, the structure of a flat or structure on a plot belongs to the allottee/ lessee till the allotment/lease subsists.
2.61 Parapet — A low wall or railing built along the edge of a roof or floor.
2.62 Parking Space — An area enclosed or unenclosed, covered or open, sufficient in size to park vehicles, together with a drive-way connecting the parking space with a street or alley and permitting ingress and egress of the vehicles.
2.63 Partition — An interior non-load bearing barrier, one storey or part-storey in height.
2.64 Plinth — The portion of a structure between the surface of the surrounding ground and surface of the floor, immediately above the ground.
2.65 Plinth Area — The built up covered area measured at the floor level of the basement or of any storey.
2.66 Porch — A covered structure supported on pillars or otherwise for the purpose of pedestrian or vehicular approach to a building.
2.67 Road — See 2.82.
2.68 Road Line — See 2.84.
2.69 Room Height — The vertical distance measured from the finished floor surface to the finished ceiling surface. Where a finished ceiling is not provided, the underside of the joists or beams or tie beams shall determine the upper point of measurement.
2.70 Row Housing/Row Type Building — A row of buildings, with only front, rear and interior open spaces where applicable.
2.71 Semi-Detached Building — A building detached on three sides.
2.72 Service Road/Lane — A road/lane provided adjacent to a plot(s) for access or service purposes as the case may be.
2.73 Set-Back Line — A line usually parallel to the plot boundaries and laid down in each case by the Authority, beyond which nothing can be constructed towards the plot boundaries.
2.74 Site (Plot) — A parcel (piece) of land enclosed by definite boundaries.
2.75 Site, Corner — A site at the junctions of and fronting on two or more intersecting streets.
2.76 Site, Depth of — The mean horizontal distance between the front and rear site boundaries.
2.77 Site, Double Frontage — A site, having a frontage on two streets, other than a corner plot.
2.78 Site, Interior or Tandem — A site access to which is by a passage from a street whether such passage forms part of the site or not.
2.79 Staircover (or MUMTY) — A structure with a roof over a staircase and its landing built to enclose only the stairs for the purpose of providing protection from weather and not used for human habitation.
2.80 Storey — The portion of a building included between the surface of any floor and the surface of the floor next above it, or if there be no floor above it, then the space between any floor and the ceiling next above it.
2.81 Storey, Topmost — The uppermost storey in a building whether constructed wholly or partly on the roof.
2.82 Street — Any means of access, namely, highway, street, lane, pathway, alley, stairway, passageway, carriageway, footway, square, place or bridge, whether a thoroughfare or not, over which the public have a right of passage or access or have passed and had access uninterruptedly for a specified period, whether existing or proposed in any scheme, and includes all bunds, channels, ditches, storm-water drains, culverts, sidewalks, traffic islands, roadside trees and hedges, retaining walls, fences, barriers and railings within the street lines.
2.83 Street Level or Grade — The officially established elevation or grade of the central line of the street upon which a plot fronts and if there is no officially established grade, the existing grade of the street at its mid-point.
2.84 Street Line — The line defining the side limits of a street.
2.85 To Abut — To abut on a street boundary such that any portion of the building is on the road boundary.
2.86 To Erect — To erect a building means:
a) to erect a new building on any site whether previously built upon or not; and
b) to re-erect any building of which portions above the plinth level have been pull down, burnt or destroyed.
2.87 Tower-like Structures — Structures shall be deemed to be tower-like structures when the height of the tower-like portion is at least twice the height of the broader base at ground level.
2.88 VERANDAH — A covered area with at least one side open to the outside with the exception of 1 m high parapet on the upper floors to be provided on the open side.
2.89 Volume to Plot Area Ratio (VPR) — The ratio of volume of building measured in cubic metres to the area of the plot measured in square metres and expressed in metres.
2.90 Water-Closet (WC) — A water flushed plumbing fixture designed to receive human excrement directly from the user of the fixture. The term is used sometimes to designate the room or compartment in which the fixture is placed.
2.91 Window — An opening to the outside other than a door, which provides all or part of the required natural light or ventilation or both to an interior space.
4.1 Every building/plot shall abut on a public/private means of access like streets/roads duly formed.
4.2 Every person who erects a building shall not at any time erect or cause or permit to erect any building which in any way encroaches upon or diminishes the area set apart as means of access required in the Code. No buildings shall be erected so as to deprive any other building of the means of access.
The residential plots shall abut on a public means of access like street/road. Plots which do not abut on a street/road shall abut/front on a means of access, the width and other requirements of which shall be as given in Table 1.
| Sl No. | Width of Means of Access | Length of Means of Access |
|---|---|---|
| m | m | |
| (1) | (2) | (3) |
| i) | 6.0 | 75 |
| ii) | 7.5 | 150 |
| iii) | 9.0 | 250 |
| iv) | 12.0 | 400 |
| v) | 18.0 | 1 000 |
| vi) | 24.0 | above 1 000 |
NOTE — If the development is only on one side of the means of access, the prescribed widths may be reduced by 1 m in each case.
In no case, development on plots shall be permitted unless it is accessible by a public street of width not less than 6 m.
For all industrial buildings, theatres, cinema houses, assembly halls, stadia, educational buildings, markets, other buildings which attract large crowd, the means of access shall not be less than the following:
| Width of Means of | Length of Means |
|---|---|
| Access | of Access |
| m | m |
| 12.0 | 200 |
| 15.0 | 400 |
| 18.0 | 600 |
| 24.0 | above 600 |
Further, in no case shall the means of access be lesser in width than the internal accessways in layouts and subdivision.
The approach to the buildings from road/street/internal means of access shall be through paved pathway of width not less than 1.5 m, provided its length is not more than 30 m.
4.3.2.1 In the case of special housing schemes for low income group and economically weaker section of society developed up to two storeyed row/cluster housing scheme, the pedestrian pathway width shall be 3 m subject to provisions of 9.4.1(a). The pedestrian pathway shall not serve more than 8 plots on each side of the pathway; the length of the pathway shall be not more than 50 m.
4.3.3 The length of the main means of access shall be determined by the distance from the farthest plot (building) to the public street. The length of the subsidiary accessway shall be measured from the point of its origin to the next wider road on which it meets.
4.3.4 In the interest of general development of an area, the Authority may require the means of access to be of larger width than that required under 4.3 and 4.3.1.
4.3.5 In existing built-up areas in the case of plots facing street/means of access less than 4.5 m in width, the plot boundary shall be shifted to be away by 2.25 m from the central line of the street/means of accessway to give rise to a new street/means of accessway of 4.5 m width.
4.4 The means of access shall be levelled, metalled, flagged, paved, sewered, drained, chanelled, lighted, laid with water supply line and provided with trees for shade to the satisfaction of the Authority free of encroachment by any structure or fixture so as not to reduce its width below the minimum required under 4.3 and shall be maintained in a condition to the satisfaction of the Authority.
4.4.1 If any private street or any other means of access to a building is not levelled, metalled, flagged or paved, sewered, drained, channelled, lighted or laid with water supply line or provided with trees for shade to the satisfaction of the Authority, who may, with the sanction of the Authority, by written notice require the owner or owners of the several premises fronting or adjoining the said street or other means of access or abutting thereon or to which access is obtained through such street or other means of access or which shall benefit by works executed, to carry out any or more of the aforesaid requirements in such manner as he shall direct.
4.4.2 If any structure or fixture is set upon a means of access so as to reduce its width below the minimum required, the Authority may remove the same further and recover the expenses so incurred from the owner.
No premises other than highway amenities like petrol pumps, motels, etc, shall have an access direct from highways and such other roads not less than 52 m in width, which the Authority with the approval of the Highway Authority shall specify from time-to-time. The Authority shall maintain a register of such roads which shall be open to public inspection at all times during office hours. The portion of such roads on which direct access may be permitted shall be as identified in the Development Plan. However, in the case of existing development on highways/other roads referred to above, the operation of this clause shall be exempted. These provisions shall, however, be subject to the provisions of the relevant State Highway Act, and National Highway Act.
4.6 For high rise buildings and buildings other than residential, the following additional provisions of means of access shall be ensured:
a) The width of the main street on which the building abuts shall not be less than 12 m and one end of this street shall join another street not less than 12 m in width;
b) The approach to the building and open spaces on all its sides up to 6 m width and the layout for the same shall be done in consultation with the Chief Fire Officer of the city and the same shall be hard surface capable of taking the mass of fire engine, weighing up to 45 tonnes. The said open space shall be kept free of obstructions and shall be motorable.
c) The main entrance to the plot shall be of adequate width to allow easy access to the fire engine and in no case shall it measure less than 6 m. The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior accessway within the plot free for movement of fire service vehicle. If the main entrance at the boundary wall is built over, the minimum clearance shall be 4.5 m. A turning radius of 9 m shall be provided for fire tender movement.
4.7 Cul-de-sacs giving access to plots and extending from 150 m to 275 m in length with an additional turning space at 150 m will be allowed only in residential areas, provided cul-de-sacs would be permissible only on straight roads and further provided the end of cul-de-sacs shall be higher in level than the level of the starting point of such dead end road. The turning space, in this case shall be not less than 81 m2 in area, with no dimension less than 9 m.
For intersection junctions of roads meeting at right angles as well as other than right angles, the rounding off or cut off or splay or similar treatment shall be done, to the approval of the Authority, depending upon the width of roads, the traffic generated, the sighting angle, etc, to provide clear sight distance.
4.9 The building line shall be set back at least 3 m from internal means of access in a layout of buildings in a plot subject to provisions of 8.2.1.
In any layout or sub-division of land measuring 0.3 hectare of more in residential and commercial zones, the community open spaces shall be reserved for recreational purposes which shall as far as possible be provided in one place or planned out for the use of the community in clusters or pockets.
5.1.1 The community open spaces shall be provided
catering to the needs of area of layout, population for which the layout is planned and the category of dwelling units. The following minimum provision shall be made:
a) 15 percent of the area of the layout, or
b) 0.3 to 0.4 ha/1 000 persons; for low income housing the open spaces shall be 0.3 ha/1 000 persons.
5.2 No recreational space shall generally be less than 450 m2.
5.2.1 The minimum average dimension of such recreational space shall be not less than 7.5 m; if the average width of such recreational space is less than 24 m, the length thereof shall not exceed 2.5 times the average width. However, depending on the configuration of the site, commonly open spaces of different shapes may be permitted by the Authority, as long as the open spaces provided serve the needs of the immediate community contiguous to the open spaces.
5.2.2 In such recreational spaces, a single storeyed structure as pavilion or gymnasia up to 25 m2 in area may be permitted; such area may be excluded from FAR calculations.
5.3 Each recreational area and the structure on it shall have an independent means of access. Independent means of access may not be insisted upon if recreational space is approachable directly from every building in the layout. Further, the building line shall be at least 3 m away from the boundary of recreational open space.
In the case of sub-division of land in industrial zones of area 0.8 hectare or more, 5 percent of the total area shall be reserved as amenity open space which shall also serve as a general parking space; when such amenity open space exceeds 1 500 m2, the excess area could be utilized for the construction of buildings for banks, canteens, welfare centres and such other common purposes considered necessary for the industrial user, as approved by the Authority.
5.4.1 In all industrial plots measuring 1 000 m2 or more in area, 10 percent of the total area shall be provided as an amenity open space to a maximum of 2 500 m2. Such an amenity open space shall have a means of access and shall be so located that it could be conveniently utilized as such by the persons working in the industry.
In addition to community open spaces, the layouts shall provide for the amenities as given in 5.5.1 to 5.5.6. These provisions may be modified based on specific requirements, as decided by the Authority.
5.5.1 Educational Facilities
Land Area Required, Min
6.1 No building shall be constructed on any site, on any part of which there is deposited refuse, excreta or other offensive matter objectionable to the Authority, until such refuse has been removed therefrom and the
site has been prepared or left in a manner suitable for building purposes to the satisfaction to the Authority.
Wherever the dampness of a site or the nature of the soil renders such precautions necessary, the ground surface of the site between the walls of any building erected thereon shall be rendered damp-proof to the satisfaction of the Authority.
Any land passage or other area within the curtilage of a building shall be effectively drained by surface water drains or other means.
6.3.1 The written approval of the Authority shall be obtained for connecting any sub-soil or surface water drain to a sewer.
No VERANDAH, balcony, or the like shall be allowed to be erected or re-erected or any additions or alterations made to a building within the distances quoted below in accordance with the current Indian Electricity Rules as amended from time-to-time between the building and any overhead electric supply line:
| (1) (2) | Vertically m(3) | Horizontally m(4) |
|---|---|---|
| a) Low and medium voltage lines and service lines | 2.5 | 1.2 |
| b) High voltage lines up to and including 11 000 V | 3.7 | 1.2 |
| c) High voltage lines above 11 000 V and up to and including 33 000 V | 3.7 | 2.0 |
| d) Extra high voltage | 3.7 | 2.0 |
| line beyond 33 000 V | (plus 0.3 m | (plus 0.3 m |
| for every | for every | |
| additional | additional | |
| 33 000 V | 33 000 V | |
| or part | or part | |
| thereof) | thereof) |
6.5 Distance of site from the normal edge of water course/area may be specified by the Authority, keeping in view the normal maximum flood/tide level.
Each plot shall have a minimum size/frontage
corresponding to the type of development as given below:
| Type of Development | Plot Size m² | Frontage m |
| (1) | (2) | (3) |
| Detached building | Above 250 | Above 12 |
| Semi-detached building | 125-250 | 8 to 12 |
| Row type building | 50-125 | 4.5 to 8 |
| NOTE — For low income housing see 12.20. | ||
6.6.1.1 The minimum size of the site for group housing development shall be as given in the Master Plan and local development control rules.
The size of the plot shall not be less than 300 m2 and its width shall not be less than 15 m.
The minimum size of plots for buildings for other uses not covered under 5.5 shall be as decided by the Authority.
7.0 Buildings are classified based on occupancy and types of construction.
7.1 For the purpose of the Code, the following shall be the occupancy classification and types of construction; for more detailed information, reference may be made to Part 4 ‘Fire and Life Safety’.
a) Residential;
b) Educational;
c) Institutional;
d) Assembly;
e) Business;
f) Mercantile (will include both retail and wholesale stores);
Industrial (will include low, moderate and high fire hazards);
h) Storage; and
j) Hazardous.
a) Type 1,
b) Type 2,
c) Type 3, and
d) Type 4.
Every room intended for human habitation shall abut on an interior or exterior open space or an open VERANDAH open to such interior or exterior open space.
8.1.1 The open spaces inside and around a building have essentially to cater for the lighting and ventilation requirements of the rooms abutting such open spaces, and in the case of buildings abutting on streets in the front, rear or sides, the open spaces provided shall be sufficient for the future widening of such streets.
The open spaces shall be separate or distinct for each building and where a building has two or more wings, each wing shall have separate or distinct open spaces for the purposes of lighting and ventilation of the wings.
However, separation between accessory and main buildings more than 7 m in height shall not be less than 1.5 m; for buildings up to 7 m in height no such separation shall be required.
8.1.3 The open space shall be the minimum distance measured between the front, rear and side of the building and the respective plot boundaries. The front, rear and side of the building shall be the point of the building nearest to the boundary.
a) Every building fronting a street shall have a front space, forming an integral part of the site as below:
| Sl | Front Open Space, | Width of Street |
|---|---|---|
| No. | Min m | Fronting the Plot m |
| (1) | (2) | (3) |
| i) | 1.5<sup>1</sup>) | Up to 7.5<sup>1</sup>) |
| ii) | 3.0 | 7.5 to 18 |
| iii) | 4.5 | 18 to 30 |
| iv) | 6.0 | Above 30 |
NOTE — In case a building abuts two or more streets, the value of open paces is to be based on the average width of streets, subject to a minimum of 1.8 m for cases (ii), (iii) and (iv) above.
b) For streets less than 7.5 m in width, the distance of the building (building line) shall
be at least 5 m from the centre line of the street (see 4.3.5).
NOTE — This limiting distance has to be determined by the Authority for individual road/street widths taking into account the traffic flow.
a) Every residential building shall have a rear open space, forming an integral part of the site, of an average width of 3 m and at no place measuring less than 1.8 m, except that in the case of a back-to-back sites, the width of the rear open space shall be 3 m throughout. Subject to the condition of free ventilation, the open space left up to half the width of the plot shall also be taken into account for calculating the average width of the rear open space. For plots of depths less than 9 m, for buildings up to 7 m in height, the rear open space may be reduced to 1.5 m.
The rear open space shall be co-extensive with the entire face of the rear wall. If a building abuts on two or more streets, such rear open space shall be provided throughout the face of the rear wall. Such rear wall shall be the wall on the opposite side of the face of the building abutting on the wider street unless the Authority directs otherwise.
c) In case of corner plots less than 300 m2 in area, the rear open space should be 2.4 m minimum.
a) Every semi-detached and detached building shall have a permanently open air space, forming an integral part of the site as below:
NOTE — For detached residential buildings up to 7 m in height on plots with a frontage less than 12 m (see 6.6.1), one of the side open spaces may be reduced to 1.5 m.
NOTE — For semi-detached buildings up to 7 m in height on plots with a frontage less than 9 m (see 6.6.1), the side open spaces may be reduced to 1.5 m.
b) In the case of semi-detached buildings, the open spaces provided on one side shall be as
in 8.2.1.3 (a) and all habitable rooms shall abut either on this side open space or front and rear open spaces or an interior open space (see 8.2.5).
8.2.2 The provisions of 8.2.1.2 and 8.2.1.3 are not applicable to parking lock-up garages up to 3 m in height located at a distance of 7.5 m from any street line or front boundary of the plot.
8.2.3 The open spaces mentioned in 8.2.1.1 to 8.2.1.3 shall be for residential buildings up to a height of 10 m.
8.2.3.1 For buildings of height above 10 m, the open spaces (side and rear) shall be as given in Table 2. The front open spaces for increasing heights of buildings shall be governed by 9.4.1 (a).
| Sl No. | Height of Buildings | Side and Rear Open Spaces to be Left Around Building |
| m | m | |
| (1) | (2) | (3) |
| i) | 10 | 3 |
| ii) | 15 | 5 |
| iii) | 18 | 6 |
| iv) | 21 | 7 |
| v) | 24 | 8 |
| vi) | 27 | 9 |
| vii) | 30 | 10 |
| viii) | 35 | 11 |
| ix) | 40 | 12 |
| x) | 45 | 13 |
| xi) | 50 | 14 |
| xii) | 55 and above | 16 |
1 For buildings above 24 m in height, there shall be a minimum front open space of 6 m.
2 Where rooms do not derive light and ventilation from the exterior open space, the width of such exterior open space as given in col 3 may be reduced by 1 m subject to a minimum of 3 m and a maximum of 8 m. No further projections shall be permitted.
3 If the length or depth of the building exceeds 40 m, add to col (3) 10 percent of length or depth of building minus 4.0 m.
a) Up to a height of 24 m, with one set-back, the open spaces at the ground level, shall be not less than 6 m;
b) For heights between 24 m and 37.5 m with one set-back, the open spaces at the ground level, shall be not less than 9 m;
c) For heights above 37.5 m with two set-backs, the open spaces at the ground level, shall be not less than 12 m; and
d) The deficiency in the open spaces shall be made good to satisfy 8.2.3.1 through the setbacks at the upper levels; these set-backs shall not be accessible from individual rooms/flats at these levels.
8.2.4 The front open space would govern the height of the building (see 9.4).
a) Inner courtyard — In case the whole of one side of every room excepting bath, WC and store room is not abutting on either the front, rear or side open spaces, it shall abut on an inner courtyard, whose minimum width shall be 3 m.
Further, the inner courtyard shall have an area, throughout its height, of not less than the square of one-fifth the height of the highest wall abutting the courtyard. Provided that when any room (excluding staircase bay, bathroom and water-closet) is dependent for its light and ventilation on an inner courtyard, the dimension shall be such as is required for each wing of the building.
Where only water-closet and bath room are abutting on the interior courtyard, the size of the interior courtyard shall be in line with the provision for ventilation shaft as given in 8.2.5 (b).
b) Ventilation shaft — For ventilating the spaces for water-closets and bath rooms, if not opening on to front, side, rear and interior open spaces, these shall open on the ventilation shaft, the size of which shall not be less than the values given below:
| Height of | Size of | Minimum |
|---|---|---|
| Buildings | Ventilation Shaft | One Dimension of the Shaft |
| m | m<sup>2</sup> | m |
| (1) | (2) | (3) |
| Up to 10 | 1.2 | 0.9 |
| 12 | 2.8 | 1.2 |
| 18 | 4.0 | 1.5 |
| 24 | 5.4 | 1.8 |
| 30 | 8.0 | 2.4 |
| Above 30 | 9.0 | 3.0 |
1 For buildings of height above 30 m, a mechanical ventilation system shall be installed besides the provision of minimum ventilation shaft.
2 For fully air-conditioned residential buildings for lodging purposes, the ventilation shaft need not be insisted upon, provided the air-conditioning system works in an uninterrupted manner, also, provided there is an alternative source of power supply.
c) Outer courtyard — The minimum width of the outer courtyard (as distinguished from its depth) shall be not less than 2.4 m. If the width of the outer courtyard is less than 2.4 m, it shall be treated as a notch and the provisions of outer courtyard shall not apply. However, if the depth of the outer courtyard is more than the width, the provisions of 8.1.2 shall apply for the open spaces to be left between the wings.
Every such interior or exterior open air space, unless the latter is a street, shall be maintained for the benefit of such building exclusively and shall be entirely within the owner's own premises.
8.2.6.1 If such interior or exterior open air space is intended to be used for the benefit of more than one building belonging to the same owner, the width of such open air space shall be the one specified for the tallest building as specified in 8.2.3 abutting on such open air space.
8.2.6.2 If such interior or exterior open air space is jointly owned by more than one person, its width shall also be as specified in 8.2, provided every such person agrees in writing to allow his portion of such joint open air space to be used for the benefit of every building abutting on such joint open air space and provided he sends such written consent to the Authority for record. Such common open air space shall thenceforth be treated as a permanently open air space required for the purposes of the Code. No boundary wall between such joint open air space shall be erected or raised to a height of more than 2.0 m.
8.3.1 Open spaces for other occupancies shall be as below:
a) Educational buildings — Except for nursery schools, the open spaces around the building shall be not less than 6 m.
b) Institutional buildings — The open spaces around the building shall be not less than 6 m.
c) Assembly buildings — The open space at front shall be not less than 12 m and the other open spaces around the building shall be not less than 6 m.
NOTE — However, if assembly buildings are permitted in purely residential zones, the open spaces around the building shall be not less than 12 m.
d) Business, mercantile and storage buildings — The open spaces around the building shall be not less than 4.5 m. Where these occur in a purely residential zone or in a residential with
shops line zone the open spaces may be relaxed.
e) Industrial buildings — The open spaces around the building shall be not less than 4.5 m for heights up to 16 m, with an increase of the open spaces of 0.25 m for every increase of 1 m or fraction thereof in height above 16 m.
NOTE — Special rules for narrow industrial plots in the city, namely plots less than 15 m in width, and with appropriate set-backs from certain streets and highways, shall be applicable.
f) Hazardous occupancies — The open spaces around the building shall be as specified for industrial buildings [see 8.3.1 (e)].
Every open space provided either interior or exterior shall be kept free from any erection thereon and shall be open to the sky, except as below:
a) Cornice, roof or weather shade not more than 0.75 m wide;
b) Sunshades over windows/ventilators or other openings not more than 0.75 m wide;
c) Canopy not to be used as a sit out with clearance of 1.5 m between the plot boundary and the canopy;
d) Projected balcony at higher floors of width not more than 1.2 m; and
e) Projecting rooms/balconies [see (d)] at alternate floors such that rooms of the lower two floors get light and air and the projection being not more than the height of the storey immediately below.
However, these projections into open spaces shall not reduce the minimum required open spaces.
The following accessory buildings may be permitted in the open spaces:
a) In an existing building, sanitary block of 2.4 m in height subject to a maximum of 4 m2 in the rear open space at a distance of 1.5 m from the rear boundary may be permitted, where facilities are not adequate.
b) Parking lock up garages not exceeding 2.4 m in height shall be permitted in the side or rear open spaces at a distance of 7.5 m from any road line or the front boundary of the plot; and
c) Suction tank and pump room each up to 2.5 m² in area.
8.4.2.1 In existing built-up or congested areas, no projection of any sort whatsoever, except sunshades (see 8.4.2.3) extending more than 23 cm below a height of 4.3 m, shall project over the road or over any drain or over any portion outside the boundaries of the site, provided the projection arising out of the vertical part of the rain-water spouts projecting at the road level or the water pipe may be permitted in accordance with the drainage plan.
Porticos in bazaar areas of existing developed areas may be permitted to project on road land subject to the following limitations:
a) Porticos may be allowed on such roads leaving a minimum clear space of 18 m between kerbs;
b) The porticos shall not be less than 3 m wide;
c) Nothing shall be allowed to be constructed on the portico which shall be used as an open terrace;
d) Nothing shall be allowed to project beyond the line of arcades; and
e) The space under the portico shall be paved and channelled according to the directions of the Authority.
Projections of sunshades over windows or ventilators in existing built-up or congested areas when permitted by the Authority shall fulfil the following conditions:
No construction work on a building shall be allowed if such work operates to reduce an open air space of any other adjoining building, belonging to the same owner to an extent less than what is prescribed at the time of the proposed work or to reduce further such open space if it is already less than that prescribed.
Additions or extensions to a building shall be allowed, provided the open spaces for the additions/extensions satisfy 8.2 after such additions/extensions are made.
The limitation of area and height of buildings of different occupancy classes and types of construction shall be achieved by specifying it in terms of FAR, which shall take into account the various aspects that govern in specifying FAR as given below:
a) Occupancy class;
b) Types of construction;
c) Width of street fronting the building and the traffic load;
d) Locality where the building is proposed and the density;
e) Parking facilities;
f) Local fire fighting facilities; and
g) Water supply and drainage facilities.
9.2 The comparative FAR’s for different occupancies and types of construction are as given in Table 3 and the Authority shall select a basic FAR for one occupancy and a type of construction and arrive at the FAR values for other combinations taking into account the other local factors (see 9.1).
The minimum fire separation on all sides of buildings of unlimited areas (see Table 3) and of Type 1 construction shall be 9 m.
The area limits shall apply to all buildings fronting on a street or public space not less than 9 m in width accessible to a public street.
The height and number of storeys shall be related to FAR and the provisions of 8.
9.4.1 Where a building height is not covered by Table 3, the maximum height shall be limited according to the width of the street as follows:
a) The maximum height of building shall not exceed 1.5 times the width of road abutting plus the front open space;
b) If a building abuts on two or more streets of different widths, the building shall be deemed to face upon the street that has the greater width and the height of the building shall be
| Occupancy Classification | Type of Construction | |||
| Type 1(2) | Type 2(3) | Type 3(4) | Type 4(5) | |
| Residential | UL | 2.0 | 1.4 | 1.0 |
| Educational | UL | 2.0 | 1.4 | 1.0 |
| Institutional | UL | 1.5 | 1.0 | 0.8 |
| Assembly | UL | 1.0 | 0.7 | 0.5 |
| Business | UL | 2.9 | 2.3 | 1.6 |
| Mercantile | 8.0 | 1.8 | 1.4 | 1.0 |
| Industrial | 7.5 | 1.9 | 1.6 | 1.3 |
| Storage(see Note 4) | 6.0 | 1.5 | 1.3 | 1.0 |
| Hazardous(see Note 4) | 2.8 | 1.1 | 0.9 | NP |
UL — Unlimited
NP — Not Permitted
1 This table has been prepared, taking into account the combustible content in the different occupancies as well as the fire resistance offered by the type of construction (see Part 4 ‘Fire and Life Safety’).
2 This table shall be modified by the Authority, taking into account the other aspects as given below (see 9.1):
a) Density in terms of dwelling units/hectare;
b) Traffic considerations;
c) Parking spaces;
d) Local fire fighting facilities; and
e) Water supply, drainage and sanitation requirements.
3 The FAR specified may be increased by 20 percent for the following:
a) A basement or cellar and space under a building constructed on stilts and used as a parking space, and airconditioning plant room used as accessory to the principal use;
b) Electric cabin or sub-station, watchman’s booth of maximum size of 1.6 m2 with minimum width or diameter of 1.2 m, pumphouse, garbage shaft, space required for location of fire hydrants, electric fittings and water tank;
c) Projections and accessory buildings as specifically exempted (see 8.4.1); and
d) Staircase room and lift rooms above the topmost storey, architectural features; and chimneys and elevated tanks of dimensions as permissible under the Code; the area of the lift shaft shall be taken only on one floor.
4 In so far as single storey storage and hazardous occupancies are concerned, they would be further governed by volume to plot area ratio (VPR), to be decided by the Authority.
regulated by the width of that street and may be continued to this height to a depth of 24 m along the narrower street subject to conformity of 8; and
c) For buildings in vicinity of aerodromes, provisions of 9.5 shall apply.
The following appurtenant structures shall not be included in the height of the building unless the aggregate area of such structures, including penthouses, exceeds one-third of the area of the roof of building upon which they are erected:
a) Roof tanks and their supports (with support height not exceeding 1 m);
b) Ventilating, air-conditioning, lift rooms and similar service equipment;
c) Stair cover (MUMTY) not exceeding 3 m in height; and
d) Chimneys, parapet walls and architectural features not exceeding 1.2 m in height.
9.4.2.2 The building height for different occupancy types shall not exceed the maximum height prescribed in Part 4 ‘Fire and Life Safety’.
9.5.1 For buildings in the vicinity of aerodromes, the maximum height of such buildings shall be decided in consultation with the Civil Aviation Authorities. This shall be regulated by the rules for giving no objection certificate for construction of buildings in the vicinity of aerodromes of Directorate General of Civil Aviation, which are given in Annex A. However, the latest rules of Directorate General of Civil Aviation shall be followed in all cases of buildings coming up in the vicinity of an aerodrome.
9.5.1.1 For the purpose of 9.5.1 new buildings, structures which rise to 30 m or more in height and are to be located within 20 km of the aerodrome reference point, shall be constructed only if no objection certificate has been obtained from the Directorate General of Civil Aviation.
9.5.1.2 In the case of buildings to be erected in the vicinity of defence aerodromes, the maximum height of such buildings shall be decided by the Defence Authority.
9.5.2 This will apply specially to new constructions, overhead high voltage/medium voltage lines, telephones/telegraph lines, factories, chimneys, wire/ TV antennas.
9.5.2.1 No new chimneys or smoke producing factories shall be constructed within a radius of 8 km from the aerodrome reference point (ARP).
9.5.2.2 Overhead high voltage/medium voltage lines or telephone/telegraph lines shall not be permitted in the approach/take-off climb areas within 3 000 m of the inner edge of these areas.
9.5.2.3 A 3 m margin shall be allowed in new constructions for wireless/TV antennas, cooling towers and MUMTIES.
9.5.3 Butcheries, tanneries and solid waste disposal sites shall not be permitted within 10 km from the aerodrome reference point.
9.6.1 Group housing development may be in low rise house clusters or multi-storeyed apartments for high density development.
9.6.2 No limit to floors and height shall be applicable, but the coverage and floor area ratio for various densities may be as given in Table 4 unless otherwise provided in the Master Plan and local development control rules.
| Sl No. | Net Residential Density in Dwelling Units/ Hectare | Maximum Coverage in Percent | Floor Area Ratio |
|---|---|---|---|
| (1) | (2) | (3) | (4) |
| i) | 25 | 25 | 0.50 |
| ii) | 50 | 30 | 0.75 |
| iii) | 75 | 33 | 0.90 |
| iv) | 100 | 35 | 1.00 |
| v) | 125 | 35 | 1.25 |
| vi) | 150 | 35 | 1.50 |
| vii) | 175 | 35 | 1.75 |
NOTE — The coverage shall be calculated on the basis of the whole area reserved for group housing.
9.6.3 The minimum size of the site for group housing multi-storeyed apartment shall be 3 000 m2.
9.6.3.1 The number of dwelling units are calculated on the basis of the density pattern given in the Development Plan taking into consideration a population of 4.5 persons per dwelling unit.
9.6.3.2 The basement may vary between 33.33 to 50 percent of the plot area and is to be used for parking, servicing and for essential household storage without counting in FAR.
9.6.3.3 One car parking space for every two flats up to 90 m2 floor area and one for every flat for 100 m2 or more shall be provided.
9.6.4 With a view to providing adequate parking for occupancies and the vehicular load, appropriate offstreet parking provisions have to be made in the building/on-site. This could also be permitted in basement areas and the footprint for the basement parking can exceed the ground coverage of the building subject to no basement building construction
to cross the building line and all other safety features for structural, fire, health and public safety being ensured.
10.1 The off-street parking (on-site parking) spaces in a plot to be provided shall be in accordance with Annex B. The spaces given in Annex B shall be considered by the Authority in conjunction with the Development Rules, in force, if any.
10.2 The spaces to be left out for off-street parking as given in 10.3 to 10.6 shall be in addition to the open spaces left out for lighting and ventilation purposes as given in 15.
10.2.1 Further 50 percent of the open spaces required around buildings under 8 may be allowed to be utilized for parking or loading or unloading spaces, provided a minimum distance of 3.6 m around the building is kept free from any parking, loading or unloading spaces subject to the provisions of Part 4 ‘Fire and Life Safety’.
10.3 Each off-street parking space provided for vehicles shall be as follows:
a) For car, the minimum parking space to be 3 m × 6 m when individual parking space is required and 2.75 m × 5 m when common parking space is required.
b) Space for scooter/two wheeler and bicycle to be not less than 1.25 m2 and 1.00 m2 respectively.
c) Area for each equivalent car space inclusive of circulation area is 23 m2 for open parking, 28 m2 for ground floor covered parking and 32 m2 for basement.
10.4 For buildings of different occupancies, off-street parking space for vehicles shall be provided as stipulated below:
a) Motor Vehicles — Space shall be provided as specified in Annex B for parking motor vehicles (cars).
b) Other Types of Vehicles — For non-residential building, in addition to the parking areas provided in (a) above, 25 to 50 percent additional parking space shall be provided for parking other types of vehicles and the additional spaces required for other vehicles shall be as decided by the Authority, keeping in view the nature of traffic generated in the city.
10.5 Off-street parking space shall be provided with adequate vehicular access to a street; and the area of drives, aisles and such other provisions required for adequate manoeuvering of vehicle shall be exclusive of the parking space stipulated in these provisions.
10.6 If the total parking space required by these provisions is provided by a group of property owners for their mutual benefits, such use of this space may be construed as meeting the off-street parking requirements under these provisions, subject to the approval of the Authority.
Greenbelts and landscaping including plantation of shrubs and trees help to certain extent in enhancing the environmental quality.
11.1.1 Planting of trees in streets and in open spaces should be done carefully to take advantage of both shades and sunshine without obstructing the flow of wind circulation and sight. Their advantage for abating glare and for providing cool and/or warm pockets in developed areas should also be taken.
11.2.1 Suitable provisions may be made for greeneries including plantation of shrubs and trees as a part of environmental protection in general. This aspect shall be taken care of from the initial stage of town and country planning, zoning and planning of development of particular area and group housing. Finally, this aspect shall also be taken into account in planning individual building of different occupancies.
11.2.2 The types of plants, the distance between trees/ plants from the building and the distance between plants shall be carefully worked out keeping in view the structural safety and aesthetic requirements of buildings.
11.3 Trees shall be numbered area-wise, plot-wise and road-wise by the concerned authority and they shall be checked periodically.
11.4 Cutting and pruning of trees in public as well as private areas shall be suitably regulated. Trees shall be cut only after obtaining the permission of the Authority designated for this purpose.
11.5 The landscape planning and design shall be done in accordance with Part 10 ‘Landscaping, Signs and Outdoor Display Structures, Section 1 Landscape Planning and Design’.
In view of critical shortage of water, conservation of water by rain water harvesting and by use of recycled water to the maximum extent possible will be required. In this regard the following provisions may be adopted.
11.6.1 The local authority preparing a town-planning scheme or a development plan should see that the local water bodies are preserved, and if dry, are activated by directing water-courses appropriately. If required, the same should be enlarged, deepened, etc.
11.6.2 The water body should be protected by ensuring that no permanent/temporary construction development takes place around it up to a distance of 50 m from the edge of the water body and the same shall be suitably landscaped. Further, the public shall have easy access to the water body.
The plinth or any part of a building or outhouse shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 450 mm from the surrounding ground level.
Every interior courtyard shall be raised at least 150 mm
above the determining ground level and shall be satisfactorily drained.
The height of a kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom slab) shall not be less than 2.75 m, except for the portion to accommodate floor trap of the upper floor.
The area of a kitchen where separate dining area is provided, shall be not less than 5.0 m2 with a minimum width of 1.8 m. Where there is a separate store, the area of the kitchen may be reduced to 4.5 m2. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 m2 with a minimum width of 2.1 m.
Every room to be used as kitchen shall have:
a) unless separately provided in a pantry, means for the washing of kitchen utensils which
shall lead directly or through a sink to a grated and trapped connection to the waste pipe;
b) an impermeable floor;
c) a flue, if found necessary; and
d) a window or ventilator or opening of size not less than as specified in 15.1.1 subject to increase in area of opening in accordance with Note 3 of 15.1.2.
The height of a bathroom or water-closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.1 m.
The area of a bathroom shall not be less than 1.8 m2 with a minimum width of 1.2 m. The floor area of water-closet shall be 1.1 m2 with a minimum width of 0.9 m. If bath and water-closet are combined, its floor area shall not be less than 2.8 m2 with a minimum width of 1.2 m.
Every bathroom or water-closet shall:
a) be so situated that at least one of its walls shall open to external air;
b) not be directly over or under any room other than another water-closet, washing place, bath or terrace, unless it has a water-tight floor;
c) have the platform or seat made of water-tight non-absorbent material;
d) be enclosed by walls or partitions and the surface of every such wall or partition shall be finished with a smooth impervious material to a height of not less than 1 m above the floor of such a room;
e) be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards VERANDAH or any other room; and
f) have a window or ventilator, opening to a shaft or open space, of area not less than 0.3 m2 with side not less than 0.3 m.
12.4.4 No room containing water-closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
The minimum head-room of ledge or TAND/loft shall be 2.2 m. The maximum height of loft shall be 1.5 m.
A ledge or TAND/loft in a habitable room shall not cover more than 25 percent of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
It shall have a minimum height of 2.2 m.
The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5 m2. The aggregate area of such mezzanine floor in a building shall in no case exceed one-third the plinth area of the building.
A mezzanine floor may be permitted over a room or a compartment provided:
a) it conform to the standard of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.5 m2 or more (see 14.1.2);
b) it is so constructed as not to interfere under any circumstances with the ventilation of the space over and under it;
c) such mezzanine floor is not sub-divided into smaller compartments;
d) such mezzanine floor or any part of it shall not be used as a kitchen; and
e) in no case shall a mezzanine floor be closed so as to make it liable to be converted into unventilated compartments.
The height of a store room shall be not less than 2.2 m.
The size of a store room, where provided in a residential building, shall be not less than 3 m2.
The height of a garage shall be not less than 2.4 m.
The size of garages shall be as below:
a) Private Garage — 3.0 m × 6.0 m, minimum; and
b) Public Garage — Based on the number of vehicles parked, etc (see 10).
Land Area Required, Min
| Land Area Required, Min | ||
| 6) | General hospital (1 for every 250 000 population) | |
| i) Capacity 500 beds (initially the provision may be for 300 beds) | ||
| ii) Total area | 6.00 ha | |
| a) Area for hospital | 4.00 ha | |
| b) Area for residential accommodation | 2.00 ha | |
| 7) | Multi-speciality hospital (1 for 100 000 population) | |
| i) Capacity 200 beds (initially the provision may be for 100 beds) | ||
| ii) Total area | 9.00 ha | |
| a) Area for hospital | 6.00 ha | |
| b) Area for residential accommodation | 3.00 ha | |
| 8) | Speciality hospital (1 for every 100 000 population) | |
| i) Capacity 200 beds (initially the provision may be for 100 beds) | ||
| ii) Total area | 3.70 ha | |
| a) Area for hospital | 2.70 ha | |
| b) Area for residential accommodation | 1.00 ha | |
| Land Area Required, Min | |
| 1) Community room (1 for every 5 000 population) | |
| Area | 750 m² |
| 2) Community hall, mangal karyayala/kalyana mandapam/barat ghar/library(1 for every 15 000 population) | |
| Area | 2 000 m² |
| 3) Recreational club (1 for every 100 000 population) (see also 5.2, 5.2.1, 5.2.2 and 5.3) | |
| Area | 10 000 m² |
| 4) Music, dance and drama centre (1 for every 100 000 population) | |
| Area | 1 000 m² |
| 5) Meditation and spiritual centre (1 for every 100 000 population) | |
| Area | 5 000 m² |
| 6) Socio-cultural centre (1 for every 1 000 000 population) | |
| Area | 15 ha |
| 1) Petrol/diesel filling and servicing centreMay be permitted in central as well as sub-central business district, district centres, community centres (only filling station), residential and industrial use zones in urban areas, along the national highways, state highways, villages identified as growth centres, freight complex and on proposed major roads.Shall not be located on the road having right of way less than 30 m.Shall be approved by the explosive/fire department.Area/Sizei) Only filling stationii) Filling-cum-service stationiii) Filing-cum-service station-cum-workshopiv) Filling station only for two and three wheelers | 30 m × 17 m36 m × 30 m45 m × 36 m18 m × 15 m |
|---|---|
| 2) Compressed natural gas (CNG)/filling centrePermitted in all use zones (except in regional parks and Developed District Parks) and along the national highways, state highways and villages identified as growth centres, freight complex and on proposed major roads |
| Land Area Required, Min | ||
| Shall not be located on the road having right of way less than 30 m.Shall be approved by the explosive/fire department.Area/size for mother station (building component—control room/office/dispensing room, store, pantry and W.C. | 1 080 m² (36 m × 30 m) | |
| 3) LPG godowns/Gas godown 1 for every 40 000 to 50 000 populationThe major concern for its storage and distribution is the location which shall be away from the residential areas and shall have open spaces all around as per the Explosive Rules.i) Capacity — 500 cylinders or 8 000 kg of LPGii) Area (inclusive of chowkidar hut) | 520 m² (26 m × 20 m) | |
| 4) Milk distribution (1 milk booth for every 5 000 population)Area inclusive of service area | 150 m² | |
| Land Area Required, Min | |
| 1) Police station (1 for every 90 000 population) | |
| Area (inclusive of essential residential accommodation 0.05 ha additional to be provided for civil defence and home guards) | 1.50 ha |
| 2) Police post (1 for every 40 000 to 50 000 population) (not served by a police station) | |
| Area (inclusive of essential residential accommodation) | 0.16 ha |
| 3) District office and battalion (1 for every 1 000 000 population) | |
| i) Area for district office | 0.80 ha |
| ii) Area for battalion | 4.00 ha |
| iii) Total area | 4.80 ha |
| 4) Police line (1 for every 2 000 000 population) | |
| Area | 4.00 to 6.00 ha |
| 5) District Jail (1 for every 1 000 000 population) | |
| Area | 10.00 ha |
| 6) Civil defence and home guards (1 for every 1 000 000 population) | |
| Area | 2.00 ha |
| Land Area Required, Min | ||
| One fire station or sub-fire station within 1 km to 3 km (for every 200 000 population) | ||
| i) | Area for fire station with essential residential accommodation | 1.00 ha |
| ii) | Area for sub-fire station with essential residential accommodation | 0.60 ha |
Land Area Required, Min
Telephone exchange of 40 000 lines (1 for every 400 000 population) Area 4.00 ha
Telegraph booking counter (1 for every 100 000 population) Floor area to be provided in community centre 200 m2
Telegraph booking and delivery office (1 for every 500 000 population) Floor area to be provided in district centres 1 700 m2
Land Area Required, Min
Post office counter without delivery (1 for every 15 000 population) Floor area to be provided in local shopping centre 85 m2
Head post office with delivery office (1 for 250 000 population) Area 750 m2
Head post office and administrative office (1 for 500 000 population) Area 2 500 m2
District sport centre (1 for 100 000 population) Area 8.00 ha
Neighbourhood play area (1 for 15 000 population) Area 1.50 ha
Residential unit play area (1 for 5 000 population) Area 5 000 m2
Local shopping including service centre (1 for 15 000 population) Area 4 600 m2
Community centre with service centre (1 for 100 000 population) Area 5.00 ha
District centre (1 at district level/1 for 500 000 population) Area 7.50 ha
Local wholesale market (1 for 1 000 000 population) Area 10.00 ha
| Land Area Required, Min | |
|---|---|
| 1) Electric crematorium (1 for large size towns) | |
| Area | 2.00 ha |
| 2) Cremation ground (1 for 500 000 population) | |
| Area | 2.50 ha |
| 3) Burial ground (1 for 500 000 population) | |
| Area | 4.00 ha |
| 1) Religious campus (1 for 100 000 population) | Land Area Required, Min |
|---|---|
| Area | 5.00 ha |
| 5.5.11 Electrical Sub-station | |
| 1) 11 kV Sub-station (1 for 15 000 population) | Land Area Required, Min |
| Area | 500 m<sup>2</sup> |
| 2) 66 kV Sub-station (2 for 100 000 population) | |
| Area for each Sub-station | 6 000 m<sup>2</sup> (that is 60 m × 100 m) |
| 3) 220 kV Sub-station (1 for 500 000 population) | |
| Area | 4.00 ha |
| Land Area Required, Min | |
| 1) Three wheeler and taxi stand (1 for 15 000 population) | |
| Area | 500 m² |
| 2) Bus terminal (1 for 100 000 population) | |
| Area | 4 000 m² |
| 3) Bus depot (1 for 500 000 population) | |
| Area | 2.00 ha |
The site shall be identified in locations, which are not proximous to residential areas
| Land Area Required, Min | |
|---|---|
| 1) Dhobi ghat with appropriate arrangements for water and drainage facilities and it shall be ensured that the water bodies are not polluted as a result of such activities (1 for 100 000 population) | |
| Area | 5 000 m² |
5.6 Every layout or sub-division shall take into account the provisions of development plan and if the land is affected by any reservation for public purposes, the Authority may agree to adjust the location of such reservations to suit the development.
a) No sunshade shall be permitted over the road or over any drain or over any portion outside the boundaries of the site below a height of 2.8 m from the road level;
b) Sunshades provided above a height of 2.8 m from the ground level shall be permitted to project up to a maximum width of 60 cm, if the road over which they project exceeds 9 m in width; and
c) No sunshade shall be permitted on roads less than 9 m in width or on roads having no footpaths.
10.7 In buildings of mercantile (commercial), industrial and storage type, in addition to the parking spaces provided, a space at the rate of 3.5 m × 7.5 m, shall be provided for loading and unloading activities, for each 1 000 m2 of floor area or fraction thereof.
10.8 Parking spaces shall be paved and clearly marked for different types of vehicles.
10.9 Apart from parking at ground level, provision of underground or multistoreyed parking may be permitted. The parking of vehicles at different level may also be mechanized. In the case of parking spaces provided in basement(s), at least two ramps of adequate width and slope shall be provided, located preferably at opposite ends. In case of underground/multistoreyed parking, special measures with regard to fire safety shall be taken (see Part 4 ‘Fire and Life Safety’).
11.6.3 The rain water run-off shall be suitably directed to Recharging Wells in plots belonging to the local authority and of appropriate design.
11.6.4 The local authority should encourage for collection of rain water from roofs and terraces and direct the same either to a storage tank or to a recharging well.
11.6.5 Buildings having central air-conditioning plants requiring water for cooling purposes may not be allowed to use fresh water for the purpose.
11.6.6 Commercial or residential multi-storey complexes may use recycled water for flushing of toilets. Separate storage tanks and separate distribution pipes shall be provided for the purpose.
12.9.1 The basement shall not be used for residential purposes.
12.9.2 The construction of the basement shall be allowed by the Authority in accordance with the land use and other provisions specified under the Development Control Rules.
12.9.2.1 The basement to be constructed within the building envelope and subject to maximum coverage on floor 1 (entrance floor) may be put to only the following uses:
a) Storage of household or other goods of ordinarily non-combustible material;
b) Strong rooms, bank cellars, etc;
c) Air-conditioning equipment and other machines used for services and utilities of the building; and
d) Parking spaces.
12.9.3 The basement shall have the following requirements:
a) Every basement shall be in every part at least 2.4 m in height from the floor to the underside of the roof slab or ceiling;
b) Adequate ventilation shall be provided for the basement. The ventilation requirements shall be the same as required by the particular occupancy according to byelaws. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air-conditioning systems, etc;
c) The minimum height of the ceiling of any basement shall be 0.9 m and the maximum, 1.2 m above the average surrounding ground level;
d) Adequate arrangements shall be made such that surface drainage does not enter the basement;
e) The walls and floors of the basement shall be watertight and be so designed that the effects of the surrounding soil and moisture, if any, are taken into account in design and adequate damp proofing treatment is given; and
f) The access to the basement shall be separate from the main and alternative staircase
providing access and exit from higher floors. Where the staircase is continuous in the case of buildings served by more than one staircase, the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors. Open ramps shall be permitted if they are constructed within the building line subject to the provision of (d).
The exist requirements in basements shall comply with the provisions of Part 4 ‘Fire and Life Safety’.
The chimneys shall be built at least 0.9 m above flat roofs, provided the top of the chimneys is not below the top of the adjacent parapet wall. In the case of sloping roofs, the chimney top shall not be less than 0.6 m above the ridge of the roof in which the chimney penetrates.
Parapet walls and handrails provided on the edges of roof terraces, balcony, VARANDAH, etc shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level.
The size of cabins shall not be less than 3.0 m2 with a minimum width of 1.0 m. The clear passages within the divided space of any floor shall not be less than 0.75 m and the distance from the farthest space in a cabin to any exit shall not be more than 18.5 m. In case the sub-divided cabin does not derive direct lighting and ventilation from any open spaces/ mechanical means, the maximum height of the cabin shall be 2.2 m.
12.13.1 The requirements of the boundary wall are given below:
a) Except with the special permission of the Authority, the maximum height of the compound wall shall be 1.5 m above the centre line of the front street. Compound wall up to 2.4 m height may be permitted if the top 0.9 m is of open type construction of a design to be approved by the Authority.
b) In the case of a corner plot, the height of the boundary wall shall be restricted to 0.75 m for a length of 10 m on the front and side of the inter-sections and the balance height of 0.75 m if required in accordance with (a) may be made up of open type construction (through railings) and of design to be approved by the Authority.
c) However, the provisions of (a) and (b) are not
applicable to boundary walls of jails. In industrial buildings, electric sub-stations, transformer stations, institutional buildings like sanitoria, hospitals, industrial buildings like workshops, factories and educational buildings like schools, colleges, including hostels, and other uses of public utility undertakings and strategically sensitive buildings, a height up to 2.4 m may be permitted by the Authority.
Wells, intended to supply water for human consumption or domestic purposes, where provided, shall comply with the requirements of 12.14.1 and 12.14.2.
The well shall be located:
a) not less than 15 m from any ash pit, refuse pit, earth closet or privy and shall be located on a site upwards from the earth closet or privy;
b) not less than 18 m from any cess pit soakway or borehole latrine and shall be located on a site upwards from the earth closet or privy;
c) that contamination by the movement of subsoil or other water is unlikely; and
d) not under a tree or otherwise it should have a canopy over it, so that leaves and twigs may not fall into the well and rot.
The well shall:
a) have a minimum internal diameter of not less than 1 m;
b) be constructed to a height not less than 1 m above the surrounding ground level, to form a parapet or kerb and to prevent surface water from flowing into a well, and shall be surrounded with a paving constructed of impervious material which shall extend for a distance of not less than 1.8 m in every direction from the parapet from the kerb forming the well head and the upper surface of such a paving shall be sloped away from the well;
c) be of sound and permanent construction (PUCCA) throughout. Temporary or exposed (KUTCHA) wells shall be permitted only in fields or gardens for purposes of irrigation; and
d) have the interior surface of the lining or walls of the well be rendered impervious for a depth of not less than 1.8 m measured from the level of the ground immediately adjoining the well-head.
Where a septic tank is used for sewage disposal, the location, design and construction of the septic tank shall conform to requirements of 12.15.1 and 12.15.2 [see also Part 9 ‘Plumbing Services, Section 1 Water Supply, Drainage and Sanitation (Including Solid Waste Management)’].
A sub-soil dispersion system shall not be closer than 18 m from any source of drinking water, such as well, to mitigate the possibility of bacterial pollution of water supply. It shall also be as far removed from the nearest habitable building as economically feasible but not closer than 6 m, to avoid damage to the structures.
a) Dimensions of septic tanks — Septic tanks shall have a minimum width of 750 mm, a minimum depth of 1 m below the water level and a minimum liquid capacity of 1 m3. The length of tanks shall be 2 to 4 times the width;
b) Septic tanks may be constructed of brickwork, stone masonry, concrete or other suitable materials as approved by the Authority;
c) Under no circumstances shall effluent from a septic tank be allowed into an open channel drain or body of water without adequate treatment;
d) The minimum nominal diameter of the pipe shall be 100 mm. Further, at junctions of pipes in manholes, direction of flow from a branch connection shall not make an angle exceeding 45° with the direction of flow in the main pipe;
e) The gradients of land drains, under-drainage as well as the bottom of dispersion trenches and soakways shall be between 1:300 and 1:400;
f) Every septic tank shall be provided with ventilating pipe of at least 50 mm diameter. The top of the pipe shall be provided with a suitable cage of mosquito-proof wire mesh.
The ventilating pipe shall extend to a height which would cause no smell nuisance to any building in the area. Generally, the ventilating pipe may extend to a height of about 2 m, when the septic tank is at least 15 m away from the nearest building and to a height of 2 m above the top of the building when it is located closer than 15 m;
g) When the disposal of septic tank effluent is to a seepage pit, the seepage pit may be of any suitable shape with the least cross-
sectional dimension of 0.90 m and not less than 1.00 m in depth below the invert level of the inlet pipe. The pit may be lined with stone, brick or concrete blocks with dry open joints which should be backed with at least 75 mm of clean coarse aggregate. The lining above the inlet level should be finished with mortar. In the case of pits of large dimensions, the top portion may be narrowed to reduce the size of the RCC cover slabs. Where no lining is used, specially near trees, the entire pit should be filled with loose stones. A masonry ring may be constructed at the top of the pit to prevent damage by flooding of the pit by surface runoff. The inlet pipe may be taken down a depth of 0.90 m from the top as an anti-mosquito measure; and
h) When the disposal of the septic tank effluent is to a dispersion trench, the dispersion trench shall be 0.50 m to 1.00 m deep and 0.30 m to 1.00 m wide excavated to a slight gradient and shall be provided with 150 mm to 250 mm of washed gravel or crushed stones. Open jointed pipes placed inside the trench shall be made of unglazed earthenware clay or concrete and shall have a minimum internal diameter of 75 mm to 100 mm. Each dispersion trench shall not be longer than 30 m and trenches shall not be placed closer than 1.8 m.
In the case of multi-storeyed multi-family dwelling apartments constructed by existing and proposed Cooperative Housing Societies or Apartment Owners Associations, limited companies and proposed societies, an office-cum-letter box room of dimension 3.6 m × 3 m shall be provided on the ground floor. In case the number of flats is more than 20, the maximum size of the office-cum-letter box room shall be 20 m2.
Provision shall be made for letter boxes on the entrance floor as per the requirements of the postal department.
For all buildings above 15 m in height and in special occupancies, like educational, assembly, institutional, industrial, storage, hazardous and mixed occupancies with any of the aforesaid occupancies having area more than 500 m2 on each floor, provision shall be made for an independent and ventilated meter (service) room, as per requirements of electric (service) supply undertakings on the ground floor with direct access from outside for the purpose of termination of electric
supply from the licensee’s service and alternative supply cables. The door/doors provided for the service room shall have fire resistance of not less than two hours.
12.18.1 The minimum clear width, minimum tread width and maximum riser of staircases for buildings shall be as given in 12.18.1.1 to 12.18.1.3 (see also Part 4 ‘Fire and Life Safety’).
12.18.1.1 Minimum width — The minimum width of staircase shall be as follows:
a) Residential buildings (dwellings) 1.0 m NOTE — For row housing with 2 storeys, the minimum width shall be 0.75 m.
b) Residential hotel buildings 1.5 m
c) Assembly buildings like 2.0 m auditoria, theatres and cinemas
d) Educational building 1.5 m
e) Institutional buildings 2.0 m
f) All other buildings 1.5 m
The minimum width of tread without nosing shall be 250 mm for residential buildings. The minimum width of tread for other buildings shall be 300 mm.
The maximum height of riser shall be 190 mm for residential buildings and 150 mm for other buildings and these shall be limited to 12 per flight.
12.18.2 The minimum head-room in a passage under the landing of a staircase shall be 2.2 m. The minimum clear head-room in any staircase shall be 2.2 m.
All aspects of exit requirements for corridors, doors, stair cases, ramps, etc in respect of widths, travel distance shall be as per Part 4 ‘Fire and Life Safety’.
12.19.1 The roof of a building shall be so designed and constructed as to effectively drain water by means of sufficient rain-water pipes of adequate size, wherever required, so arranged, jointed and fixed as to ensure that the rain-water is carried away from the building without causing dampness in any part of the walls, roof or foundations of the building or an adjacent building.
12.19.2 The Authority may require rain-water pipes to be connected to a drain or sewer to a covered channel formed beneath the public footpath to connect the rain-
water pipe to the road gutter or in any other approved manner.
12.19.3 Rain-water pipes shall be affixed to the outside of the external walls of the building or in recesses or chases cut or formed in such external walls or in such other manner as may be approved by the Authority.
12.19.4 It is desirable to conserve rain water using suitable rain water harvesting techniques including by roof water collection. In this context, reference may be made to Part 9 ‘Plumbing Services, Section 1 Water Supply, Drainage and Sanitation (Including Solid Waste Management)’.
Special requirements of low income housing shall be as given in Annex C. For detailed information in this regard, reference may be made to the accepted standards [3(1)].
Special requirements for planning of buildings and facilities keeping in view the needs of the physically challenged, applicable particularly to public buildings meant for their use, are given in Annex D.
Special requirements for cluster planning for housing shall be as given in Annex E.
Special requirements for low income habitat planning in rural areas shall be as given in Annex F.
Special requirements for development planning in hilly areas is given in Annex G.
15.1 For requirements regarding lighting and
ventilation for different uses and occupancies, reference shall be made to Part 8 ‘Building Services, Section 1 Lighting and Ventilation’.
Rooms shall have, for the admission of light and air, one or more openings, such as windows and ventilators, opening directly to the external air or into an open VERANDAH.
15.1.2 Notwithstanding the area of openings obtained through 15.1, the minimum aggregate area (see Notes 1 to 3) of such openings, excluding doors inclusive of frames, shall be not less than:
a) one-tenth of the floor area for dry hot climate;
b) one-sixth of the floor area for wet hot climate;
c) one-eighth of the floor area for intermediate climate; and
d) one-twelfth of the floor area for cold climate. NOTES
1 If a window is partly fixed, the openable area shall be counted.
2 No portion of a room shall be assumed to be lighted, if it is more than 7.5 m away from the opening assumed for lighting that portion.
3 The area of openings as given in (a) to (d) above shall be increased by 25 percent in the case of a kitchen [see 12.3.3(d)].
Provision for lifts shall be made for buildings 15 m or more in height. For requirements regarding planning, designing and installation, etc of lifts and escalators, reference shall be made to Part 8 ‘Building Services, Section 5 Installation of Lifts and Escalators’.